In this paper,the single hole heat transfer power of the ground source heat pump system in Hengshui is compared with data gained from thermal response test.The results show that maximum monitoring data of heat transfe...In this paper,the single hole heat transfer power of the ground source heat pump system in Hengshui is compared with data gained from thermal response test.The results show that maximum monitoring data of heat transfer power per meter in summer is 97.1% of the test data,and the average value accounts for 81.8%.The per meter heat power data through on-site thermal response test can provide references for designing engineering project and optimizing ground source heat pump system as these data do not vary greatly from the actual monitoring data.展开更多
The building sector consumes much energy either for cooling or heating and is associated to greenhouse gas emissions. To meet energy and environmental challenges, the use of ground-to-air heat exchangers for preheatin...The building sector consumes much energy either for cooling or heating and is associated to greenhouse gas emissions. To meet energy and environmental challenges, the use of ground-to-air heat exchangers for preheating and cooling buildings has recently received considerable attention. They provide substantial energy savings and contribute to the improvement of thermal comfort in buildings. For these systems, the ground temperature plays the main role. The present work aims to investigate numerically the influence of the nature of soil on the thermal behavior of the ground-to-air heat exchanger used for building passive cooling. We have taken into account in this work the influence of the soil nature by considering three types of dry soil: clay soil, sandy-clay soil and sandy soil. The mixed convection equations governing the heat transfers in the earth-to-air heat exchanger have been presented and discretized using the finite difference method with an Alternate Direction Implicit (ADI) scheme. The resulting algebraic equations are then solved using the algorithm of Thomas combined with an iterative Gauss-Seidel procedure. The results show that the flow is dominated by forced convection. The examination of the sensitivity of the model to the type of soil shows that the distributions of contours of streamlines, isotherms, isovalues of moisture are less affected by the variations of the nature of soil through the variation of the diffusivity of the soil. However, it is observed that the temperature values obtained for the clay soil are higher while the sandy soil shows lower temperature values. The values of the ground-to-air heat exchanger efficiency are only slightly influenced by the nature of the soil. Nevertheless, we note a slightly better efficiency for the sandy soil than for the sandy-clayey silt and clayey soils. This result shows that a sandy soil would be more suitable for geothermal system installations.展开更多
On the basis of practical projects in Chongqing,the thermal performance of heat exchangers (single U-tube type and double U-tube type) of the ground-source heat pump (GSHP) system in the hot summer was obtained and an...On the basis of practical projects in Chongqing,the thermal performance of heat exchangers (single U-tube type and double U-tube type) of the ground-source heat pump (GSHP) system in the hot summer was obtained and analyzed. The data obtained from test could match with the result deduced from theoretical calculation. From the test results,the cooling capacity of double U-tube is 1.6 times that of single U-tube. Taking cost per depth per watt Clq as the evaluation standard,Clq of single U-tube is 4.69 RMB$/W,and Clq of double U-tube is 3.14 RMB$/W. The double U-tube heat exchangers usage should be prioritized.展开更多
The artificial ground freezing(AGF)systems are designed to operate continuously for an extended period of time to control the groundwater seepage and to strengthen the groundwater structure surrounding excavation area...The artificial ground freezing(AGF)systems are designed to operate continuously for an extended period of time to control the groundwater seepage and to strengthen the groundwater structure surrounding excavation areas.This mode of operation requires a massive amount of energy to sustain the thickness of the frozen body.Therefore,it is of great interest to propose new concepts to reduce energy consumption while providing sufficient structural stability and safe operation.This paper discusses the principle of the freezing on demand(FoD)by means of experiment and mathematical model.A lab-scale rig that mimics the AGF process is conceived and developed.The setup is equipped with more than 80 thermocouples,flow-meters,and advanced instrumentation system to analyze the performance of the AGF process under the FoD concept.A mathematical model has been derived,validated,and utilized to simulate the transient FoD concept.The results suggest that the overall energy saving notably depends on the coolant’s temperature;the energy saving increases while decreasing the coolant inlet temperature.Moreover,applying the FoD concept in an AGF system leads to a significant drop in energy consumption.展开更多
文摘In this paper,the single hole heat transfer power of the ground source heat pump system in Hengshui is compared with data gained from thermal response test.The results show that maximum monitoring data of heat transfer power per meter in summer is 97.1% of the test data,and the average value accounts for 81.8%.The per meter heat power data through on-site thermal response test can provide references for designing engineering project and optimizing ground source heat pump system as these data do not vary greatly from the actual monitoring data.
文摘The building sector consumes much energy either for cooling or heating and is associated to greenhouse gas emissions. To meet energy and environmental challenges, the use of ground-to-air heat exchangers for preheating and cooling buildings has recently received considerable attention. They provide substantial energy savings and contribute to the improvement of thermal comfort in buildings. For these systems, the ground temperature plays the main role. The present work aims to investigate numerically the influence of the nature of soil on the thermal behavior of the ground-to-air heat exchanger used for building passive cooling. We have taken into account in this work the influence of the soil nature by considering three types of dry soil: clay soil, sandy-clay soil and sandy soil. The mixed convection equations governing the heat transfers in the earth-to-air heat exchanger have been presented and discretized using the finite difference method with an Alternate Direction Implicit (ADI) scheme. The resulting algebraic equations are then solved using the algorithm of Thomas combined with an iterative Gauss-Seidel procedure. The results show that the flow is dominated by forced convection. The examination of the sensitivity of the model to the type of soil shows that the distributions of contours of streamlines, isotherms, isovalues of moisture are less affected by the variations of the nature of soil through the variation of the diffusivity of the soil. However, it is observed that the temperature values obtained for the clay soil are higher while the sandy soil shows lower temperature values. The values of the ground-to-air heat exchanger efficiency are only slightly influenced by the nature of the soil. Nevertheless, we note a slightly better efficiency for the sandy soil than for the sandy-clayey silt and clayey soils. This result shows that a sandy soil would be more suitable for geothermal system installations.
文摘On the basis of practical projects in Chongqing,the thermal performance of heat exchangers (single U-tube type and double U-tube type) of the ground-source heat pump (GSHP) system in the hot summer was obtained and analyzed. The data obtained from test could match with the result deduced from theoretical calculation. From the test results,the cooling capacity of double U-tube is 1.6 times that of single U-tube. Taking cost per depth per watt Clq as the evaluation standard,Clq of single U-tube is 4.69 RMB$/W,and Clq of double U-tube is 3.14 RMB$/W. The double U-tube heat exchangers usage should be prioritized.
基金McGill Engineering Doctoral Award(MEDA)Fonds de recherche du Québec-Nature et technologies(FRQNT)-Bourses de doctorat(B2X)for supporting this research
文摘The artificial ground freezing(AGF)systems are designed to operate continuously for an extended period of time to control the groundwater seepage and to strengthen the groundwater structure surrounding excavation areas.This mode of operation requires a massive amount of energy to sustain the thickness of the frozen body.Therefore,it is of great interest to propose new concepts to reduce energy consumption while providing sufficient structural stability and safe operation.This paper discusses the principle of the freezing on demand(FoD)by means of experiment and mathematical model.A lab-scale rig that mimics the AGF process is conceived and developed.The setup is equipped with more than 80 thermocouples,flow-meters,and advanced instrumentation system to analyze the performance of the AGF process under the FoD concept.A mathematical model has been derived,validated,and utilized to simulate the transient FoD concept.The results suggest that the overall energy saving notably depends on the coolant’s temperature;the energy saving increases while decreasing the coolant inlet temperature.Moreover,applying the FoD concept in an AGF system leads to a significant drop in energy consumption.