Hybrid circuit breaker (HCB) technology based on a vacuum interrupter and a SF6 interrupter in series has become a new research direction because of the low-carbon requirements for high voltage switches. The vacuum ...Hybrid circuit breaker (HCB) technology based on a vacuum interrupter and a SF6 interrupter in series has become a new research direction because of the low-carbon requirements for high voltage switches. The vacuum interrupter has an excellent ability to deal with the steep rising part of the transient recovery voltage (TRV), while the SF6 interrupter can withstand the peak part of the voltage easily. An HCB can take advantage of the interrupters in the current interruption process. In this study, an HCB model based on the vacuum ion diffusion equations, ion density equation, and modified Cassie-Mayr arc equation is explored. A simulation platform is constructed by using a set of software called the alternative transient program (ATP). An HCB prototype is also designed, and the short circuit current is interrupted by the HCB under different action sequences of contacts. The voltage distribution of the HCB is analyzed through simulations and tests. The results demonstrate that if the vacuum interrupter withstands the initial TRV and interrupts the post-arc current first, then the recovery speed of the dielectric strength of the SF6 interrupter will be fast. The voltage distribution between two interrupters is determined by their post-arc resistance, which happens after current-zero, and subsequently, it is determined by the capacitive impedance after the post-arc current decays to zero.展开更多
Firstly, relevant stress properties of millisecond level breaking process and microsecond level commutation process of hybrid HVDC circuit breaker are studied in detail on the basis of the analysis for the application...Firstly, relevant stress properties of millisecond level breaking process and microsecond level commutation process of hybrid HVDC circuit breaker are studied in detail on the basis of the analysis for the application environment and topological structure and operating principles of hybrid circuit breakers, and key stress parameters in transient state process of two time dimensions are extracted. The established digital simulation circuit for PSCAD/EMTDC device-level operation of the circuit breaker has verified the stress properties of millisecond level breaking process and microsecond level commutation process. Then, equivalent test method, circuits and parameters based on LC power supply are proposed on the basis of stress extraction. Finally, the results of implemented breaking tests for complete 200 kV circuit breaker, 100 kV and 50 kV circuit breaker units, as well as single power electronic module have verified the accuracy of the simulation circuit and mathematical analysis. The result of this paper can be a guide to electrical structure and test system design of hybrid HVDC circuit breaker.展开更多
Due to the low impedance characteristic of the high voltage direct current(HVDC)grid,the fault current rises extremely fast after a DC-side fault occurs,and this phenomenon seriously endangers the safety of the HVDC g...Due to the low impedance characteristic of the high voltage direct current(HVDC)grid,the fault current rises extremely fast after a DC-side fault occurs,and this phenomenon seriously endangers the safety of the HVDC grid.In order to suppress the rising speed of the fault current and reduce the current interruption requirements of the main breaker(MB),a fault current limiting hybrid DC circuit breaker(FCL-HCB)has been proposed in this paper,and it has the capability of bidirectional fault current limiting and fault current interruption.After the occurrence of the overcurrent in the HVDC grid,the current limiting circuit(CLC)of FCL-HCB is put into operation immediately,and whether the protected line is cut off or resumed to normal operation is decided according to the fault detection result.Compared with the traditional hybrid DC circuit breaker(HCB),the required number of semiconductor switches and the peak value of fault current after fault occurs are greatly reduced by adopting the proposed device.Extensive simulations also verify the effectiveness of the proposed FCL-HCB.展开更多
能量路由器的核心元件为双有源桥(dual active bridge,DAB)直流变压器,针对其短路故障时电流上升速率快,峰值大,导致DAB内部电力电子器件闭锁的问题,该文提出一种具有限流型结构的直流变压器,限流装置结构为从DAB高压侧H桥连接单相整流...能量路由器的核心元件为双有源桥(dual active bridge,DAB)直流变压器,针对其短路故障时电流上升速率快,峰值大,导致DAB内部电力电子器件闭锁的问题,该文提出一种具有限流型结构的直流变压器,限流装置结构为从DAB高压侧H桥连接单相整流桥,再与输出端口的限流电感相连。当直流系统发生短路故障时,限流型直流变压器采用混合控制算法进行整流,为限流电感提供钳位电压,限制故障电流的峰值,并与断路器配合实现无弧开断,该方法避免DAB中电力电子器件发生闭锁,快速实现故障限流和隔离。在仿真系统中搭建了基于10kV/750V直流变压器的限流型直流变压器的模型,仿真结果表明限流型直流变压器与断路器配合实现故障限流和隔离的有效性和可行性。展开更多
In traditional hybrid DC circuit breakers(HCBs)schemes,complex equipment is usually required to ensure current commutation from mechanical to semiconductor switches,which cause not only additional construction costs a...In traditional hybrid DC circuit breakers(HCBs)schemes,complex equipment is usually required to ensure current commutation from mechanical to semiconductor switches,which cause not only additional construction costs and volume but also additional losses and maintenance work.Different from this condition,a low-loss and compact HCB scheme that does not use separate current commutation equipment is proposed in this study.By rationally using the charge and discharge of the snubber capacitor,the self-commutated semiconductor switch(SCS)module can integrate both the current commutation and shutdown functions,thereby greatly reducing cost and volume.The working process is discussed and analyzed in detail,and then a 10-kA prototype is developed and tested,which verifies the feasibility and effectiveness of the proposed scheme.Index Terms-HVDC circuit breakers,hybrid DC circuit breakers(HCBs),self-commutated semiconductor switch(SCS).展开更多
