A mathematical model was built for simulating an innovative design system combined solar energy with biogas boiler for floor radiant heating and fuel. Effects of the ambient air temperature on the performance of the s...A mathematical model was built for simulating an innovative design system combined solar energy with biogas boiler for floor radiant heating and fuel. Effects of the ambient air temperature on the performance of the system had been examined. And the results also support theoretical feasibility of the system.展开更多
In order to improve the heat transfer characteristics of the traditional phase change material(PCM) floor, a new double-layer radiant floor system with PCM is proposed, which can store thermal or cold energy in the ...In order to improve the heat transfer characteristics of the traditional phase change material(PCM) floor, a new double-layer radiant floor system with PCM is proposed, which can store thermal or cold energy in the off-peak period and use them in the peak period. An experimental setup was developed to study the heat transfer characteristics of the new system under both cooling and heating modes. The experimental results show that the double-layer radiant floor system with PCM can meet both the cold and thermal requirements of users. Moreover, with the same duration of the thermal energy storage process, the increase of water temperature supplied to the system can improve the heat transfer characteristics of the system but lead to the discomfort of users. On the other hand, if the air temperature at the end of the thermal energy storage process is the same under different conditions, the increase of supplied water temperature will decrease the thermal energy storage time and ensure the comfort of users.展开更多
To evaluate the thermal performance of a low-temperature electrical radiant floor heating system,an experimental facility equipped with a constant temperature chamber and different specimen floors is designed and buil...To evaluate the thermal performance of a low-temperature electrical radiant floor heating system,an experimental facility equipped with a constant temperature chamber and different specimen floors is designed and built.The heating cable is installed in the floor slab with a unit-rated power of 30 W/m.Twenty-four different schemes are worked out and tested,which include three kinds of composite floor structures and eight kinds of cable distances.The cable distances are 30,40,50,60,80,100,130,150 mm.The main affective factors of the thermal performance and their influencing regularity are discussed.The experimental results show that the system has good stability and reliability,and the ratio of the radiation heat-transfer rate to the gross heat-transfer rate is greater than 50%.When the floor structure and the cable distance are fixed,the gross heat-transfer rate of the upper floor surface has a maximum value at an optimal cable distance.Under the experimental conditions in this paper,the optimal cable distance is 50 mm.展开更多
The feasibility of adopting a balanced energy mix mode (domestic solar energy, biogas, coal-fired boiler and radiant floor heating) was proposed. Taking a typical rural residence in Zhengzhou City for example, the stu...The feasibility of adopting a balanced energy mix mode (domestic solar energy, biogas, coal-fired boiler and radiant floor heating) was proposed. Taking a typical rural residence in Zhengzhou City for example, the study through theoretical analysis and calculation showed that such a balanced energy mix is an economic way and efficient in saving energy and reducing air pollution, and elaborated the theoretical feasibility of popularizing such a heat supply mode in rural areas.展开更多
Pre-dehumidification time(τ_(pre))and pre-dehumidification energy consumption(E_(pre))play important roles in preventing the condensation of moisture on the floors of rooms that use a radiant floor cooling(RFC)system...Pre-dehumidification time(τ_(pre))and pre-dehumidification energy consumption(E_(pre))play important roles in preventing the condensation of moisture on the floors of rooms that use a radiant floor cooling(RFC)system.However,there are few theoretical or experimental studies that focus on these two important quantities.In this study,an artificial neural network(ANN)was used to predict condensation risk for the integration of RFC systems with mixed ventilation(MV),stratum ventilation(SV),and displacement ventilation(DV)systems.A genetic algorithm-back-propagation(GA-BP)neural network model was established to predict τ_(pre) and E_(pre).Both training data and validation data were obtained from tests in a computational fluid dynamics(CFD)simulation.The results show that the established GA-BP model can predict τ_(pre) and E_(pre) well.The coefficient of determination(R^(2))of τ_(pre) and of E_(pre) were,respectively,0.973 and 0.956.For an RFC system integrated with an MV,SV,or DV system,the lowest values of τ_(pre) and E_(pre) were with the DV system,23.1 s and 0.237 kWh,respectively,for a 67.5 m^(3) room.Therefore,the best pre-dehumidification effect was with integration of the DV and RFC systems.This study showed that an ANN-based method can be used for predictive control for condensation prevention in RFC systems.It also provides a novel and effective method by which to assess the pre-dehumidification control of radiant floor surfaces.展开更多
