期刊文献+
共找到4篇文章
< 1 >
每页显示 20 50 100
Arcing Model of a Disconnector and its Effect on VFTO 被引量:6
1
作者 林莘 王娜 徐建源 《Plasma Science and Technology》 SCIE EI CAS CSCD 2013年第7期644-647,共4页
In the computational process of very fast transient over-voltage (VFTO), it is essen-tial to find an accurate model for a gas insulated substation. The arcing model of the disconnector is particularly important. The... In the computational process of very fast transient over-voltage (VFTO), it is essen-tial to find an accurate model for a gas insulated substation. The arcing model of the disconnector is particularly important. The general arcing model is not able to give a good description of the arc development process. In this paper, based on the physical process of arcing and existing arc models (the exponential time-varying resistance model and the segmental arcing models), a dy- namic arcing model is proposed, which is divided into two stages before and after the zero crossing. The dynamic arcing model combines hyperbola time-varying resistance and the Mayr model to describe the dynamic process of arcing. The present paper creates an arc model blockset upon the Matlab/Simulink software platform. Moreover for a specific 1100 kV station, VFTO is simulated in detail based on different arcing models. It is demonstrated that the dynamic arcing model can describe the physical arc process precisely and is useful for improving the accuracy of VFTO simulations. 展开更多
关键词 disconnector switching UHV dynamic arcing model gas insulated substa-tion VFTO
下载PDF
Statistical characteristics of transient enclosure voltage in ultra-high-voltage gas-insulated switchgear 被引量:2
2
作者 Yuanji CAI Yonggang GUAN Weidong LIU 《Plasma Science and Technology》 SCIE EI CAS CSCD 2017年第6期74-81,共8页
Transient enclosure voltage(TEV),which is a phenomenon induced by the inner dielectric breakdown of SF_6 during disconnector operations in a gas-insulated switchgear(GIS),may cause issues relating to shock hazard ... Transient enclosure voltage(TEV),which is a phenomenon induced by the inner dielectric breakdown of SF_6 during disconnector operations in a gas-insulated switchgear(GIS),may cause issues relating to shock hazard and electromagnetic interference to secondary equipment.This is a critical factor regarding the electromagnetic compatibility of ultra-high-voltage(UHV)substations.In this paper,the statistical characteristics of TEV at UHV level are collected from field experiments,and are analyzed and compared to those from a repeated strike process.The TEV waveforms during disconnector operations are recorded by a self-developed measurement system first.Then,statistical characteristics,such as the pulse number,duration of pulses,frequency components,magnitude and single pulse duration,are extracted.The transmission line theory is introduced to analyze the TEV and is validated by the experimental results.Finally,the relationship between the TEV and the repeated strike process is analyzed.This proves that the pulse voltage of the TEV is proportional to the corresponding breakdown voltage.The results contribute to the definition of the standard testing waveform of the TEV,and can aid the protection of electronic devices in substations by minimizing the threat of this phenomenon. 展开更多
关键词 transient enclosure voltage (TEV) gas-insulated switchgear (GIS) ultra-high-voltage (UHV) repeated strike process DISCONNECTOR
下载PDF
Repeated Strike Process During Disconnector Operation in Ultra-High Voltage Gas-Insulated Switchgear 被引量:1
3
作者 关永刚 蔡元纪 +4 位作者 陈维江 刘卫东 李志兵 岳功昌 张俊民 《Plasma Science and Technology》 SCIE EI CAS CSCD 2016年第3期247-253,共7页
Very fast transient over-voltage (VFTO), induced by disconnector operations in gas- insulated switchgears, has become the limiting dielectric stress at ultra-high voltage levels. Much work has been done to investiga... Very fast transient over-voltage (VFTO), induced by disconnector operations in gas- insulated switchgears, has become the limiting dielectric stress at ultra-high voltage levels. Much work has been done to investigate single-strike waveforms of VFTO. However, little study has been carried out investigating the repeated strike process, which would influence VFTO significantly. In this paper, we carried out 450 effective experiments in an ultra-high voltage test circuit, and conducted calculations through the Monte Carlo simulation method, to investigate the repeated strike process. Firstly, the mechanism of the repeated strike process is proposed, based on the ex- perimentai results. Afterwards, statistical breakdown characteristics of disconnectors are obtained and analyzed. Finally, simulations of the repeated strike process are conducted, which indicate that the dielectric strength recovery speed and polarity effect factor have a joint effect on VFTO. This study enhances the understanding of the nature of VFTO, and may help to optimize the disconnector designed to minimize VFTO. 展开更多
关键词 disconnector (DS) repeated strike process DISCHARGE statistical breakdowncharacteristics ultra-high voltage (UHV) very fast transient over-voltage (VFTO)
下载PDF
Protection of Low Voltage CIGRE Distribution Network 被引量:1
4
作者 Ghullam Mustafa Bhutto Birgitte Bak-Jensen +1 位作者 Claus Leth Bak Jayakrishnan R. Pillai 《Smart Grid and Renewable Energy》 2013年第9期489-500,共12页
High quality electricity services are the prime objectives in the modern power systems around the world. One of the main players to achieve this is the protection of the system which needs to be fast, reliable and cos... High quality electricity services are the prime objectives in the modern power systems around the world. One of the main players to achieve this is the protection of the system which needs to be fast, reliable and cost effective. The study about the protection of the Low Voltage (LV) CIGRE distribution grid and networks like this has been proposed in this paper. The main objective of this paper is to develop protection against short circuit faults which might appear anywhere in the network. The protection of the power networks that comprises of renewable energy generation units is complicated because of the bidirectional flow of the current and is a challenge for the protection engineers. The selection of the protection devices in this paper is made to protect the network against faults in grid connected and island mode of operation. Ultra-fast fuses are proposed in order to protect the inverters used for Photovoltaic (PV) and battery applications. The disconnection of the PV solar panels when in island mode is made by proposing switch disconnecting devices. ABB is currently using these kinds of disconnection devices for the purpose of protecting solar panels against over voltages in the case of islanding. The over speed protection of the existing Wind Turbine Generator (WTG) in the CIGRE network in case of grid loss is also proposed in this paper. 展开更多
关键词 Current BASED PROTECTION VOLTAGE BASED PROTECTION Over Speed PROTECTION Fuse Under VOLTAGE Relay Circuit BREAKER Switch DISCONNECTOR
下载PDF
上一页 1 下一页 到第
使用帮助 返回顶部