This paper proposes an equivalent Hamiltonian equations model for the modular multilevel converter-based high-voltage direct-current(MMC-HVDC)transmission system,and constructs an energy function for multi-machine pow...This paper proposes an equivalent Hamiltonian equations model for the modular multilevel converter-based high-voltage direct-current(MMC-HVDC)transmission system,and constructs an energy function for multi-machine power systems with MMC-HVDC transmission lines.The equivalent Hamiltonian equations model is verified to be able to track the power output dynamics of the full model of an MMC-HVDC transmission system.Both theoretical and numerical studies have been undertaken to validate that the energy function proposed for hybrid AC/DC systems satisfies the conditions of an energy function.The work of this paper bridges the gap between the well-developed direct methods of transient stability analysis and power systems with MMC-HVDC transmission lines.展开更多
This paper presents a performance analysis of novel doubledampedtuned alternating current (AC) filters in high voltage direct current(HVDC) systems. The proposed double-damped tuned AC filters offer theadvantages of i...This paper presents a performance analysis of novel doubledampedtuned alternating current (AC) filters in high voltage direct current(HVDC) systems. The proposed double-damped tuned AC filters offer theadvantages of improved performance of HVDC systems in terms of betterpower quality, high power factor, and lower total harmonic distortion (THD).The system under analysis consists of an 878 km long HVDC transmissionline connecting converter stations at Matiari and Lahore, two major cities inPakistan. The main focus of this research is to design a novel AC filter usingthe equivalent impedance method of two single-tuned and double-dampedtuned AC filters. Additionally, the impact of the damping resistor on the ACchannel is examined. TheTHDof theHVDCsystem with and without currentAC filters was also compared in this research and a double-damped tuned ACfilter was proposed. The results of the simulation represent that the proposeddouble-damped tuned AC filter is far smaller in size, offers better powerquality, and has a much lower THD compared to the AC filters currently inplace in the converter station. The simulation analysis was carried out utilizingpower systems computer-aided design (PSCAD) software.展开更多
The AC/DC hybrid distribution network is one of the trends in distribution network development, which poses great challenges to the traditional distribution transformer. In this paper, a new topology suitable for AC/D...The AC/DC hybrid distribution network is one of the trends in distribution network development, which poses great challenges to the traditional distribution transformer. In this paper, a new topology suitable for AC/DC hybrid distribution network is put forward according to the demands of power grid, with advantages of accepting DG and DC loads, while clearing DC fault by blocking the clamping double sub-module(CDSM) of input stage. Then, this paper shows the typical structure of AC/DC distribution network that is hand in hand. Based on the new topology, this paper designs the control and modulation strategies of each stage, where the outer loop controller of input stage is emphasized for its twocontrol mode. At last, the rationality of new topology and the validity of control strategies are verified by the steady and dynamic state simulation. At the same time, the simulation results highlight the role of PET in energy regulation.展开更多
China Southern Power Grid is a unique EHV AC/DC hybrid transmission network that operates in China. In its service area, the distribution of energy resources and the development of economy are extremely unbalanced, so...China Southern Power Grid is a unique EHV AC/DC hybrid transmission network that operates in China. In its service area, the distribution of energy resources and the development of economy are extremely unbalanced, so long-distance and bulk power transmission are needed; besides, the geography and climate conditions are serious, rains, fogs, lightning and typhoon as well as high temperature are common all the year round. Facing these challenges, the power grid enhanced stability control, improved the equipment and strengthen the network structure. In the future, the power grid plans to optimize the disposition of power sources and build digitalized power system.展开更多
HVDC (High Voltage Direct Current) systems are increasingly being applied to improve power system operation and controllability. However, inappropriate setting of HVDC controller may have a detriment effect on the sys...HVDC (High Voltage Direct Current) systems are increasingly being applied to improve power system operation and controllability. However, inappropriate setting of HVDC controller may have a detriment effect on the system performance. Generally, PSS (Power System Stabilizer) is known as a simple concept, easy to perform, and computationally effective to enhance damping of power system oscillations through excitation control of synchronous generator. This paper examines the effectiveness of the PSS to enhance the dynamic performance of AC-DC power systems and to compensate the negative damping of HVDC system. The dynamic performance is evaluated by examining the system response to various disturbances. In order to ensure the reliability of the simulation test results as well as the performance of the PSS, detailed HVDC modeling is adopted using SimPowerSystems toolbox in the MATLAB, and some important conclusions are drawn.展开更多
