Numerical study on critical flow velocity of ice slurry in the pipe of ice source heat pump system
1
作者 Tao Wu Na Zhu +3 位作者 Zhigao Hu Zhenyu Luo Pingfang Hu Fei Lei 《Energy and Built Environment》 EI 2024年第4期607-614,共8页
The traditional evaporator of water source heat pump system is easy to freeze when the water source temperature is too low in winter.A novel ice source heat pump system is proposed,which can use low temperature surfac... The traditional evaporator of water source heat pump system is easy to freeze when the water source temperature is too low in winter.A novel ice source heat pump system is proposed,which can use low temperature surface water to supply heat to buildings.One of the key problems for safe transportation is velocity range of ice slurry in ice outlet pipeline.In order to study the critical flow velocity of ice slurry in the pipe,an Euler model of horizontal straight pipe and 90°elbow pipe were established by Fluent software.The influence of five factors on the critical flow velocity of two kinds of pipes,including initial ice packing fraction,ice particle size,pipe diameter,length of straight pipe and radius curvature of elbow was studied.It found that the initial ice content should be controlled from 10%to 15%.The inlet flow rate was 20%higher than the critical flow rate under the most unfavorable condition.Ice particle size was less than 0.2 mm.The total length of ice discharge pipeline was less than 50 m.Curvature radius of the bend should be met the minimum requirements of the specification of the pipe used. 展开更多
关键词 ice slurry ice packing fraction Flow in pipeline Critical velocity