When a high impedance fault(HIF)occurs in a distribution network,the detection efficiency of traditional protection devices is strongly limited by the weak fault information.In this study,a method based on S-transform...When a high impedance fault(HIF)occurs in a distribution network,the detection efficiency of traditional protection devices is strongly limited by the weak fault information.In this study,a method based on S-transform(ST)and average singular entropy(ASE)is proposed to identify HIFs.First,a wavelet packet transform(WPT)was applied to extract the feature frequency band.Thereafter,the ST was investigated in each half cycle.Afterwards,the obtained time-frequency matrix was denoised by singular value decomposition(SVD),followed by the calculation of the ASE index.Finally,an appropriate threshold was selected to detect the HIFs.The advantages of this method are the ability of fine band division,adaptive time-frequency transformation,and quantitative expression of signal complexity.The performance of the proposed method was verified by simulated and field data,and further analysis revealed that it could still achieve good results under different conditions.展开更多
High-impedance faults(HIFs)in distribution networks may result in fires or electric shocks.However,considerable difficulties exist in HIF detection due to low-resolution measurements and the considerably weaker time-f...High-impedance faults(HIFs)in distribution networks may result in fires or electric shocks.However,considerable difficulties exist in HIF detection due to low-resolution measurements and the considerably weaker time-frequency characteristics.This paper presents a novel HIF detection method using synchronized current information.The method consists of two stages.In the first stage,joint key characteristics of the system are extracted with the minimal system prior knowledge to identify the global optimal micro-phase measurement unit(μPMU)placement.In the second stage,the HIF is detected through a multivariate Jensen-Shannon divergence similarity measurement using high-resolution time-synchronized data inμPMUs in a high-noise environment.l2,1 principal component analysis(PCA),i.e.,PCA based on the l2,1 norm,is applied to an extracted system state and fault features derived from different resolution data in both stages.An economic observability index and HIF criteria are employed to evaluate the performance of placement method and to identify HIFs.Simulation results show that the method can reliably detect HIFs with reasonable detection accuracy in noisy environments.展开更多
Definite-time zero-sequence over-current protection is presently used in systems whose neutral point is grounded by a low resistance(low-resistance grounding systems).These systems frequently malfunction owing to thei...Definite-time zero-sequence over-current protection is presently used in systems whose neutral point is grounded by a low resistance(low-resistance grounding systems).These systems frequently malfunction owing to their high settings of the action value when a high-impedance grounding fault occurs.In this study,the relationship between the zero-sequence currents of each feeder and the neutral branch was analyzed.Then,a grounding protection method was proposed on the basis of the zero-sequence current ratio coefficient.It is defined as the ratio of the zero-sequence current of the feeder to that of the neutral branch.Nonetheless,both zero-sequence voltage and zero-sequence current are affected by the transition resistance,The influence of transition resistance can be eliminated by calculating this coefficient.Therefore,a method based on the zero-sequence current ratio coefficient was proposed considering the significant difference between the faulty feeder and healthy feeder.Furthermore,unbalanced current can be prevented by setting the starting current.PSCAD simulation results reveal that the proposed method shows high reliability and sensitivity when a high-resistance grounding fault occurs.展开更多
This paper proposes an extension of the algorithm in [1], as well as utilization of the wavelet transform in event detection, including High Impedance Fault (HIF). Techniques to analyze the abundant data of PMUs quick...This paper proposes an extension of the algorithm in [1], as well as utilization of the wavelet transform in event detection, including High Impedance Fault (HIF). Techniques to analyze the abundant data of PMUs quickly and effectively are paramount to increasing response time to events and unstable parameters. With the amount of data PMUs output, unstable parameters, tie line oscillations, and HIFs are often overlooked in the bulk of the data. This paper explores model-free techniques to attain stability information and determine events in real-time. When full system connectivity is unknown, many traditional methods requiring other bus measurements can be impossible or computationally extensive to apply. The traditional method of interest is analyzing the power flow Jacobian for singularities and system weak points, attained by applying singular value decomposition. This paper further develops upon the approach in [1] to expand the Discrete-Time Jacobian Eigenvalue Approximation (DDJEA), giving values to significant off-diagonal terms while establishing a generalized connectivity between correlated buses. Statistical linear models are applied over large data sets to prove significance to each term. Then the off diagonal terms are given time-varying weights to account for changes in topology or sensitivity to events using a reduced system model. The results of this novel method are compared to the present errors of the previous publication in order to quantify the degree of improvement that this novel method imposes. The effective bus eigenvalues are briefly compared to Prony analysis to check similarities. An additional application for biorthogonal wavelets is also introduced to detect event types, including the HIF, for PMU data.展开更多
The nonlinear operation of metal oxide varistor(MOV)-protected series compensator in transmission lines introduces complications into fault detection approaches. The accuracy of a conventional fault detection schemes ...The nonlinear operation of metal oxide varistor(MOV)-protected series compensator in transmission lines introduces complications into fault detection approaches. The accuracy of a conventional fault detection schemes is adversely affected by continuous change of the system impedance and load current at the point of a series compensation unit. Thus, this study suggests a method for detecting the faulted phase in MOV-protected series-compensated transmission lines. Primarily, the fault feature is identified using the covariance coefficients of the current samples during the fault period and the current samples during the pre-fault period. Furthermore, a convenience fault detection index is established by applying the cumulative sum technique. Extensive validation through different fault circumstances is accomplished, including different fault positions,resistances, and inception times. The experimental results show that the proposed method performs well with high resistance or impedance faults, faults in noisy conditions, and close-in and far-end faults. The proposed method is simple and efficient for faulty phase detection in MOV-protected series-compensated transmission lines.展开更多
基金financial supported by the Natural Science Foundation of Fujian,China(2021J01633).
