Protection of radial distribution networks is widely based on coordinated inverse time overcurrent relays (OCRs) ensuring both effectiveness and selectivity. However, the integration of distributed generation (DG) int...Protection of radial distribution networks is widely based on coordinated inverse time overcurrent relays (OCRs) ensuring both effectiveness and selectivity. However, the integration of distributed generation (DG) into an existing distribution network not only inevitably increases fault current levels to levels that may exceed the OCR ratings, but it may also disturb the original overcurrent relay coordination adversely effecting protection selectivity. To analyze the potentially adverse impact of DG on distribution system protective devices with respect to circuit breaker ratings and OCR coordination fault current studies are carried out for common reference test system under the influence of additional DG. The possible advantages of Superconducting Fault Current Limiter (SFCL) as a means to limit the adverse effect of DG on distribution system protection and their effectiveness will be demonstrated. Furthermore, minimum SFCL impedances required to avoid miss-operation of the primary and back-up OCRs are determined. The theoretical analysis will be validated using the IEEE 13-bus distribution test system is used. Both theoretical and simulation results indicate that the proposed application of SFCL is a viable option to effectively mitigate the DG impact on protective devices, thus enhancing the reliability of distribution network interfaced with DG.展开更多
A novel magnetic-controlled switcher type fault current limiter (FCL) based on the topology of the saturated iron core high temperature superconducting FCL is proposed. The magnetic field distribution of the FCL iron ...A novel magnetic-controlled switcher type fault current limiter (FCL) based on the topology of the saturated iron core high temperature superconducting FCL is proposed. The magnetic field distribution of the FCL iron core is analyzed by FEA software ANSYS. The current limiting characteristic is investigated by both 3-D field-circuit coupled simulation and Matlab. The experiments on the 220 V/50 A test model show that the FCL can limit the fault current swiftly and effectively,and the FCL has the advantages of simple and reliable structure, flexible control strategy. The simulation and experimental results prove that the theoretical expectation and current limiting performance is satisfactory for practical use.展开更多
The design progress of superconducting fault current limiter(SFCL)for transmission voltage is presented,with a focus on the results of recent key experiments that have led to a state‐of‐the‐art high‐voltage high‐...The design progress of superconducting fault current limiter(SFCL)for transmission voltage is presented,with a focus on the results of recent key experiments that have led to a state‐of‐the‐art high‐voltage high‐capacity super‐conducting current limiting techniques:the resistive alternating current(AC)SFCL,saturated iron cores AC SFCL,and resistive direct current(DC)SFCL.The main driving factors for designing SFCL in these projects are the preparation of high‐performance superconducting materials,the development of large‐scale superconducting current limiting winding,system testing,and operation technology.Based on the authors’experience with both AC and DC SFCLs,this paper focuses on the main design aspects of resistive SFCL at transmission voltage.The relationship between the hot spot caused by the inhomogeneity of long superconducting tape and the overall parameter selection is presented.In addition,the thermal calculation based on the current limiting resistance and a real‐time current curve is also proposed for the parameter design of the current limiting winding.展开更多
