The neutral grounding mode of medium-voltage distribution network decides the reliability, overvoltage, relay protection and electrical safety. Therefore, a comprehensive consideration of the reliability, safety and e...The neutral grounding mode of medium-voltage distribution network decides the reliability, overvoltage, relay protection and electrical safety. Therefore, a comprehensive consideration of the reliability, safety and economy is particularly important for the decision of neutral grounding mode. This paper proposes a new decision method of neutral point grounding mode for mediumvoltage distribution network. The objective function is constructed for the decision according the life cycle cost. The reliability of the neutral point grounding mode is taken into account through treating the outage cost as an operating cost. The safety condition of the neutral point grounding mode is preserved as the constraint condition of decision models, so the decision method can generate the most economical and reliable scheme of neutral point grounding mode within a safe limit. The example is used to verify the feasibility and effectiveness of the decision method.展开更多
多电源系统在相互切换时因中性线接地方式的不同,将会对不间断电源(uninterruptible power supply,UPS)系统性能产生较大影响。首先,在三极和四极自动转换开关基础上,通过不同接地方式搭建了多电源系统电路等效模型,探讨了不同电路结构...多电源系统在相互切换时因中性线接地方式的不同,将会对不间断电源(uninterruptible power supply,UPS)系统性能产生较大影响。首先,在三极和四极自动转换开关基础上,通过不同接地方式搭建了多电源系统电路等效模型,探讨了不同电路结构的优缺点,并通过搭建MATLAB/Simulink仿真模型,对多电源系统电路性能指标进行了仿真验证;在多电源系统电路基础上,搭建了多电源系统UPS电路MATLAB/Simulink仿真模型,对多电源系统UPS电路关键性能指标进行了仿真实验。其次,以多电源系统UPS电路不产生杂散电流,中性线不分流,中性线接地基准连续,多路输入电源之间、输入电源与输出电源之间、输入电源与旁路电源之间电气隔离等性能指标为优化目标,提出了3种多电源系统UPS电路结构优化方案。最后,搭建3种优化改进电路MATLAB/Simulink仿真模型,对3种UPS电路性能指标进行仿真实验,实验表明改进方案三“多电源系统UPS电源电路加装旁路隔离变压器”具有多电源系统UPS电源电路最优性能指标。展开更多
文摘The neutral grounding mode of medium-voltage distribution network decides the reliability, overvoltage, relay protection and electrical safety. Therefore, a comprehensive consideration of the reliability, safety and economy is particularly important for the decision of neutral grounding mode. This paper proposes a new decision method of neutral point grounding mode for mediumvoltage distribution network. The objective function is constructed for the decision according the life cycle cost. The reliability of the neutral point grounding mode is taken into account through treating the outage cost as an operating cost. The safety condition of the neutral point grounding mode is preserved as the constraint condition of decision models, so the decision method can generate the most economical and reliable scheme of neutral point grounding mode within a safe limit. The example is used to verify the feasibility and effectiveness of the decision method.
文摘多电源系统在相互切换时因中性线接地方式的不同,将会对不间断电源(uninterruptible power supply,UPS)系统性能产生较大影响。首先,在三极和四极自动转换开关基础上,通过不同接地方式搭建了多电源系统电路等效模型,探讨了不同电路结构的优缺点,并通过搭建MATLAB/Simulink仿真模型,对多电源系统电路性能指标进行了仿真验证;在多电源系统电路基础上,搭建了多电源系统UPS电路MATLAB/Simulink仿真模型,对多电源系统UPS电路关键性能指标进行了仿真实验。其次,以多电源系统UPS电路不产生杂散电流,中性线不分流,中性线接地基准连续,多路输入电源之间、输入电源与输出电源之间、输入电源与旁路电源之间电气隔离等性能指标为优化目标,提出了3种多电源系统UPS电路结构优化方案。最后,搭建3种优化改进电路MATLAB/Simulink仿真模型,对3种UPS电路性能指标进行仿真实验,实验表明改进方案三“多电源系统UPS电源电路加装旁路隔离变压器”具有多电源系统UPS电源电路最优性能指标。