基金supported in part by National Natural Science Foundation of China(No.50977004)Key Projects in the National Science and Technology Pillar Program during the Eleventh Five-year Plan Period.Research of China(2009BAA19B03,2009BAA19B05)+1 种基金Fok Ying Tung Education Foundation(No.131057)New Century Excellent Talents in University of China(No.NCET-10-0282)
文摘Hybrid circuit breaker (HCB) technology based on a vacuum interrupter and a SF6 interrupter in series has become a new research direction because of the low-carbon requirements for high voltage switches. The vacuum interrupter has an excellent ability to deal with the steep rising part of the transient recovery voltage (TRV), while the SF6 interrupter can withstand the peak part of the voltage easily. An HCB can take advantage of the interrupters in the current interruption process. In this study, an HCB model based on the vacuum ion diffusion equations, ion density equation, and modified Cassie-Mayr arc equation is explored. A simulation platform is constructed by using a set of software called the alternative transient program (ATP). An HCB prototype is also designed, and the short circuit current is interrupted by the HCB under different action sequences of contacts. The voltage distribution of the HCB is analyzed through simulations and tests. The results demonstrate that if the vacuum interrupter withstands the initial TRV and interrupts the post-arc current first, then the recovery speed of the dielectric strength of the SF6 interrupter will be fast. The voltage distribution between two interrupters is determined by their post-arc resistance, which happens after current-zero, and subsequently, it is determined by the capacitive impedance after the post-arc current decays to zero.
基金supported by SGCC Scientific and Technological Project(52110116004W)
文摘Firstly, relevant stress properties of millisecond level breaking process and microsecond level commutation process of hybrid HVDC circuit breaker are studied in detail on the basis of the analysis for the application environment and topological structure and operating principles of hybrid circuit breakers, and key stress parameters in transient state process of two time dimensions are extracted. The established digital simulation circuit for PSCAD/EMTDC device-level operation of the circuit breaker has verified the stress properties of millisecond level breaking process and microsecond level commutation process. Then, equivalent test method, circuits and parameters based on LC power supply are proposed on the basis of stress extraction. Finally, the results of implemented breaking tests for complete 200 kV circuit breaker, 100 kV and 50 kV circuit breaker units, as well as single power electronic module have verified the accuracy of the simulation circuit and mathematical analysis. The result of this paper can be a guide to electrical structure and test system design of hybrid HVDC circuit breaker.
基金This project is funded by the Dongying Science Development Fund Project(DJ2021013).
文摘Due to the low impedance characteristic of the high voltage direct current(HVDC)grid,the fault current rises extremely fast after a DC-side fault occurs,and this phenomenon seriously endangers the safety of the HVDC grid.In order to suppress the rising speed of the fault current and reduce the current interruption requirements of the main breaker(MB),a fault current limiting hybrid DC circuit breaker(FCL-HCB)has been proposed in this paper,and it has the capability of bidirectional fault current limiting and fault current interruption.After the occurrence of the overcurrent in the HVDC grid,the current limiting circuit(CLC)of FCL-HCB is put into operation immediately,and whether the protected line is cut off or resumed to normal operation is decided according to the fault detection result.Compared with the traditional hybrid DC circuit breaker(HCB),the required number of semiconductor switches and the peak value of fault current after fault occurs are greatly reduced by adopting the proposed device.Extensive simulations also verify the effectiveness of the proposed FCL-HCB.
文摘能量路由器的核心元件为双有源桥(dual active bridge,DAB)直流变压器,针对其短路故障时电流上升速率快,峰值大,导致DAB内部电力电子器件闭锁的问题,该文提出一种具有限流型结构的直流变压器,限流装置结构为从DAB高压侧H桥连接单相整流桥,再与输出端口的限流电感相连。当直流系统发生短路故障时,限流型直流变压器采用混合控制算法进行整流,为限流电感提供钳位电压,限制故障电流的峰值,并与断路器配合实现无弧开断,该方法避免DAB中电力电子器件发生闭锁,快速实现故障限流和隔离。在仿真系统中搭建了基于10kV/750V直流变压器的限流型直流变压器的模型,仿真结果表明限流型直流变压器与断路器配合实现故障限流和隔离的有效性和可行性。
基金supported by the National Natural Science Foundation of China(No.52107004)the China Postdoctoral Science Foundation(No.2020M680484 and No.2021T140201)the Fundamental Research Funds for the Central Universities(No.2021MS003)。
文摘In traditional hybrid DC circuit breakers(HCBs)schemes,complex equipment is usually required to ensure current commutation from mechanical to semiconductor switches,which cause not only additional construction costs and volume but also additional losses and maintenance work.Different from this condition,a low-loss and compact HCB scheme that does not use separate current commutation equipment is proposed in this study.By rationally using the charge and discharge of the snubber capacitor,the self-commutated semiconductor switch(SCS)module can integrate both the current commutation and shutdown functions,thereby greatly reducing cost and volume.The working process is discussed and analyzed in detail,and then a 10-kA prototype is developed and tested,which verifies the feasibility and effectiveness of the proposed scheme.Index Terms-HVDC circuit breakers,hybrid DC circuit breakers(HCBs),self-commutated semiconductor switch(SCS).