In DC micro grids and networks,DC-DC power converters having a large number of semiconductor-based power electronic devices are usually adopted to interconnect the renewable sources and flexible loads.Most of the semi...In DC micro grids and networks,DC-DC power converters having a large number of semiconductor-based power electronic devices are usually adopted to interconnect the renewable sources and flexible loads.Most of the semiconductor-based devices suffer from poor fault withstanding abilities,but conventional power electronic protection schemes have the bottlenecks of the time-delay,self-malfunction and mis-judgement.This paper presents a novel solution using the superconducting fault current limiter(SFCL)to protect a power electronic device and extend the usage to a micro grid.This SFCL is actually a self-triggering,recoverable,and passive current limiter,which does not involve any additional circuit hardware and software.Experimental investigations and simulation analyses clarify the feasibility of using this superconductor-based protection scheme to implement the self-acting fail-safe protection of DC-DC converters.Further system-level simulations explore the SFCL to suppress the over-current and stabilize the bus voltage of a photovoltaic based DC micro grid,particularly facing millisecond-level transients and faults.Our experimental and theoretical investigations lay some technical bases to establish a superconductor-semiconductor-coupled interdisciplinary application from the view from the applied superconductivity,to power electronics,and to micro grids.展开更多
随着电力负荷快速增长,电力系统的故障电流水平持续上升,甚至超出了现有断路器的开断能力;为有效限制故障电流,超导故障限流器(superconducting fault current limiter,SFCL)逐渐投入应用。SFCL在正常运行时呈现零阻抗,故障发生后迅速...随着电力负荷快速增长,电力系统的故障电流水平持续上升,甚至超出了现有断路器的开断能力;为有效限制故障电流,超导故障限流器(superconducting fault current limiter,SFCL)逐渐投入应用。SFCL在正常运行时呈现零阻抗,故障发生后迅速转为高阻抗,可作为配合断路器开断的理想选择,提高电力系统的运行安全性。介绍了一种磁偏置型超导故障限流器(magneto-biased superconducting fault current limiter,MBSFCL),提出了考虑短路电流非周期分量影响的MBSFCL设计方法,对于MBSFCL的制造具有一定的指导意义。通过搭建仿真模型,验证了所提出方法的可行性,并对MBSFCL的限流特性进行了深入分析,讨论了不同非周期分量对断路器的开断影响,以及MBSFCL中电感、电阻参数变化对短路电流及其分量的限流效果影响。分析结果表明,在所提出MBSFCL设计方法中必须考虑非周期分量,且MBSFCL的电阻参数变化对短路电流的抑制效果更为显著。展开更多
在综合大量文献的基础上综述了国内外各种故障限流装置的研究现状、发展应用,特别对广泛应用的电力电子类故障限流器 FCL(Fault Current Limiter)和前景广阔的超导类故障限流器 SFCL(Superconducting Fault Current Limiter)进行了比较...在综合大量文献的基础上综述了国内外各种故障限流装置的研究现状、发展应用,特别对广泛应用的电力电子类故障限流器 FCL(Fault Current Limiter)和前景广阔的超导类故障限流器 SFCL(Superconducting Fault Current Limiter)进行了比较深入的分析,对各类限流装置的技术水平做了比较,提出了实用化过程中存在的应用问题,并对限流装置的发展趋势做出了预测。展开更多
直流故障隔离技术是多端柔性直流输、配电系统发展的关键技术。然而,直流系统直流侧故障存在电流快速上升、过流幅值大等特点,对隔离技术提出了极为苛刻的要求。该文针对工程实际中最为典型的两电平电压源换流器(two-level voltage sour...直流故障隔离技术是多端柔性直流输、配电系统发展的关键技术。然而,直流系统直流侧故障存在电流快速上升、过流幅值大等特点,对隔离技术提出了极为苛刻的要求。该文针对工程实际中最为典型的两电平电压源换流器(two-level voltage source converter,two-level VSC)型和模块化多电平换流器(modular multi-level converter,MMC)型直流系统,结合国内外研究成果,以交流断路器、换流器和直流断路器为分类依据,归纳、阐述了各自适用的隔离措施。同时,对各种隔离措施的优缺点进行了分析说明。基于Matlab/Simulink仿真平台,分别搭建了基于两电平VSC和MMC的直流系统,对相关隔离方法进行了仿真测试、验证与比较,为工程实际中隔离措施的配置提供理论依据。展开更多
文摘Protection of radial distribution networks is widely based on coordinated inverse time overcurrent relays (OCRs) ensuring both effectiveness and selectivity. However, the integration of distributed generation (DG) into an existing distribution network not only inevitably increases fault current levels to levels that may exceed the OCR ratings, but it may also disturb the original overcurrent relay coordination adversely effecting protection selectivity. To analyze the potentially adverse impact of DG on distribution system protective devices with respect to circuit breaker ratings and OCR coordination fault current studies are carried out for common reference test system under the influence of additional DG. The possible advantages of Superconducting Fault Current Limiter (SFCL) as a means to limit the adverse effect of DG on distribution system protection and their effectiveness will be demonstrated. Furthermore, minimum SFCL impedances required to avoid miss-operation of the primary and back-up OCRs are determined. The theoretical analysis will be validated using the IEEE 13-bus distribution test system is used. Both theoretical and simulation results indicate that the proposed application of SFCL is a viable option to effectively mitigate the DG impact on protective devices, thus enhancing the reliability of distribution network interfaced with DG.
