750 kV substation of Riyue Mountain, Qinghai is a substation that annual average thunderstorm days are the maximum at the same volt- age level and altitude in the wodd. We detailedly described testing methods and step...750 kV substation of Riyue Mountain, Qinghai is a substation that annual average thunderstorm days are the maximum at the same volt- age level and altitude in the wodd. We detailedly described testing methods and steps of 6 characteristic parameters for grounding device of 750 kV substation by using 8000S comprehensive test system, and scientifically judged overall performance of the grounding device. Moreover, we espe- cially emphasized key and difficult points in testing process, providing reference for the majority of grounding test workers.展开更多
Some brief informations about AC 500 kV substations inChina, historical data of their design and essential design principles arepresented in thes paper. Some technical and engineering problems ofAC 500 kV substation d...Some brief informations about AC 500 kV substations inChina, historical data of their design and essential design principles arepresented in thes paper. Some technical and engineering problems ofAC 500 kV substation design and construction are discussed. It isemphasized to introduce the 500 kV substation scales, main electricalconnections, selection of equipment and apparatus, insulationcoordination, distribution sWitchyard, control and protection etc.. Herewe also discuss the policy of project cost control at present time and aprospective view of China AC substahons in future.展开更多
This paper describes the quasi-static testing and analytical modelling of the hysteretic behavior of aluminum alloy rigid bus-flexible connectors of 220 kV electrical substations.The main objective of the study is to ...This paper describes the quasi-static testing and analytical modelling of the hysteretic behavior of aluminum alloy rigid bus-flexible connectors of 220 kV electrical substations.The main objective of the study is to experimentally investigate the hysteretic behavior of six different types of rigid bus-flexible connectors 220 kV electrical substations when subjected to cyclic loading.Another objective is to theoretically study the flexibility and effectiveness of a previously proposed analytical model in fitting the experimental hysteresis loops of the tested rigid bus-flexible connectors.The experimental investigation indicates that the tested rigid bus-flexible connectors exhibit highly asymmetric hysteresis behavior along with tension stiffening effect.The theoretical study demonstrates that the generalized Bouc-Wen model has high flexibility and is effective in fitting the experimental hysteresis resisting force-displacement curves of the six tested rigid bus-flexible connectors.展开更多
Considering the complex environment in 750 kV AC substation,porcelain insulators have particular electric field and voltage distribution in comparison with those used in AC transmission line,meanwhile,the investigatio...Considering the complex environment in 750 kV AC substation,porcelain insulators have particular electric field and voltage distribution in comparison with those used in AC transmission line,meanwhile,the investigation of a typical 750 kV AC substation located in Lanzhou with ultraviolet imager(UVI) demonstrated that the corona discharge of some insulators is serious due to the improper structure design and installation,so research on porcelain insulators used in substation is needed.The three-dimensional finite element method(FEM) 750 kV AC substation calculation model was established to calculate electric field and voltage distribution of insulators,and the voltage distribution curves along insulators which are classified by type and suspension location were obtained using a novel FEM method which can effectively reduce the calculation amount without losing accuracy,meanwhile,the effect of the grading ring for improving voltage distribution of insulators was studied by adjusting the structure parameters of grading ring. Consequently,an optimization structure of rings was proposed by improving the voltage distribution of insulator string and reducing the electric strength of grading ring for the purpose of restricting corona noise,and the onsite observations by UVI showed that the newly manufactured and installed grading ring could obviously avoid the occurrences of corona discharge which validates the optimization design.This paper proposed an effective method combining UVI observation and FEM calculation to study voltage-sharing characteristics of porcelain insulators,and the results can provide experiences and references for the design of 750 kV AC substation.展开更多
文摘750 kV substation of Riyue Mountain, Qinghai is a substation that annual average thunderstorm days are the maximum at the same volt- age level and altitude in the wodd. We detailedly described testing methods and steps of 6 characteristic parameters for grounding device of 750 kV substation by using 8000S comprehensive test system, and scientifically judged overall performance of the grounding device. Moreover, we espe- cially emphasized key and difficult points in testing process, providing reference for the majority of grounding test workers.
文摘Some brief informations about AC 500 kV substations inChina, historical data of their design and essential design principles arepresented in thes paper. Some technical and engineering problems ofAC 500 kV substation design and construction are discussed. It isemphasized to introduce the 500 kV substation scales, main electricalconnections, selection of equipment and apparatus, insulationcoordination, distribution sWitchyard, control and protection etc.. Herewe also discuss the policy of project cost control at present time and aprospective view of China AC substahons in future.
基金National Natural Science Foundation of China under Grant No.51978397。
文摘This paper describes the quasi-static testing and analytical modelling of the hysteretic behavior of aluminum alloy rigid bus-flexible connectors of 220 kV electrical substations.The main objective of the study is to experimentally investigate the hysteretic behavior of six different types of rigid bus-flexible connectors 220 kV electrical substations when subjected to cyclic loading.Another objective is to theoretically study the flexibility and effectiveness of a previously proposed analytical model in fitting the experimental hysteresis loops of the tested rigid bus-flexible connectors.The experimental investigation indicates that the tested rigid bus-flexible connectors exhibit highly asymmetric hysteresis behavior along with tension stiffening effect.The theoretical study demonstrates that the generalized Bouc-Wen model has high flexibility and is effective in fitting the experimental hysteresis resisting force-displacement curves of the six tested rigid bus-flexible connectors.
文摘Considering the complex environment in 750 kV AC substation,porcelain insulators have particular electric field and voltage distribution in comparison with those used in AC transmission line,meanwhile,the investigation of a typical 750 kV AC substation located in Lanzhou with ultraviolet imager(UVI) demonstrated that the corona discharge of some insulators is serious due to the improper structure design and installation,so research on porcelain insulators used in substation is needed.The three-dimensional finite element method(FEM) 750 kV AC substation calculation model was established to calculate electric field and voltage distribution of insulators,and the voltage distribution curves along insulators which are classified by type and suspension location were obtained using a novel FEM method which can effectively reduce the calculation amount without losing accuracy,meanwhile,the effect of the grading ring for improving voltage distribution of insulators was studied by adjusting the structure parameters of grading ring. Consequently,an optimization structure of rings was proposed by improving the voltage distribution of insulator string and reducing the electric strength of grading ring for the purpose of restricting corona noise,and the onsite observations by UVI showed that the newly manufactured and installed grading ring could obviously avoid the occurrences of corona discharge which validates the optimization design.This paper proposed an effective method combining UVI observation and FEM calculation to study voltage-sharing characteristics of porcelain insulators,and the results can provide experiences and references for the design of 750 kV AC substation.