期刊文献+
共找到1篇文章
< 1 >
每页显示 20 50 100
Effect of Non-Condensable Gas Leakage on Long Term Cooling Performance of Loop Thermosyphon
1
作者 Hiroyuki Toyoda Yoshihiro Kondo 《Journal of Electronics Cooling and Thermal Control》 2013年第4期131-135,共5页
We have developed a loop thermosyphon for cooling electronic devices. The cooling performance of a thermosyphon deteriorates with an increasing amount of non-condensable gas (NCG). Design of a thermosyphon must consid... We have developed a loop thermosyphon for cooling electronic devices. The cooling performance of a thermosyphon deteriorates with an increasing amount of non-condensable gas (NCG). Design of a thermosyphon must consider NCG to provide guaranteed performance for a long time. In this study, the heat transfer performance of a thermosyphon was measured while changing the amount of NCG. The resultant performances were expressed as approximations. These approximations enabled us to predict the total thermal resistance of the thermosyphon by the amount of NCG and input heating. Then, using the known leakage in the thermosyphon and the amount of dissolved NCG in the water, we can predict the amount of NCG and the total thermal resistance of the thermosyphon after ten years. Although there is a slight leakage in the thermosyphon, we are able to design a thermosyphon with a guaranteed level of cooling performance for a long time using the proposed design method. 展开更多
关键词 thermosyphon BOILING CONDENSATION non-condensable gas Heat Transfer PERFORMANCE CPU COOLING
下载PDF
上一页 1 下一页 到第