The slight-alkalization of generator internal cooling water(GICW)is widely used to inhibit the corrosion of hollow copper conductor and thereby ensure the safe operation of the generator.CO_(2) inleakage is increasing...The slight-alkalization of generator internal cooling water(GICW)is widely used to inhibit the corrosion of hollow copper conductor and thereby ensure the safe operation of the generator.CO_(2) inleakage is increasingly identified as a potential security risk for GICW system.In this paper,the influence of CO_(2) inleakage on the slight-alkalization of GICW was theoretically discussed.Based on the equilibriums of the CO_(2)-NaOH-H_(2)O system,CO_(2) inleakage saturation was derived to quantify the amount of the dissolved CO_(2) in GICW.This parameter can be directly calculated with the measured conductivity and the[Na+]of GICW.The influence of CO_(2) inleakage on the slight-alkalization conditioning of GICW and the measurement of its water quality parameters were then analyzed.The more severe the inleakage,the narrower the water quality operation ranges of GICW,resulting in the more difficult the slight-alkalization conditioning of GICW.The temperature calibrations of the conductivity and the pH value of GICW show nonlinear correlations with the amount of CO_(2) inleakage and the NaOH dosage.This study provides insights into the influence of CO_(2) inleakage on the slight-alkalization of GICW,which can serve as the theoretical basis for the actual slight-alkalization when CO_(2) inleakage occurs.展开更多
文摘The slight-alkalization of generator internal cooling water(GICW)is widely used to inhibit the corrosion of hollow copper conductor and thereby ensure the safe operation of the generator.CO_(2) inleakage is increasingly identified as a potential security risk for GICW system.In this paper,the influence of CO_(2) inleakage on the slight-alkalization of GICW was theoretically discussed.Based on the equilibriums of the CO_(2)-NaOH-H_(2)O system,CO_(2) inleakage saturation was derived to quantify the amount of the dissolved CO_(2) in GICW.This parameter can be directly calculated with the measured conductivity and the[Na+]of GICW.The influence of CO_(2) inleakage on the slight-alkalization conditioning of GICW and the measurement of its water quality parameters were then analyzed.The more severe the inleakage,the narrower the water quality operation ranges of GICW,resulting in the more difficult the slight-alkalization conditioning of GICW.The temperature calibrations of the conductivity and the pH value of GICW show nonlinear correlations with the amount of CO_(2) inleakage and the NaOH dosage.This study provides insights into the influence of CO_(2) inleakage on the slight-alkalization of GICW,which can serve as the theoretical basis for the actual slight-alkalization when CO_(2) inleakage occurs.