Dynamic physical characteristics of DC arc on arcing horn for HVDC grounding electrode line
1
作者 刘益岑 杨晨光 +4 位作者 郭裕钧 张血琴 肖嵩 高国强 吴广宁 《Plasma Science and Technology》 SCIE EI CAS CSCD 2023年第1期80-87,共8页
The dynamic physical characteristics of a DC arc on an arcing horn for a high voltage direct current(HVDC)grounding electrode line are significantly different from those of the switching device arc,secondary arc,AC fa... The dynamic physical characteristics of a DC arc on an arcing horn for a high voltage direct current(HVDC)grounding electrode line are significantly different from those of the switching device arc,secondary arc,AC fault arc and pantograph-catenary arc.In this work,an experimental platform for the DC arc on the arcing horn was built,and mechanisms of the arc column short circuit and arc root movement were studied.This work further analyzes the characteristics and mechanisms of the arc motion when wind speed and direction,magnetic field and the expansion angle of the electrode are varied.Arc root movement is more likely to occur at the upper electrode.There is a competitive relationship between arc expansion and the transferring effect.The effect of wind on the arc column is greater than the effect on the arc root.The magnetic field has a significant driving effect on both the arc column and the arc root.The research results provide a comprehensive experimental basis for forther probing the method of DC arc suppression,and the improvement of the arcing horn. 展开更多
关键词 grounding electrode line arcing horn DC arc dynamic physical characteristics
下载PDF
Measured Impedance and Threshold Value of Electrode Line Impedance Supervision Based Protection in HVDC Transmission System
2
作者 Qiang Sun Bin Li +1 位作者 Jiawei He Ye Li 《Journal of Modern Power Systems and Clean Energy》 SCIE EI CSCD 2023年第4期1294-1304,共11页
At present,electrode line impedance supervision(ELIS)based protection is widely used to detect faults on grounding electrode lines,which are indispensable elements of high-voltage direct current(HVDC)systems.The exist... At present,electrode line impedance supervision(ELIS)based protection is widely used to detect faults on grounding electrode lines,which are indispensable elements of high-voltage direct current(HVDC)systems.The existing theoretical analysis of measured impedance is based on lumped line model and the threshold value is generally set according to engineering experience,which have caused the dead zone problem and even accidents.Therefore,a study on measured impedance of ELIS-based protection and its threshold value selection method is carried out to solve this problem.In this study,the expressions of measured impedance under normal operation and fault conditions are deduced based on rigorous and accurate line model.Based on the expressions,the characteristics of the measured impedance are calculated and analyzed.With the characteristics of the measured impedance,the applicability of the protection with the traditional threshold value is further discussed and the distribution of the dead zone can be located.Then,the method to calculate the threshold value of ELIS-based protection is proposed.With a proper threshold value selected by the proposed method,the dead zone of ELIS-based protection is effectively eliminated,and the protection can identify all types of faults even with large transition resistances.Case studies on PSCAD/EMTDC have been conducted to verify the conclusion. 展开更多
关键词 Grounding electrode line electrode line impedance supervision(ELIS)based protection measured impedance characteristic threshold value selection