Due to the low impedance characteristic of the high voltage direct current(HVDC)grid,the fault current rises extremely fast after a DC-side fault occurs,and this phenomenon seriously endangers the safety of the HVDC g...Due to the low impedance characteristic of the high voltage direct current(HVDC)grid,the fault current rises extremely fast after a DC-side fault occurs,and this phenomenon seriously endangers the safety of the HVDC grid.In order to suppress the rising speed of the fault current and reduce the current interruption requirements of the main breaker(MB),a fault current limiting hybrid DC circuit breaker(FCL-HCB)has been proposed in this paper,and it has the capability of bidirectional fault current limiting and fault current interruption.After the occurrence of the overcurrent in the HVDC grid,the current limiting circuit(CLC)of FCL-HCB is put into operation immediately,and whether the protected line is cut off or resumed to normal operation is decided according to the fault detection result.Compared with the traditional hybrid DC circuit breaker(HCB),the required number of semiconductor switches and the peak value of fault current after fault occurs are greatly reduced by adopting the proposed device.Extensive simulations also verify the effectiveness of the proposed FCL-HCB.展开更多
Firstly, relevant stress properties of millisecond level breaking process and microsecond level commutation process of hybrid HVDC circuit breaker are studied in detail on the basis of the analysis for the application...Firstly, relevant stress properties of millisecond level breaking process and microsecond level commutation process of hybrid HVDC circuit breaker are studied in detail on the basis of the analysis for the application environment and topological structure and operating principles of hybrid circuit breakers, and key stress parameters in transient state process of two time dimensions are extracted. The established digital simulation circuit for PSCAD/EMTDC device-level operation of the circuit breaker has verified the stress properties of millisecond level breaking process and microsecond level commutation process. Then, equivalent test method, circuits and parameters based on LC power supply are proposed on the basis of stress extraction. Finally, the results of implemented breaking tests for complete 200 kV circuit breaker, 100 kV and 50 kV circuit breaker units, as well as single power electronic module have verified the accuracy of the simulation circuit and mathematical analysis. The result of this paper can be a guide to electrical structure and test system design of hybrid HVDC circuit breaker.展开更多
DC circuit breakers are major enabling components for multi-terminal HVDC systems.Their key design targets are operating speed and efficiency.This paper proposes a novel moving coil actuator using a compensation coil ...DC circuit breakers are major enabling components for multi-terminal HVDC systems.Their key design targets are operating speed and efficiency.This paper proposes a novel moving coil actuator using a compensation coil topology to operate mechanical circuit breakers.This topology aims to significantly improve the magnetic field saturation and reduce the system inductance,so that the operating speed is increased.Four possible connection methods for the compensation coils are proposed and analyzed using finite element modeling,ensuing simulation results are compared and discussed.The operating speed of the moving coil actuator with compensation coils is significantly improved compared with the original moving coil actuator.The moving coil actuator with compensation coils can open a distance of 5 mm within 2.8 ms and the peak efficiency is 47%.展开更多
High voltage direct current(HVDC)systems are efficient solutions for the integration of large-scale renewable energy sources with the main power grids.The rapid development of the HVDC grid has resulted in a growing i...High voltage direct current(HVDC)systems are efficient solutions for the integration of large-scale renewable energy sources with the main power grids.The rapid development of the HVDC grid has resulted in a growing interest in DC circuit breakers(DCCBs).A fast and reliable circuit breaker is a necessary requirement in the development of large scale HVDC grids.This paper provides a comprehensive review and survey of the HVDC CBs and discusses potential research directions.Operational principles and the main features of various DCCBs are described and their merits and shortcomings are also highlighted.展开更多
This paper proposes a star type multiport hybrid circuit breaker(Star-HCB)topology for protection of multiterminal DC transmission.Reliability and stability of high voltage DC(HVDC)grids are determined by their capabi...This paper proposes a star type multiport hybrid circuit breaker(Star-HCB)topology for protection of multiterminal DC transmission.Reliability and stability of high voltage DC(HVDC)grids are determined by their capabilities to withstand DC-side faults.In order to maintain reliability of HVDC grids,both ends of each line should be equipped with hybrid circuit breakers(HCB).This method will increase expenditure of the HVDC,especially the meshed topology.The n-port Star-HCB consists of ultra-fast mechanical disconnectors,load current switch and only one transferring branch which is formed by improved half-bridge sub-module.Compared with existing traditional hybrid circuit breakers and other multiport hybrid circuit breakers,the proposed topology can realize the same short-circuit blocking goal using fewer components.Detailed mathematical transient process calculation and timedomain simulation of the proposed Star-HCB are given to verify its superiority.展开更多
基金This project is funded by the Dongying Science Development Fund Project(DJ2021013).
