Feasibility Analysis on the Integrated Application of Solar Energy, Biogas, Coal-fired Boiler and Radiant Floor Heating for Rural Residence 被引量:3
1
作者 JIN Junjie TANG Zhonghua +2 位作者 GAO Lifu TANG Li ZHANG Xiaodong 《Journal of Landscape Research》 2013年第4期12-14,共3页
The feasibility of adopting a balanced energy mix mode (domestic solar energy, biogas, coal-fired boiler and radiant floor heating) was proposed. Taking a typical rural residence in Zhengzhou City for example, the stu... The feasibility of adopting a balanced energy mix mode (domestic solar energy, biogas, coal-fired boiler and radiant floor heating) was proposed. Taking a typical rural residence in Zhengzhou City for example, the study through theoretical analysis and calculation showed that such a balanced energy mix is an economic way and efficient in saving energy and reducing air pollution, and elaborated the theoretical feasibility of popularizing such a heat supply mode in rural areas. 展开更多
关键词 Solar energy COLLECTOR BIOGAS Coal-fired BOILER radiant floor heating
下载PDF
A simulation Study on the System Combined Solar Energy with Biogas Boiler for Floor Radiant Heating and Fuel 被引量:1
2
作者 LI Na LI Cheng-xiang 《科技视界》 2015年第15期169-170,268,共3页
A mathematical model was built for simulating an innovative design system combined solar energy with biogas boiler for floor radiant heating and fuel. Effects of the ambient air temperature on the performance of the s... A mathematical model was built for simulating an innovative design system combined solar energy with biogas boiler for floor radiant heating and fuel. Effects of the ambient air temperature on the performance of the system had been examined. And the results also support theoretical feasibility of the system. 展开更多
关键词 太阳能 锅炉 数学模型 温度
下载PDF
Evaluation of the thermal performance of radiant floor heating system with the influence of unevenly distributed solar radiation based on the theory of discretization
3
作者 Jiacheng Zheng Tao Yu +1 位作者 Bo Lei Xiujing Luo 《Building Simulation》 SCIE EI CSCD 2023年第1期105-120,共16页
