Enhancement of Thermo-Flow Performances by Windbreakers for Two-Tower Indirect Dry Cooling System 被引量:4
1
作者 YAN Jingbo WANG Weijia +2 位作者 CHEN Lei YANG Lijun DU Xiaoze 《Journal of Thermal Science》 SCIE EI CAS CSCD 2020年第3期676-686,共11页
The winds will greatly weaken the cooling performance of indirect dry cooling system with twin towers.The exterior windbreakers are recommended to restrain the wind adverse effects in this paper.The macro heat exchang... The winds will greatly weaken the cooling performance of indirect dry cooling system with twin towers.The exterior windbreakers are recommended to restrain the wind adverse effects in this paper.The macro heat exchanger model was adopted to simulate the heat exchange between circulating water and ambient air.The performances of natural draft dry cooling system(NDDCS)with and without exterior windbreakers were numerically studied.The pressure,velocity and temperature distribution of cooling air in wind angles of 0°,45°and 90°was obtained and presented.The results show that in all wind directions,the performances for lateral sector of towers with windbreakers are significantly improved,but the low-pressure zone appears unexpectedly for the rear sectors,which reduces the air flow rate.The cooling performances of the twin towers with or without windbreakers decrease at first but then recover with the wind velocity increasing.Besides,the optimal flow and heat transfer performances appear in the wind angle of 0°.The cooling performances can be significantly improved in all three wind directions due to windbreaker configuration. 展开更多
关键词 indirect dry cooling system twin towers windbreakers wind directions flow and heat transfer performances
原文传递
某间冷塔X支柱施工偏差的安全性评估 被引量:1
2
作者 梁娅莉 李武申 +1 位作者 刘淑萍 侯宪安 《电力勘测设计》 2015年第6期49-53,共5页
本文针对某电厂1×200 MW机组工程间接空冷塔X支柱施工中产生几何偏差的情况,根据三维扫描测量结果,利用ANSYS有限元分析软件对有施工缺陷的冷却塔结构进行线性分析,比较不同偏差对结构稳定性和支柱强度的影响,并根据计算结果得出... 本文针对某电厂1×200 MW机组工程间接空冷塔X支柱施工中产生几何偏差的情况,根据三维扫描测量结果,利用ANSYS有限元分析软件对有施工缺陷的冷却塔结构进行线性分析,比较不同偏差对结构稳定性和支柱强度的影响,并根据计算结果得出相应结论。 展开更多
关键词 间接空冷塔 X支柱 施工偏差分析
下载PDF
不同风压下光滑塔与加肋塔的方案比较
3
作者 梁娅莉 侯宪安 +1 位作者 李武申 姚友成 《电力勘测设计》 2017年第S1期318-324,共7页
本文针对某工程给定热力尺寸的间接空冷塔,假定在不同的设计风压下,分别对两种典型塔筒外表面粗糙度(光滑、子午向加肋)设计方案所对应的冷却塔结构稳定性及内力进行了比较,并对整个冷却塔的土建造价与钢筋价格水平的关系进行了分析。... 本文针对某工程给定热力尺寸的间接空冷塔,假定在不同的设计风压下,分别对两种典型塔筒外表面粗糙度(光滑、子午向加肋)设计方案所对应的冷却塔结构稳定性及内力进行了比较,并对整个冷却塔的土建造价与钢筋价格水平的关系进行了分析。本文结论可供冷却塔的结构选型时参考。 展开更多
关键词 间接空冷塔 光滑塔 加肋塔