基金Major State Basic Research Development Program of China ( No.2005CB221505)Research Foundation for the Doctoral Programof Higher Education of China(No.20050248058)
文摘A novel magnetic-controlled switcher type fault current limiter (FCL) based on the topology of the saturated iron core high temperature superconducting FCL is proposed. The magnetic field distribution of the FCL iron core is analyzed by FEA software ANSYS. The current limiting characteristic is investigated by both 3-D field-circuit coupled simulation and Matlab. The experiments on the 220 V/50 A test model show that the FCL can limit the fault current swiftly and effectively,and the FCL has the advantages of simple and reliable structure, flexible control strategy. The simulation and experimental results prove that the theoretical expectation and current limiting performance is satisfactory for practical use.
基金supported in part by the National Key Research and Development Program under Grant 2017YFB0902300。
文摘The design progress of superconducting fault current limiter(SFCL)for transmission voltage is presented,with a focus on the results of recent key experiments that have led to a state‐of‐the‐art high‐voltage high‐capacity super‐conducting current limiting techniques:the resistive alternating current(AC)SFCL,saturated iron cores AC SFCL,and resistive direct current(DC)SFCL.The main driving factors for designing SFCL in these projects are the preparation of high‐performance superconducting materials,the development of large‐scale superconducting current limiting winding,system testing,and operation technology.Based on the authors’experience with both AC and DC SFCLs,this paper focuses on the main design aspects of resistive SFCL at transmission voltage.The relationship between the hot spot caused by the inhomogeneity of long superconducting tape and the overall parameter selection is presented.In addition,the thermal calculation based on the current limiting resistance and a real‐time current curve is also proposed for the parameter design of the current limiting winding.
基金the National Natural Science Foundation of China[Grant No.51807128].
文摘In DC micro grids and networks,DC-DC power converters having a large number of semiconductor-based power electronic devices are usually adopted to interconnect the renewable sources and flexible loads.Most of the semiconductor-based devices suffer from poor fault withstanding abilities,but conventional power electronic protection schemes have the bottlenecks of the time-delay,self-malfunction and mis-judgement.This paper presents a novel solution using the superconducting fault current limiter(SFCL)to protect a power electronic device and extend the usage to a micro grid.This SFCL is actually a self-triggering,recoverable,and passive current limiter,which does not involve any additional circuit hardware and software.Experimental investigations and simulation analyses clarify the feasibility of using this superconductor-based protection scheme to implement the self-acting fail-safe protection of DC-DC converters.Further system-level simulations explore the SFCL to suppress the over-current and stabilize the bus voltage of a photovoltaic based DC micro grid,particularly facing millisecond-level transients and faults.Our experimental and theoretical investigations lay some technical bases to establish a superconductor-semiconductor-coupled interdisciplinary application from the view from the applied superconductivity,to power electronics,and to micro grids.
文摘随着电力负荷快速增长,电力系统的故障电流水平持续上升,甚至超出了现有断路器的开断能力;为有效限制故障电流,超导故障限流器(superconducting fault current limiter,SFCL)逐渐投入应用。SFCL在正常运行时呈现零阻抗,故障发生后迅速转为高阻抗,可作为配合断路器开断的理想选择,提高电力系统的运行安全性。介绍了一种磁偏置型超导故障限流器(magneto-biased superconducting fault current limiter,MBSFCL),提出了考虑短路电流非周期分量影响的MBSFCL设计方法,对于MBSFCL的制造具有一定的指导意义。通过搭建仿真模型,验证了所提出方法的可行性,并对MBSFCL的限流特性进行了深入分析,讨论了不同非周期分量对断路器的开断影响,以及MBSFCL中电感、电阻参数变化对短路电流及其分量的限流效果影响。分析结果表明,在所提出MBSFCL设计方法中必须考虑非周期分量,且MBSFCL的电阻参数变化对短路电流的抑制效果更为显著。
文摘在综合大量文献的基础上综述了国内外各种故障限流装置的研究现状、发展应用,特别对广泛应用的电力电子类故障限流器 FCL(Fault Current Limiter)和前景广阔的超导类故障限流器 SFCL(Superconducting Fault Current Limiter)进行了比较深入的分析,对各类限流装置的技术水平做了比较,提出了实用化过程中存在的应用问题,并对限流装置的发展趋势做出了预测。