In the building with many transparent envelopes,solar radiation can irradiate on the local surface of floor and cause overheating.The local thermal comfort in the room will be dissatisfactory and the thermal performan... In the building with many transparent envelopes,solar radiation can irradiate on the local surface of floor and cause overheating.The local thermal comfort in the room will be dissatisfactory and the thermal performance of radiant floor will be strongly affected.However,in many current calculation models,solar radiation on the floor surface is assumed to be uniformly distributed,resulting in the inaccurate evaluation of the thermal performance of the radiant floor.In this paper,a calculation model based on the theory of discretization and the RC thermal network is proposed to calculate the dynamic thermal performance of radiant floor with the consideration of unevenly distributed solar radiation.Then,the discretization model is experimentally validated and is used to simulate a radiant floor heating system of an office room in Lhasa.It is found that with the unevenly distributed solar radiation,the maximum surface temperature near the south exterior window can reach up to 35.6℃,which exceeds the comfort temperature limit and is nearly 8.5℃higher than that in the north zone.Meanwhile,the heating capacity of the radiant floor in the irradiated zone can reach up to 171 W/m^(2),while that in the shaded zone is only 79 W/m^(2).The model with the assumption of uniformly distributed solar radiation ignores the differences between the south and north zones and fails to describe local overheating in the irradiated zones.By contrast,the discretization model can more accurately evaluate the thermal performance of radiant floor with the influence of real solar radiation.Based on this discretization model,novel design and control schemes of radiant floor heating system can be proposed to alleviate local overheating and reduce heating capacity in the irradiated zone. 展开更多
关键词 radiant floor heating solar radiation simplified model thermal performance
原文传递
高原铁路站房地板辐射系统的分区供暖效果
4
作者 郑嘉诚 余涛 +2 位作者 雷波 陈辰 吕瑞欣 《西南交通大学学报》 EI CSCD 北大核心 2024年第1期62-69,共8页