A radiant floor cooling system(RFCS)is a high-comfort and low energy consumption system suitable for residential buildings.Radiant floor systems usually work with fresh air,and their operating performance is affected ...A radiant floor cooling system(RFCS)is a high-comfort and low energy consumption system suitable for residential buildings.Radiant floor systems usually work with fresh air,and their operating performance is affected by climatic conditions.Indoor and outdoor environmental disturbances and the system’s control strategy affect the indoor thermal comfort and energy efficiency of the system.Firstly,a multi-story residential building model was established in this study.Transient system simulation program was used to study the operation dynamics of three control strategies of the RFCS based on the calibrated model.Then,the performance of the control strategies in five climate zones in China were compared using multi-criteria decision-making in combination.The results show that control strategy has a negligible effect on condensation risk,but the thermal comfort and economic performance differ for different control strategies.The adaptability of different control strategies varies in different climate zones based on the consideration of multiple factors.The performance of the direct-ground cooling source system is better in Hot summer and warm winter zone.The variable air volume control strategy scores higher in Serve cold and Temperate zones,and the hours exceeding thermal comfort account for less than 3%of the total simulation period.Therefore,it is suggested to choose the RFCS control strategy for residential buildings according to the climate zone characteristics,to increase the energy savings.Our results provide a reliable reference for implementing RFCSs in residential buildings.展开更多
文摘A mathematical model was built for simulating an innovative design system combined solar energy with biogas boiler for floor radiant heating and fuel. Effects of the ambient air temperature on the performance of the system had been examined. And the results also support theoretical feasibility of the system.
基金The National Science and Technology Pillar Program during the 12th Five-Year Plan Period(No.2011BAJ03B14)the National Natural Science Foundation of China(No.51376044)
文摘In order to improve the heat transfer characteristics of the traditional phase change material(PCM) floor, a new double-layer radiant floor system with PCM is proposed, which can store thermal or cold energy in the off-peak period and use them in the peak period. An experimental setup was developed to study the heat transfer characteristics of the new system under both cooling and heating modes. The experimental results show that the double-layer radiant floor system with PCM can meet both the cold and thermal requirements of users. Moreover, with the same duration of the thermal energy storage process, the increase of water temperature supplied to the system can improve the heat transfer characteristics of the system but lead to the discomfort of users. On the other hand, if the air temperature at the end of the thermal energy storage process is the same under different conditions, the increase of supplied water temperature will decrease the thermal energy storage time and ensure the comfort of users.
文摘To evaluate the thermal performance of a low-temperature electrical radiant floor heating system,an experimental facility equipped with a constant temperature chamber and different specimen floors is designed and built.The heating cable is installed in the floor slab with a unit-rated power of 30 W/m.Twenty-four different schemes are worked out and tested,which include three kinds of composite floor structures and eight kinds of cable distances.The cable distances are 30,40,50,60,80,100,130,150 mm.The main affective factors of the thermal performance and their influencing regularity are discussed.The experimental results show that the system has good stability and reliability,and the ratio of the radiation heat-transfer rate to the gross heat-transfer rate is greater than 50%.When the floor structure and the cable distance are fixed,the gross heat-transfer rate of the upper floor surface has a maximum value at an optimal cable distance.Under the experimental conditions in this paper,the optimal cable distance is 50 mm.
