In order to minimize the harmonic distortion rate of the current at the common coupling point,this paper proposes a coordinated allocation strategy of harmonic compensation capacity considering the performance of acti...In order to minimize the harmonic distortion rate of the current at the common coupling point,this paper proposes a coordinated allocation strategy of harmonic compensation capacity considering the performance of active power filters(APF).On the premise of proportional distribution of harmonic compensation capacity,the harmonic compensation rate of each APF is considered,and the harmonic current value of each APF to be compensated is obtained.At the same time,the communication topology is introduced.Each APF takes into account the compensation ability of other APFs.Finally,three APFs with different capacity and performance are configured at the harmonic source to suppress the same harmonic source,and the harmonic distortion rate is reduced to 1.73%.The simulation results show that the strategy can effectively improve the compensation capability of the multiple APF cascaded system to the power grid without increasing the installed capacity.展开更多
基金This work was supported in part by the National Natural Science Foundation of China(Grant No.61863023).
文摘In order to minimize the harmonic distortion rate of the current at the common coupling point,this paper proposes a coordinated allocation strategy of harmonic compensation capacity considering the performance of active power filters(APF).On the premise of proportional distribution of harmonic compensation capacity,the harmonic compensation rate of each APF is considered,and the harmonic current value of each APF to be compensated is obtained.At the same time,the communication topology is introduced.Each APF takes into account the compensation ability of other APFs.Finally,three APFs with different capacity and performance are configured at the harmonic source to suppress the same harmonic source,and the harmonic distortion rate is reduced to 1.73%.The simulation results show that the strategy can effectively improve the compensation capability of the multiple APF cascaded system to the power grid without increasing the installed capacity.