为了解决高原铁路站房部分区域在强太阳辐射的影响下出现过热、地板辐射供暖系统能耗浪费的问题,以某高原铁路车站为研究对象,根据站房内太阳照射情况对地板辐射系统提出了分区供暖方案;利用建筑能耗模拟软件Energyplus对该铁路站房进... 为了解决高原铁路站房部分区域在强太阳辐射的影响下出现过热、地板辐射供暖系统能耗浪费的问题,以某高原铁路车站为研究对象,根据站房内太阳照射情况对地板辐射系统提出了分区供暖方案;利用建筑能耗模拟软件Energyplus对该铁路站房进行模拟分析,对比了地板辐射系统分区前后站房内的热环境和系统供暖量.结果表明:地板辐射系统采用统一的设计及运行控制方案供暖时,站房内太阳直射影响区的平均操作温度在日间最高可达27℃,与非直射影响区之间的温差超过5℃;在地板辐射系统分区供暖时,直射影响区的平均操作温度最高为26℃,室内温度分布更为均匀,局部过热现象得到缓解;在保证站房热舒适性的前提下,地板辐射系统的分区供暖方案能够使直射影响区整个供暖季的供暖量降低38.2%. 展开更多
关键词 铁路站房 太阳辐射 地板辐射供暖 室内热环境 系统供暖量
下载PDF
地面局部辐射供暖典型热环境特征化表征研究
5
作者 苏玲 王登甲 +1 位作者 董斌彦 王天慧 《西安建筑科技大学学报(自然科学版)》 北大核心 2024年第1期141-149,共9页
局部精细化采暖是满足室内人员舒适前提下降低采暖能耗、实现采暖能源高效利用的重要方式之一.为提高采暖效率,给精细化辐射供暖提供方法参考,本文选取具有显著工位布局要求的办公场所作为对象,对地面局部辐射供暖模块影响下,室内不同... 局部精细化采暖是满足室内人员舒适前提下降低采暖能耗、实现采暖能源高效利用的重要方式之一.为提高采暖效率,给精细化辐射供暖提供方法参考,本文选取具有显著工位布局要求的办公场所作为对象,对地面局部辐射供暖模块影响下,室内不同区域热环境分布情况进行典型化研究分析,得到了不同局部模块供暖工况下室内非均匀热环境分布特征.分析结果表明,局部辐射面积为16.7%时辐射区域与非辐射区域平均辐射温度相差3℃以上,具有明显的局部环境营造效果;地面局部辐射供暖辐射区域与非辐射区域不对称辐射温度差异显著;将局部辐射源设置在靠近外墙区域,可以提高整体平均辐射温度,使室内平均辐射温度分布更为均匀.本研究初步给出基于地面局部辐射供暖的典型化热环境共性特征表述,可为后续局部辐射供暖系统的精细化设计提供参考. 展开更多
关键词 地面局部辐射供暖 非均匀热环境 数值模拟
下载PDF
夏热冬冷地区低温辐射地板供暖影响因素的正交试验
6
作者 冯梦雅 王汉青 李正明 《科学技术与工程》 北大核心 2024年第6期2367-2377,共11页
为了研究夏热冬冷地区低温辐射地板供暖影响因素,采用L25(56)的正交试验方法探究供水温度、管间流速、管径、管间距、填充层厚度5因素对地板表面平均温度和均匀度的影响,获得各因素对试验指标的影响趋势、显著性程度和组合的最优解。研... 为了研究夏热冬冷地区低温辐射地板供暖影响因素,采用L25(56)的正交试验方法探究供水温度、管间流速、管径、管间距、填充层厚度5因素对地板表面平均温度和均匀度的影响,获得各因素对试验指标的影响趋势、显著性程度和组合的最优解。研究表明:对地板表面平均温度的影响程度为供水温度>管间距>管径>填充层厚度>管间流速,对均匀度的影响程度为管间距>供水温度>填充层厚度>管径>管间流速,最优水平组合为:供水温度取35℃,管间流速取0.4 m/s,管径取16 mm,管间距取100 mm,填充层厚度取75 mm。试验结果为夏热冬冷地区辐射供暖设计提供借鉴,亦可对数值分析软件与统计学的结合提供思路。 展开更多
关键词 低温辐射地板供暖 数值模拟 正交试验 地板表面平均温度 均匀度
下载PDF
夏热冬冷地区地板辐射和风机盘管供暖的对比分析
7
作者 何险峰 《流体测量与控制》 2024年第2期41-46,50,共7页
为分析地板辐射供暖和风机盘管供暖在夏热冬冷地区的具体运行效果,对两种模式下的室内热舒适、供热能力和能耗进行了实验和OpenStudio模拟分析。实验和模拟结果表明:风机盘管系统在运行初期体现优势,但后期地板辐射供暖具有更好的室内... 为分析地板辐射供暖和风机盘管供暖在夏热冬冷地区的具体运行效果,对两种模式下的室内热舒适、供热能力和能耗进行了实验和OpenStudio模拟分析。实验和模拟结果表明:风机盘管系统在运行初期体现优势,但后期地板辐射供暖具有更好的室内舒适性,垂直峰谷差仅为0.03℃,预测平均值模型PMV为-0.28,预测不满意百分比指标(PPD)为6.83%;地板辐射供热能力大于风机盘管供热,且耗电量更低。 展开更多
关键词 地板辐射供暖 风机盘管 热舒适性 供热能力 OpenStudio
下载PDF
四川某学校整体迁建工程空调系统设计探讨与分析
8
作者 张慧颖 《重庆建筑》 2024年第7期20-23,共4页
