To reduce current harmonics caused by switching frequency,T-type grid-connected inverter topology with LCL filter is adopted.In view of the disadvantages of the slow response speed of the traditional current control a...To reduce current harmonics caused by switching frequency,T-type grid-connected inverter topology with LCL filter is adopted.In view of the disadvantages of the slow response speed of the traditional current control and the failure to eliminate the influence of the LCL filter on the grid-connected current by using current PI control alone,a current double closed loop PI current tracking control is proposed.Through the theoretical analysis of the grid-connected inverter control principle,the grid-connected inverter control model is designed,and the transfer functionmodel of each control link is deduced,and the current loop PI regulator is designed at last.The simulation results show that the control strategy is feasible.展开更多
基金Supported by Science and Technology Projects of State Grid Corporation ofChina(J2022019).
文摘To reduce current harmonics caused by switching frequency,T-type grid-connected inverter topology with LCL filter is adopted.In view of the disadvantages of the slow response speed of the traditional current control and the failure to eliminate the influence of the LCL filter on the grid-connected current by using current PI control alone,a current double closed loop PI current tracking control is proposed.Through the theoretical analysis of the grid-connected inverter control principle,the grid-connected inverter control model is designed,and the transfer functionmodel of each control link is deduced,and the current loop PI regulator is designed at last.The simulation results show that the control strategy is feasible.