Thermal Dissipation Modelling and Design of ITER PF Converter Alternating Current Busbar 被引量:2
1
作者 郭斌 宋执权 +4 位作者 傅鹏 蒋力 李金超 王敏 董琳 《Plasma Science and Technology》 SCIE EI CAS CSCD 2016年第10期1049-1054,共6页
Because the larger metallic surrounds are heated by the eddy current, which is generated by the AC current flowing through the AC busbar in the International Thermonuclear ExperimentM Reactor (ITER) poloidal field ... Because the larger metallic surrounds are heated by the eddy current, which is generated by the AC current flowing through the AC busbar in the International Thermonuclear ExperimentM Reactor (ITER) poloidal field (PF) converter system, shielding of the AC busbar is required to decrease the temperature rise of the surrounds to satisfy the design requirement. Three special types of AC busbar with natural cooling, air cooling and water cooling busbar structure have been proposed and investigated in this paper. For each cooling scheme, a 3D finite model based on the proposed structure has been developed to perform the electromagnetic and thermal analysis to predict their operation behavior. Comparing the analysis results of the three different cooling patterns, water cooling has more advantages than the other patterns and it is selected to be the thermal dissipation pattern for the AC busbar of ITER PF converter unit. The approach to qualify the suitable cooling scheme in this paper can be provided as a reference on the thermal dissipation design of AC busbar in the converter system. 展开更多
关键词 thermal dissipation modelling and design AC busbar CONVERTER