该文以某学校空调系统设计为工程案例,根据建筑特点、各功能区使用要求,对整个项目的冷热源和空调系统进行简要介绍,重点介绍礼堂空调系统,并针对项目投入使用后现场出现的问题,分析原因并提出解决方案,最后总结项目疑难点,可供同类项... 该文以某学校空调系统设计为工程案例,根据建筑特点、各功能区使用要求,对整个项目的冷热源和空调系统进行简要介绍,重点介绍礼堂空调系统,并针对项目投入使用后现场出现的问题,分析原因并提出解决方案,最后总结项目疑难点,可供同类项目参考。 展开更多
关键词 风冷热泵 气流组织 礼堂 地板辐射采暖
下载PDF
兰州某教育园区综合体育馆采暖系统设计
9
作者 冯坤旋 《技术与市场》 2024年第3期79-82,共4页
以兰州某教育园区综合体育馆为例,介绍了综合体育馆在热源唯一的情况下根据综合体育馆建筑功能布置,同时考虑兰州位于西北寒冷地区的气候特点,在满足各功能分区设计参数的条件下,对整体采暖设计方案进行创新性优化,在同一建筑不同分区采... 以兰州某教育园区综合体育馆为例,介绍了综合体育馆在热源唯一的情况下根据综合体育馆建筑功能布置,同时考虑兰州位于西北寒冷地区的气候特点,在满足各功能分区设计参数的条件下,对整体采暖设计方案进行创新性优化,在同一建筑不同分区采用3种不同的采暖方式保证整体采暖系统,在满足实际使用需求的同时,达到经济合理、节能可靠的目的。 展开更多
关键词 综合体育馆 采暖设计 低温地板辐射采暖 大空间采暖
下载PDF
Performance simulation and optimization of new radiant floor heating based on micro heat pipe array 被引量:2
10
作者 Heran Jing Zhenhua Quan +3 位作者 Ruixue Dong Limin Hao Yunhan Liu Yaohua Zhao 《Building Simulation》 SCIE EI CSCD 2022年第7期1295-1308,共14页
This paper proposes two new radiant floor heating structures based on micro heat pipe array(MHPA),namely cement-tile floor and keel-wood floor.The numerical models for these different floor structures are established ... This paper proposes two new radiant floor heating structures based on micro heat pipe array(MHPA),namely cement-tile floor and keel-wood floor.The numerical models for these different floor structures are established and verified by experiments.The temperature distribution and heat transfer process of each part are comprehensively obtained,and the structure is optimized.The results show that the cement-tile floor has the better heat transfer performance of the two.When under the same inlet water temperature and flow rate,the keel-wood floor's surface temperature distribution is about 2℃ lower than that of the cement-tile floor.The inlet water temperature of cement-tile floor is about 10℃ lower than that of keel-wood structure when the floor surface temperature is the same.During a longitudinal heat transfer above MHPA,the floor surface temperature decreases by 0.5℃ for every 10 mm filling layer increase.In order to reduce the non-uniformity of the floor's surface temperature and improve the thermal comfort of the heated