The problem of logical node(LN)importance quantification in an IEC 61850 based substation automation system(SAS)is investigated in this paper.First,a weighted and directed static complex network model is established b...The problem of logical node(LN)importance quantification in an IEC 61850 based substation automation system(SAS)is investigated in this paper.First,a weighted and directed static complex network model is established by analyzing the characteristics of SAS,according to IEC 61850.Then,we propose a method,which combines topology value and information adjunction value by introducing a first-order linear feedback controller to quantify the value of LNs.On this basis,some definitions for equivalent network conversion are proposed to greatly reduce the complexity of the original network topology.Also,the absolute value and relative value are introduced to quantify LN importance from the perspective of the node’s necessity and influence,respectively.Finally,simulation results of the case study demonstrate that the proposed method is effective and provides a broader and clearer perspective for viewing the logical node importance for IEC61850 based SAS.展开更多
基金This work was supported in part by the National Natural Science Foundation of China(U1866209)。
文摘The problem of logical node(LN)importance quantification in an IEC 61850 based substation automation system(SAS)is investigated in this paper.First,a weighted and directed static complex network model is established by analyzing the characteristics of SAS,according to IEC 61850.Then,we propose a method,which combines topology value and information adjunction value by introducing a first-order linear feedback controller to quantify the value of LNs.On this basis,some definitions for equivalent network conversion are proposed to greatly reduce the complexity of the original network topology.Also,the absolute value and relative value are introduced to quantify LN importance from the perspective of the node’s necessity and influence,respectively.Finally,simulation results of the case study demonstrate that the proposed method is effective and provides a broader and clearer perspective for viewing the logical node importance for IEC61850 based SAS.