As the steady-state frequency of an actual power system decreases from its nominal value,the composite load of the system generally responds positively to lower power consumption,and vice versa.It is believed that thi...As the steady-state frequency of an actual power system decreases from its nominal value,the composite load of the system generally responds positively to lower power consumption,and vice versa.It is believed that this load frequency damping(LFD)effect will be artificially enhanced,i.e.,sensitivities of loads with respect to operational frequency will increase,in future power systems.Thus,for wind-integrated power systems,this paper proposes a frequency-dependent chance constrained unit commitment(FDCCUC)model that employs the operational frequency as a dispatching variable so that the LFD effect-based load power can act as a supplemental reserve.Because the frequency deviation is safely restricted,this low-cost reserve can be sufficiently exerted to upgrade the wind power accommodation capability of a power system that is normally confined by an inadequate reserve to cope with uncertain wind power forecasting error.Moreover,when the FDCCUC model is applied to a bulk AC/DC hybrid power system consisting of several independently operated regional AC grids interconnected by DC tie-lines,a hierarchically implemented searching algorithm is proposed to protect private scheduling information of the regional AC grids.Simulations on a 2-area 6-bus system and a 3-area 354-bus system verify the effectiveness of the FDCCUC model and hierarchical searching algorithm.展开更多
The interaction mechanism between AC and DC systems in a hybrid AC-DC transmission grid is discussed with PSS/E software. Analysis shows that receiving-end AC faults may cause much more damage on the HVDC system opera...The interaction mechanism between AC and DC systems in a hybrid AC-DC transmission grid is discussed with PSS/E software. Analysis shows that receiving-end AC faults may cause much more damage on the HVDC system operation than the sending-end AC faults in a multi-infeed HVDC system, and the damage severity depends on the power recovering rate of the HVDC systems. For HVDC systems with slow power recovering rate, the receiving-end AC faults may probably be a critical factor to constrain power transfer limits. Larger capacity of HVDC system means not only higher power transfer-limit of the parallel connected AC-DC transmission grid, but also more expensive stabilizing cost.展开更多
针对风电和光伏并网发电系统的功率波动问题,研究了一种基于双向DC/AC变换器的混合储能系统的动态控制策略。对含有超级电容器与蓄电池组的混合储能系统,通过双闭环控制器对变换器内部的电压电流进行控制,把波动变化较快的电流分量分配...针对风电和光伏并网发电系统的功率波动问题,研究了一种基于双向DC/AC变换器的混合储能系统的动态控制策略。对含有超级电容器与蓄电池组的混合储能系统,通过双闭环控制器对变换器内部的电压电流进行控制,把波动变化较快的电流分量分配给超级电容器,由蓄电池来响应波动变化较慢的电流分量。同时,控制系统将超级电容器的电压稳定在预设范围内。基于扩展卡尔曼滤波(Extended Kalman Filter,EKF)对蓄电池的荷电状态(State of Charge,SOC)进行控制,使其SOC值稳定在安全范围内并延长了蓄电池的使用寿命。通过仿真实验,验证了控制方法的有效性。展开更多
基金supported in part by the National Natural Science Foundation of China under Grant No.51807067the State Key Program of National Natural Science Foundation of China under Grant No.U1866210,Young Elite Scientists Sponsorship Program by CSEE under Grant No.CSEE-YESS-2018the Fundamental Research Funds for the Central Universities of China under Grant No.2018MS77。
文摘This paper proposes an equivalent Hamiltonian equations model for the modular multilevel converter-based high-voltage direct-current(MMC-HVDC)transmission system,and constructs an energy function for multi-machine power systems with MMC-HVDC transmission lines.The equivalent Hamiltonian equations model is verified to be able to track the power output dynamics of the full model of an MMC-HVDC transmission system.Both theoretical and numerical studies have been undertaken to validate that the energy function proposed for hybrid AC/DC systems satisfies the conditions of an energy function.The work of this paper bridges the gap between the well-developed direct methods of transient stability analysis and power systems with MMC-HVDC transmission lines.
基金supported by Creative Challenge Research Program (2021R1I1A1A01052521)the BK-21 FOUR program through the National Research Foundation of Korea (NRF)under the Ministry of Education.
文摘This paper presents a performance analysis of novel doubledampedtuned alternating current (AC) filters in high voltage direct current(HVDC) systems. The proposed double-damped tuned AC filters offer theadvantages of improved performance of HVDC systems in terms of betterpower quality, high power factor, and lower total harmonic distortion (THD).The system under analysis consists of an 878 km long HVDC transmissionline connecting converter stations at Matiari and Lahore, two major cities inPakistan. The main focus of this research is to design a novel AC filter usingthe equivalent impedance method of two single-tuned and double-dampedtuned AC filters. Additionally, the impact of the damping resistor on the ACchannel is examined. TheTHDof theHVDCsystem with and without currentAC filters was also compared in this research and a double-damped tuned ACfilter was proposed. The results of the simulation represent that the proposeddouble-damped tuned AC filter is far smaller in size, offers better powerquality, and has a much lower THD compared to the AC filters currently inplace in the converter station. The simulation analysis was carried out utilizingpower systems computer-aided design (PSCAD) software.