room,the optimal structure for a floor is given,with the maximum surface temperature difference reduced by 3.35℃.We used research focusing on new radiant floor heating,with advantages including high efficiency heat transfer,low water supply temperature,simple waterway structure,low resistance and leakage risk,to provide theory and data to support the application of an effective radiant floor heating based on MHPA. 展开更多
关键词 radiant floor heating micro heat pipe array numerical simulation heat transfer
原文传递
R290直膨式太阳能热泵供暖系统实验研究
11
作者 孔祥强 张鹏 +2 位作者 徐显 闫循正 岳振伟 《太阳能学报》 EI CAS CSCD 北大核心 2023年第6期323-329,共7页
为分析直膨式太阳能热泵耦合地板辐射供暖系统在北方寒冷地区的实际运行特性,设计并搭建以丙烷(R290)为工质的直膨式太阳能热泵供暖实验平台,分析冬季不同运行工况下环境参数对系统热力性能的影响。实验结果表明:系统可实现室内供暖的... 为分析直膨式太阳能热泵耦合地板辐射供暖系统在北方寒冷地区的实际运行特性,设计并搭建以丙烷(R290)为工质的直膨式太阳能热泵供暖实验平台,分析冬季不同运行工况下环境参数对系统热力性能的影响。实验结果表明:系统可实现室内供暖的稳定性,实验测试期间平均室温保持在16.1~20.8℃之间,热泵系统性能系数(COP)保持在2.57~4.30之间,供暖系统COP保持在2.24~3.98之间。太阳辐照度每增加50 W/m^(2),热泵系统COP提升4.9%;环境温度每升高1℃,热泵系统COP提升2.4%。太阳辐照度对热泵系统的电子膨胀阀开度和工质质量流量影响较为显著。当终止水温从45℃提升至55℃时,热泵系统COP降低12.2%;而在终止水温为50℃时,供暖系统COP达到最大值3.37。 展开更多
关键词 太阳能 热泵系统 丙烷 性能系数 地板辐射供暖 实验
下载PDF
和田地区空气源热泵地暖辐射采暖系统实验
12
作者 孙志利 任彤 +4 位作者 刘起友 焦峰 李金涛 梁迪 王易安 《制冷学报》 CAS CSCD 北大核心 2023年第3期67-73,共7页
热泵供暖可以解决燃煤供暖带来的环境污染问题,本文以和田地区应用的空气源热泵系统为研究对象,实验测试了采用辐射地板为末端的空气源热泵供暖系统的实际性能,在典型日(环境温度为-4.7~9.6℃,相对湿度为26%~61%)24 h内分析了各项性能... 热泵供暖可以解决燃煤供暖带来的环境污染问题,本文以和田地区应用的空气源热泵系统为研究对象,实验测试了采用辐射地板为末端的空气源热泵供暖系统的实际性能,在典型日(环境温度为-4.7~9.6℃,相对湿度为26%~61%)24 h内分析了各项性能参数的变化和室外环境温度变化对热泵供暖系统性能的影响。结果表明:在典型日的实际工况下,热泵供暖系统COP在16:00附近达到最高值2.64,在8:00附近达到最低值1.98。由于供暖建筑的保温性能相对较好,当室外温度发生变化时,房间内供暖温度波动较小;对于阳面房间,房间温度全天可稳定在23~24℃;对于阴面房间,房间温度也能达到20℃以上。采用辐射地板为末端的空气源热泵供暖系统满足和田地区供暖需求,系统效率较高,应用前景广阔。 展开更多
关键词 空气源热泵 地板辐射 清洁供暖 系统性能
下载PDF
太阳辐射影响下地板供暖室内环境与控制策略优化
13
作者 李念平 段若岚 阿勇嘎 《沈阳建筑大学学报(自然科学版)》 CAS 北大核心 2023年第2期323-330,共8页
目的 研究太阳在辐射供暖地板室内的照射特点以及利用太阳辐射优化供暖策略。方法 利用CFD建立数值模型模拟太阳在室内的投影位置和室内温度场,实验测量太阳辐射强度和室内热环境参数,评估冬季辐射地板的供暖效果和室内环境温度。结果 ... 目的 研究太阳在辐射供暖地板室内的照射特点以及利用太阳辐射优化供暖策略。方法 利用CFD建立数值模型模拟太阳在室内的投影位置和室内温度场,实验测量太阳辐射强度和室内热环境参数,评估冬季辐射地板的供暖效果和室内环境温度。结果 太阳辐射在地板表面形成投影区,区域内外温度不均匀,两区域温差大于15℃,但工作面温度分布较均匀;室内各环境参数随太阳辐射强度改变而规律性变化,峰值延迟出现,太阳辐射使室内空气温度和平均辐射温度提升9~10℃。结论 辐射地板供暖房间可有效利用太阳辐射能量以降低供暖系统总供暖量,辐射地板设定供暖温度可降低6℃,供暖系统总供暖量降低47 kW;可根据太阳辐射变化规律调整设定地板温度,以避免房间过热,在满足室内热环境需求的同时减少供暖量降低能耗。 展开更多