文摘Due to the low impedance characteristic of the high voltage direct current(HVDC)grid,the fault current rises extremely fast after a DC-side fault occurs,and this phenomenon seriously endangers the safety of the HVDC grid.In order to suppress the rising speed of the fault current and reduce the current interruption requirements of the main breaker(MB),a fault current limiting hybrid DC circuit breaker(FCL-HCB)has been proposed in this paper,and it has the capability of bidirectional fault current limiting and fault current interruption.After the occurrence of the overcurrent in the HVDC grid,the current limiting circuit(CLC)of FCL-HCB is put into operation immediately,and whether the protected line is cut off or resumed to normal operation is decided according to the fault detection result.Compared with the traditional hybrid DC circuit breaker(HCB),the required number of semiconductor switches and the peak value of fault current after fault occurs are greatly reduced by adopting the proposed device.Extensive simulations also verify the effectiveness of the proposed FCL-HCB.
基金supported by SGCC Scientific and Technological Project(52110116004W)
文摘Firstly, relevant stress properties of millisecond level breaking process and microsecond level commutation process of hybrid HVDC circuit breaker are studied in detail on the basis of the analysis for the application environment and topological structure and operating principles of hybrid circuit breakers, and key stress parameters in transient state process of two time dimensions are extracted. The established digital simulation circuit for PSCAD/EMTDC device-level operation of the circuit breaker has verified the stress properties of millisecond level breaking process and microsecond level commutation process. Then, equivalent test method, circuits and parameters based on LC power supply are proposed on the basis of stress extraction. Finally, the results of implemented breaking tests for complete 200 kV circuit breaker, 100 kV and 50 kV circuit breaker units, as well as single power electronic module have verified the accuracy of the simulation circuit and mathematical analysis. The result of this paper can be a guide to electrical structure and test system design of hybrid HVDC circuit breaker.
文摘DC circuit breakers are major enabling components for multi-terminal HVDC systems.Their key design targets are operating speed and efficiency.This paper proposes a novel moving coil actuator using a compensation coil topology to operate mechanical circuit breakers.This topology aims to significantly improve the magnetic field saturation and reduce the system inductance,so that the operating speed is increased.Four possible connection methods for the compensation coils are proposed and analyzed using finite element modeling,ensuing simulation results are compared and discussed.The operating speed of the moving coil actuator with compensation coils is significantly improved compared with the original moving coil actuator.The moving coil actuator with compensation coils can open a distance of 5 mm within 2.8 ms and the peak efficiency is 47%.
文摘High voltage direct current(HVDC)systems are efficient solutions for the integration of large-scale renewable energy sources with the main power grids.The rapid development of the HVDC grid has resulted in a growing interest in DC circuit breakers(DCCBs).A fast and reliable circuit breaker is a necessary requirement in the development of large scale HVDC grids.This paper provides a comprehensive review and survey of the HVDC CBs and discusses potential research directions.Operational principles and the main features of various DCCBs are described and their merits and shortcomings are also highlighted.
基金supported by the Institute of Electrical Engineering,CAS under grant(E155610101,E155610201 and E155610301).
文摘This paper proposes a star type multiport hybrid circuit breaker(Star-HCB)topology for protection of multiterminal DC transmission.Reliability and stability of high voltage DC(HVDC)grids are determined by their capabilities to withstand DC-side faults.In order to maintain reliability of HVDC grids,both ends of each line should be equipped with hybrid circuit breakers(HCB).This method will increase expenditure of the HVDC,especially the meshed topology.The n-port Star-HCB consists of ultra-fast mechanical disconnectors,load current switch and only one transferring branch which is formed by improved half-bridge sub-module.Compared with existing traditional hybrid circuit breakers and other multiport hybrid circuit breakers,the proposed topology can realize the same short-circuit blocking goal using fewer components.Detailed mathematical transient process calculation and timedomain simulation of the proposed Star-HCB are given to verify its superiority.