基金supported by National Key Research and Development Program of China (2016YFB0900500,2017YFB0903100)the State Grid Science and Technology Project (SGRI-DL-F1-51-011)
文摘The AC/DC hybrid distribution network is one of the trends in distribution network development, which poses great challenges to the traditional distribution transformer. In this paper, a new topology suitable for AC/DC hybrid distribution network is put forward according to the demands of power grid, with advantages of accepting DG and DC loads, while clearing DC fault by blocking the clamping double sub-module(CDSM) of input stage. Then, this paper shows the typical structure of AC/DC distribution network that is hand in hand. Based on the new topology, this paper designs the control and modulation strategies of each stage, where the outer loop controller of input stage is emphasized for its twocontrol mode. At last, the rationality of new topology and the validity of control strategies are verified by the steady and dynamic state simulation. At the same time, the simulation results highlight the role of PET in energy regulation.
文摘China Southern Power Grid is a unique EHV AC/DC hybrid transmission network that operates in China. In its service area, the distribution of energy resources and the development of economy are extremely unbalanced, so long-distance and bulk power transmission are needed; besides, the geography and climate conditions are serious, rains, fogs, lightning and typhoon as well as high temperature are common all the year round. Facing these challenges, the power grid enhanced stability control, improved the equipment and strengthen the network structure. In the future, the power grid plans to optimize the disposition of power sources and build digitalized power system.
文摘HVDC (High Voltage Direct Current) systems are increasingly being applied to improve power system operation and controllability. However, inappropriate setting of HVDC controller may have a detriment effect on the system performance. Generally, PSS (Power System Stabilizer) is known as a simple concept, easy to perform, and computationally effective to enhance damping of power system oscillations through excitation control of synchronous generator. This paper examines the effectiveness of the PSS to enhance the dynamic performance of AC-DC power systems and to compensate the negative damping of HVDC system. The dynamic performance is evaluated by examining the system response to various disturbances. In order to ensure the reliability of the simulation test results as well as the performance of the PSS, detailed HVDC modeling is adopted using SimPowerSystems toolbox in the MATLAB, and some important conclusions are drawn.
基金supported by the National Natural Science Foundation of China(No.51777143)。
文摘As the steady-state frequency of an actual power system decreases from its nominal value,the composite load of the system generally responds positively to lower power consumption,and vice versa.It is believed that this load frequency damping(LFD)effect will be artificially enhanced,i.e.,sensitivities of loads with respect to operational frequency will increase,in future power systems.Thus,for wind-integrated power systems,this paper proposes a frequency-dependent chance constrained unit commitment(FDCCUC)model that employs the operational frequency as a dispatching variable so that the LFD effect-based load power can act as a supplemental reserve.Because the frequency deviation is safely restricted,this low-cost reserve can be sufficiently exerted to upgrade the wind power accommodation capability of a power system that is normally confined by an inadequate reserve to cope with uncertain wind power forecasting error.Moreover,when the FDCCUC model is applied to a bulk AC/DC hybrid power system consisting of several independently operated regional AC grids interconnected by DC tie-lines,a hierarchically implemented searching algorithm is proposed to protect private scheduling information of the regional AC grids.Simulations on a 2-area 6-bus system and a 3-area 354-bus system verify the effectiveness of the FDCCUC model and hierarchical searching algorithm.
文摘The interaction mechanism between AC and DC systems in a hybrid AC-DC transmission grid is discussed with PSS/E software. Analysis shows that receiving-end AC faults may cause much more damage on the HVDC system operation than the sending-end AC faults in a multi-infeed HVDC system, and the damage severity depends on the power recovering rate of the HVDC systems. For HVDC systems with slow power recovering rate, the receiving-end AC faults may probably be a critical factor to constrain power transfer limits. Larger capacity of HVDC system means not only higher power transfer-limit of the parallel connected AC-DC transmission grid, but also more expensive stabilizing cost.
文摘针对风电和光伏并网发电系统的功率波动问题,研究了一种基于双向DC/AC变换器的混合储能系统的动态控制策略。对含有超级电容器与蓄电池组的混合储能系统,通过双闭环控制器对变换器内部的电压电流进行控制,把波动变化较快的电流分量分配给超级电容器,由蓄电池来响应波动变化较慢的电流分量。同时,控制系统将超级电容器的电压稳定在预设范围内。基于扩展卡尔曼滤波(Extended Kalman Filter,EKF)对蓄电池的荷电状态(State of Charge,SOC)进行控制,使其SOC值稳定在安全范围内并延长了蓄电池的使用寿命。通过仿真实验,验证了控制方法的有效性。