关键词 毛细管辐射地板 供暖 太阳辐射 温度分布 数值模拟
下载PDF
严寒地区地铁车站利用设备废热供暖研究
14
作者 黄泽茂 《制冷与空调(四川)》 2023年第2期282-286,共5页
位于严寒地区的地铁车站,冬季时,为了阻挡出入口渗透进入车站的冷空气,需要设置电热风幕,同时为避免引入车站的新风凝露,也设置了新风预热装置,耗费大量的电能,且存在安全隐患。与此同时,车站内弱电、供电设备用房产生的大量热量还需要... 位于严寒地区的地铁车站,冬季时,为了阻挡出入口渗透进入车站的冷空气,需要设置电热风幕,同时为避免引入车站的新风凝露,也设置了新风预热装置,耗费大量的电能,且存在安全隐患。与此同时,车站内弱电、供电设备用房产生的大量热量还需要利用机械通风系统将热量排除室外,造成能量大量损失。针对地铁车站设备发热特点,结合常规的冷源形式,研究得出采用热回收型风冷热泵机组进行供暖和新风预热的方案,具有系统简单、控制简便、节能效果好、经济效益显著的特点,值得推广应用。 展开更多
关键词 严寒地区 地铁 热回收型风冷热泵 预热 供暖
下载PDF
高寒气候下集合住宅顶层节能设计策略研究——以西宁为例 被引量:1
15
作者 汪珊珊 武玉艳 汪留成 《南方建筑》 CSCD 北大核心 2023年第1期72-80,共9页
集合住宅顶层外表面积大,室内、外热环境交互敏感,在太阳能富集、冬季寒冷漫长的气候环境下,直接利用太阳辐射热节约采暖用能的潜力大。以西宁地区为例,建立集合住宅顶层的典型空间模型,采用Designbuilder能耗模拟软件,从户内空间组合... 集合住宅顶层外表面积大,室内、外热环境交互敏感,在太阳能富集、冬季寒冷漫长的气候环境下,直接利用太阳辐射热节约采暖用能的潜力大。以西宁地区为例,建立集合住宅顶层的典型空间模型,采用Designbuilder能耗模拟软件,从户内空间组合、单一空间、围护界面形态构造3个层级分析太阳辐射热作用下其设计要素与顶层采暖用能的关联性。总结住宅顶层的节能设计策略,并从设计要素利用太阳辐射热对采暖用能的节能贡献率角度,对设计策略进行优先级排序。为建筑师开展强化太阳辐射热利用效果的设计应用提供依据。 展开更多
关键词 太阳辐射热利用 被动式设计 节能 西宁 集合住宅 建筑顶层
下载PDF
窗墙比对供暖房间热舒适及系统能耗影响研究
16
作者 刘娜 刘东 +1 位作者 李涫宇 周浩天 《制冷与空调(四川)》 2023年第1期66-72,共7页
建筑围护结构直接影响室内热湿负荷,而窗户作为三大围护结构中热工性能最差的构件,其对室内热负荷的影响最大,尤其是当存在太阳辐射时会直接影响室内热舒适性。搭建空气源热泵对流-辐射联合供暖系统测试台,并在大窗墙比的情况下增设保... 建筑围护结构直接影响室内热湿负荷,而窗户作为三大围护结构中热工性能最差的构件,其对室内热负荷的影响最大,尤其是当存在太阳辐射时会直接影响室内热舒适性。搭建空气源热泵对流-辐射联合供暖系统测试台,并在大窗墙比的情况下增设保温材料设置等效墙的形式,研究了窗墙比对冬季不同供暖模式下室内热舒适及能耗的影响。结果表明,在空气源热泵供水温度一定时,地板辐射末端供暖比风机盘管末端具有更舒适的室内热环境、垂直温度梯度较小并且能耗相对较少;受到太阳辐射的影响,随着窗墙比的增加,地板辐射供暖系统下室内温度波动减小,能耗增加,PMV值变化在热舒适范围内。 展开更多
关键词 窗墙比 能耗 热舒适 地板供暖 风机盘管
下载PDF
基于建筑热惰性的空调系统动态调节优化研究
17
作者 张雨虹 张林华 宋永兴 《节能》 2023年第4期1-7,共7页
从运行方式的角度对地板辐射+地源热泵空调系统进行优化,以济南某办公建筑为例,利用Trnsys仿真模拟软件建立地板辐射+地源热泵空调系统模型,通过改变负荷侧水泵流量、机组功率、系统启停时间,比较不同方式运行的舒适性和经济性,探索地... 从运行方式的角度对地板辐射+地源热泵空调系统进行优化,以济南某办公建筑为例,利用Trnsys仿真模拟软件建立地板辐射+地源热泵空调系统模型,通过改变负荷侧水泵流量、机组功率、系统启停时间,比较不同方式运行的舒适性和经济性,探索地板辐射供冷系统建筑围护结构的蓄热特性。结果显示:在保证舒适性的前提下,可以减小负荷侧水泵流量和机组功率,确定最佳运行参数,减少系统能耗;墙体总蓄热时间为12.5 h,放热时间为11.5 h,由于墙体具有热惰性,温度变化具有明显的峰值延迟现象;系统在7:30~18:00运行能够缩短运行时间,降低空调系统运行能耗。 展开更多
关键词 地源热泵 地板辐射 TRNSYS 蓄热特性
下载PDF
基于峰谷电价的地板辐射供暖系统运行方案分析及优化
18