文摘When a high impedance fault(HIF)occurs in a distribution network,the detection efficiency of traditional protection devices is strongly limited by the weak fault information.In this study,a method based on S-transform(ST)and average singular entropy(ASE)is proposed to identify HIFs.First,a wavelet packet transform(WPT)was applied to extract the feature frequency band.Thereafter,the ST was investigated in each half cycle.Afterwards,the obtained time-frequency matrix was denoised by singular value decomposition(SVD),followed by the calculation of the ASE index.Finally,an appropriate threshold was selected to detect the HIFs.The advantages of this method are the ability of fine band division,adaptive time-frequency transformation,and quantitative expression of signal complexity.The performance of the proposed method was verified by simulated and field data,and further analysis revealed that it could still achieve good results under different conditions.
基金supported in part by the National Key Research and Development Program of China(No.2017YFB0902800)Science and Technology Project of the State Grid Corporation of China(No.52094017003D)。
文摘High-impedance faults(HIFs)in distribution networks may result in fires or electric shocks.However,considerable difficulties exist in HIF detection due to low-resolution measurements and the considerably weaker time-frequency characteristics.This paper presents a novel HIF detection method using synchronized current information.The method consists of two stages.In the first stage,joint key characteristics of the system are extracted with the minimal system prior knowledge to identify the global optimal micro-phase measurement unit(μPMU)placement.In the second stage,the HIF is detected through a multivariate Jensen-Shannon divergence similarity measurement using high-resolution time-synchronized data inμPMUs in a high-noise environment.l2,1 principal component analysis(PCA),i.e.,PCA based on the l2,1 norm,is applied to an extracted system state and fault features derived from different resolution data in both stages.An economic observability index and HIF criteria are employed to evaluate the performance of placement method and to identify HIFs.Simulation results show that the method can reliably detect HIFs with reasonable detection accuracy in noisy environments.
基金supported in part by National Key Research and Development Program of China(2016YFB0900603)Technology Projects of State Grid Corporation of China(52094017000W).
文摘Definite-time zero-sequence over-current protection is presently used in systems whose neutral point is grounded by a low resistance(low-resistance grounding systems).These systems frequently malfunction owing to their high settings of the action value when a high-impedance grounding fault occurs.In this study,the relationship between the zero-sequence currents of each feeder and the neutral branch was analyzed.Then,a grounding protection method was proposed on the basis of the zero-sequence current ratio coefficient.It is defined as the ratio of the zero-sequence current of the feeder to that of the neutral branch.Nonetheless,both zero-sequence voltage and zero-sequence current are affected by the transition resistance,The influence of transition resistance can be eliminated by calculating this coefficient.Therefore,a method based on the zero-sequence current ratio coefficient was proposed considering the significant difference between the faulty feeder and healthy feeder.Furthermore,unbalanced current can be prevented by setting the starting current.PSCAD simulation results reveal that the proposed method shows high reliability and sensitivity when a high-resistance grounding fault occurs.
文摘This paper proposes an extension of the algorithm in [1], as well as utilization of the wavelet transform in event detection, including High Impedance Fault (HIF). Techniques to analyze the abundant data of PMUs quickly and effectively are paramount to increasing response time to events and unstable parameters. With the amount of data PMUs output, unstable parameters, tie line oscillations, and HIFs are often overlooked in the bulk of the data. This paper explores model-free techniques to attain stability information and determine events in real-time. When full system connectivity is unknown, many traditional methods requiring other bus measurements can be impossible or computationally extensive to apply. The traditional method of interest is analyzing the power flow Jacobian for singularities and system weak points, attained by applying singular value decomposition. This paper further develops upon the approach in [1] to expand the Discrete-Time Jacobian Eigenvalue Approximation (DDJEA), giving values to significant off-diagonal terms while establishing a generalized connectivity between correlated buses. Statistical linear models are applied over large data sets to prove significance to each term. Then the off diagonal terms are given time-varying weights to account for changes in topology or sensitivity to events using a reduced system model. The results of this novel method are compared to the present errors of the previous publication in order to quantify the degree of improvement that this novel method imposes. The effective bus eigenvalues are briefly compared to Prony analysis to check similarities. An additional application for biorthogonal wavelets is also introduced to detect event types, including the HIF, for PMU data.
基金supported by National Natural Science Foundation of China(No. 51777173)。
文摘The nonlinear operation of metal oxide varistor(MOV)-protected series compensator in transmission lines introduces complications into fault detection approaches. The accuracy of a conventional fault detection schemes is adversely affected by continuous change of the system impedance and load current at the point of a series compensation unit. Thus, this study suggests a method for detecting the faulted phase in MOV-protected series-compensated transmission lines. Primarily, the fault feature is identified using the covariance coefficients of the current samples during the fault period and the current samples during the pre-fault period. Furthermore, a convenience fault detection index is established by applying the cumulative sum technique. Extensive validation through different fault circumstances is accomplished, including different fault positions,resistances, and inception times. The experimental results show that the proposed method performs well with high resistance or impedance faults, faults in noisy conditions, and close-in and far-end faults. The proposed method is simple and efficient for faulty phase detection in MOV-protected series-compensated transmission lines.