基金Supported by Key Scientific Research Projects of Sichuan Provincial Department of Technology (2010JY0165)Key Special Scientific Research Projects of Mianyang City of Sichuan Province (09Y003-13)Key Scientific Research Projects of Sichuan Provincial Department of Education (2003A112)
文摘The feasibility of adopting a balanced energy mix mode (domestic solar energy, biogas, coal-fired boiler and radiant floor heating) was proposed. Taking a typical rural residence in Zhengzhou City for example, the study through theoretical analysis and calculation showed that such a balanced energy mix is an economic way and efficient in saving energy and reducing air pollution, and elaborated the theoretical feasibility of popularizing such a heat supply mode in rural areas.
基金funded by the Natural Science Foundation of Shan-dong Province(ZR2021ME199,ZR2020ME211)the Support Plan for Outstanding Youth Innovation Team in Colleges and Universities of Shandong Province(2019KJG005)supported by the Plan of Introduction and Cultivation for Young Innovative Talents in Colleges and Universities of Shandong Province.
文摘Pre-dehumidification time(τ_(pre))and pre-dehumidification energy consumption(E_(pre))play important roles in preventing the condensation of moisture on the floors of rooms that use a radiant floor cooling(RFC)system.However,there are few theoretical or experimental studies that focus on these two important quantities.In this study,an artificial neural network(ANN)was used to predict condensation risk for the integration of RFC systems with mixed ventilation(MV),stratum ventilation(SV),and displacement ventilation(DV)systems.A genetic algorithm-back-propagation(GA-BP)neural network model was established to predict τ_(pre) and E_(pre).Both training data and validation data were obtained from tests in a computational fluid dynamics(CFD)simulation.The results show that the established GA-BP model can predict τ_(pre) and E_(pre) well.The coefficient of determination(R^(2))of τ_(pre) and of E_(pre) were,respectively,0.973 and 0.956.For an RFC system integrated with an MV,SV,or DV system,the lowest values of τ_(pre) and E_(pre) were with the DV system,23.1 s and 0.237 kWh,respectively,for a 67.5 m^(3) room.Therefore,the best pre-dehumidification effect was with integration of the DV and RFC systems.This study showed that an ANN-based method can be used for predictive control for condensation prevention in RFC systems.It also provides a novel and effective method by which to assess the pre-dehumidification control of radiant floor surfaces.
基金This work was funded by the Natural Science Foundation of Shandong Province(ZR2021ME199,ZR2021ME237)the Support Plan for Outstanding Youth Innovation Team in Colleges and Universities of Shandong Province(2019KJG005).This work was also supported by the Plan of Introduction and Cultivation for Young Innovative Talents in Colleges and Universities of Shandong Province,and Funding for Domestic Visiting Scholars at Shandong Jianzhu University.
文摘A radiant floor cooling system(RFCS)is a high-comfort and low energy consumption system suitable for residential buildings.Radiant floor systems usually work with fresh air,and their operating performance is affected by climatic conditions.Indoor and outdoor environmental disturbances and the system’s control strategy affect the indoor thermal comfort and energy efficiency of the system.Firstly,a multi-story residential building model was established in this study.Transient system simulation program was used to study the operation dynamics of three control strategies of the RFCS based on the calibrated model.Then,the performance of the control strategies in five climate zones in China were compared using multi-criteria decision-making in combination.The results show that control strategy has a negligible effect on condensation risk,but the thermal comfort and economic performance differ for different control strategies.The adaptability of different control strategies varies in different climate zones based on the consideration of multiple factors.The performance of the direct-ground cooling source system is better in Hot summer and warm winter zone.The variable air volume control strategy scores higher in Serve cold and Temperate zones,and the hours exceeding thermal comfort account for less than 3%of the total simulation period.Therefore,it is suggested to choose the RFCS control strategy for residential buildings according to the climate zone characteristics,to increase the energy savings.Our results provide a reliable reference for implementing RFCSs in residential buildings.