作者 张志强 徐大坤 +5 位作者 张文科 姚海清 赵树旺 刘霞 马雪晴 王科荀 《节能》 2023年第7期17-20,共4页
以减少供暖季热泵机组的运行费用为目标,基于峰谷电价政策提出地板辐射供暖系统运行方案的优化模型以分析系统运行过程,从而实现系统的优化控制。对全国各省份的峰谷电价政策进行分类总结;以某商用地板辐射供暖房间为研究对象,建立室内... 以减少供暖季热泵机组的运行费用为目标,基于峰谷电价政策提出地板辐射供暖系统运行方案的优化模型以分析系统运行过程,从而实现系统的优化控制。对全国各省份的峰谷电价政策进行分类总结;以某商用地板辐射供暖房间为研究对象,建立室内温度与上一时刻室内温度、供水温度、室外温度等参数之间的函数关系,并建立以日运行费用最低为目标且能够保证室内温度舒适性的优化模型;采用自适应粒子群优化算法进行寻优计算,并利用Matlab语言进行编程计算与分析。按照峰谷电价政策分类从全国选取3个典型城市,寻求地板辐射供暖系统节省费用的运行控制策略。结果显示:经过优化之后3个案例的日用电费用均明显下降,且峰与谷电价差距越大,费用节省效果越明显。 展开更多
关键词 地板辐射供暖 峰谷电价 自适应粒子群算法 优化模型
下载PDF
用于地板辐射采暖的多元水合盐复合相变砂浆的制备及性能研究
19
作者 刘洁 杨英英 +2 位作者 李爱征 王文松 任燕 《储能科学与技术》 CAS CSCD 北大核心 2023年第12期3655-3662,共8页
本研究以地板辐射采暖为应用背景,Na_(2)HPO_(4)·12H_(2)O和Na_(2)SO_(4)·10H_(2)O为原料,研发出一种新型无机水合盐复合相变砂浆。首先,采用物理共混法制备出二元混合熔融盐(80%Na_(2)HPO_(4)·12H_(2)O-20%Na_(2)SO_(4)... 本研究以地板辐射采暖为应用背景,Na_(2)HPO_(4)·12H_(2)O和Na_(2)SO_(4)·10H_(2)O为原料,研发出一种新型无机水合盐复合相变砂浆。首先,采用物理共混法制备出二元混合熔融盐(80%Na_(2)HPO_(4)·12H_(2)O-20%Na_(2)SO_(4)·10H_(2)O),并通过添加成核剂(2%Na_(2)SiO_(3)·9H_(2)O)优化其过冷度;然后,选择2~2.5 mm的膨胀珍珠岩对其进行吸附封装,得到定型复合相变材料;最后,将定型复合相变材料掺入砂浆中制备出复合相变砂浆。通过差示扫描量热法(DSC)测试,获得二元混合熔融盐、二元共晶盐和定型复合相变材料的相变焓值分别为229.1 J/g、214.1 J/g和156.7 J/g,通过电子扫描显微镜(SEM)对定型复合相变材料进行表征,发现膨胀珍珠岩与共晶盐相变材料相容性良好。所制备的复合相变砂浆的导热系数为0.63 W/(m·K),固态比热容和液态比热容分别为1.56 J/(g·K)和1.75 J/(g·K),传热系数为3.85 W/(m^(2)·K)。对复合相变砂浆进行了储热性能试验,发现与普通砂浆相比,复合相变砂浆可以更明显地减缓温度波动。在50℃恒温加热时,其冷端峰值温度比普通砂浆低2.5℃,在冷却时,其温度下降速率更小,说明复合相变砂浆具有良好的储热能力。将所制备的复合相变砂浆应用到间歇性地板辐射采暖中,可以在供暖时进行储热,使室内温度不至于过高,同时在停止供暖时释放热量,减缓室内温度降低速率,避免室内温度过低。复合相变砂浆的使用,能够在满足室内热舒适的同时抑制室内温度波动,实现热量的“移峰填谷”,减少供暖能耗,从而达到建筑节能的目的。 展开更多
关键词 无机水合盐 相变材料 砂浆 储热 地板辐射采暖
下载PDF
间歇用能特征下的干湿式地板辐射供暖热性能对比
20
作者 周文杰 朱文涛 +1 位作者 朱懿德 李涛 《西安工程大学学报》 CAS 2023年第6期26-33,共8页
针对间歇供暖应用背景下干湿式地板辐射供暖形式选择的问题,建立2种地板辐射供暖的传热数学模型,并通过实验验证了传热数学模型的准确性。利用CFD模拟仿真方法,通过改变管间距、填充层厚度以及供暖间歇时间等因素分析2种地板的散热特性... 针对间歇供暖应用背景下干湿式地板辐射供暖形式选择的问题,建立2种地板辐射供暖的传热数学模型,并通过实验验证了传热数学模型的准确性。利用CFD模拟仿真方法,通过改变管间距、填充层厚度以及供暖间歇时间等因素分析2种地板的散热特性。结果表明:填充层厚度对干式地板的热性能影响较小,主要影响湿式地板的散热速率,管间距对2种地板散热速率的影响较小,温度随管间距增大而降低。在不同间歇供暖方案下,当室外温度为8℃、室内初始温度为12℃、盘管平均温度为40℃时,干式地板温度比湿式地板高1.2~2.9℃,室内空气温度高0.5~1.3℃。干式地板不适用于供暖时间较短的间歇方案。过长或过短的间歇方案在夜间无法长久维持在舒适温度区间内,2种地板辐射供暖采用开机12 h的间歇方案运行效果较好。 展开更多
关键词 间歇供暖 热性能 地板辐射供暖 室内热环境
下载PDF