In the current paper,which deals with the noise pollution excited by distribution transformers in the living area,a comprehensive treatment scheme is put forward for the purpose of reducing the sound pressure level em...In the current paper,which deals with the noise pollution excited by distribution transformers in the living area,a comprehensive treatment scheme is put forward for the purpose of reducing the sound pressure level emitting into the environment.In accordance with the associated test standard,the sound pressure levels of distribution transformer and surrounding environment are not only tested but analyzed as well.The measurements were carried out with the frequency analysis of the 1/3 octave resolution,with the center frequencies at 125 Hz,250 Hz,400 Hz,and 500 Hz.As illustrated,on the basis of the measurement results,the frequency of noise at 500 Hz of distribution transformer causes the major noise pollution in the surrounding environment.This measurement result is in line with the noise frequency characteristics of distribution transformer.There are two transmission routes of noise:(i)the noise excited by distribution transformer transmits by means of the wall of distribution room,and (ii)part of noise spreads through the ground of distribution room.Accordingly,acoustic shield and vibration isolation device are applied for the reduction of the low frequency noise emitted through the above two paths.Aimed at applying the appropriate acoustic material and vibration mounting,the evaluation of the noise reduction and vibration absorption is carried out in accordance with the sound and vibration insulation theory.Following the noise treatment,the transformer and environment noise are measured again.The corresponding findings shed light on the fact that the sound level satisfied the requirement of limits of the ordinance.The proposed noise treatment scheme can be applied to the existing power distribution facilities for controlling the sound levels that reach a point where it is comparatively more unobjectionable.展开更多
基金supported by the science and technology project of China Southern Power Grid(No.GDKJXM20180152).
文摘In the current paper,which deals with the noise pollution excited by distribution transformers in the living area,a comprehensive treatment scheme is put forward for the purpose of reducing the sound pressure level emitting into the environment.In accordance with the associated test standard,the sound pressure levels of distribution transformer and surrounding environment are not only tested but analyzed as well.The measurements were carried out with the frequency analysis of the 1/3 octave resolution,with the center frequencies at 125 Hz,250 Hz,400 Hz,and 500 Hz.As illustrated,on the basis of the measurement results,the frequency of noise at 500 Hz of distribution transformer causes the major noise pollution in the surrounding environment.This measurement result is in line with the noise frequency characteristics of distribution transformer.There are two transmission routes of noise:(i)the noise excited by distribution transformer transmits by means of the wall of distribution room,and (ii)part of noise spreads through the ground of distribution room.Accordingly,acoustic shield and vibration isolation device are applied for the reduction of the low frequency noise emitted through the above two paths.Aimed at applying the appropriate acoustic material and vibration mounting,the evaluation of the noise reduction and vibration absorption is carried out in accordance with the sound and vibration insulation theory.Following the noise treatment,the transformer and environment noise are measured again.The corresponding findings shed light on the fact that the sound level satisfied the requirement of limits of the ordinance.The proposed noise treatment scheme can be applied to the existing power distribution facilities for controlling the sound levels that reach a point where it is comparatively more unobjectionable.