This paper focuses on the transient protection of transmission line with FACTS Devices;the principle and mathematical model of static synchronous compensator (STATCOM) has been analyzed. And feasible control strategy ...This paper focuses on the transient protection of transmission line with FACTS Devices;the principle and mathematical model of static synchronous compensator (STATCOM) has been analyzed. And feasible control strategy has been proposed considering the voltage source inverter (VSI) as a core part of the FACTS components. The simulation results verify the rightness using electromagnetic transient simulation software PSCAD/EMTDC to set up electromagnetic transient model.展开更多
Multi-terminal hybrid high-voltage direct current(HVDC)systems have been developed quickly in recent years in power transmission area.However,for voltage-source converter(VSC)stations in hybrid HVDC systems,no direct ...Multi-terminal hybrid high-voltage direct current(HVDC)systems have been developed quickly in recent years in power transmission area.However,for voltage-source converter(VSC)stations in hybrid HVDC systems,no direct current(DC)filters are required.In addition,the DC reactor is also not installed at the line end because the DC fault can be limited by the converter itself.This means that the boundary element at the line end is absent,and the single-ended protections used in line commutated converter(LCC)based HVDC(LCC-HVDC)systems or VSC-HVDC systems cannot distinguish the fault line in multi-terminal hybrid HVDC systems.This paper proposes a novel singleended DC protection strategy suitable for the multi-terminal hybrid HVDC system,which mainly applies the transient information and active injection concept to detect and distinguish the fault line.Compared with the single-ended protections used in LCC-HVDC and VSC-HVDC systems,the proposed protection strategy is not dependent on the line boundary element and is thus suitable for the multiterminal hybrid HVDC system.The corresponding simulation cases based on power systems computer aided design(PSCAD)/electromagnetic transients including DC(EMTDC)are carried out to verify the superiority of the proposed protection.展开更多
The paper is concerned with whether CT transient saturation, which caused by sympathetic inrush, is the direct reason for mal-operation of transformer differential relays. In order to analyze transforming characterist...The paper is concerned with whether CT transient saturation, which caused by sympathetic inrush, is the direct reason for mal-operation of transformer differential relays. In order to analyze transforming characteristics of saturated CT, the gain of each harmonic current transforming from primary winding to secondary winding of transient saturation CT is calculated. Based on the fact that series sympathetic inrush is easier to lead differential relay mal-operation than parallel sympathetic inrush, the effect of CT saturation on differential relay?in the case of both parallel sympathetic inrush and series sympathetic inrush are investigated respectively. Theory analysis and simulation show that higher harmonic will be transferred by saturated CT more easily than lower harmonic, and then the second harmonic proportion of CT secondary side is higher than that of CT primary side. Thus CT transient saturation itself is not essential reason for differential relay mal-operation. Parallel sympathetic inrush and series sympathetic inrush will lead to different location CT saturated. Parallel sympathetic inrush will lead to CT located system side saturated;second harmonic ratio of differential current increase and dead angle is large. Series sympathetic inrush will lead to CT located load side saturated;second harmonic ratio of differential current decrease and dead angle is small.展开更多
This paper presents an integrated relay and its associated protection scheme for power transmission lines.The concept of integrated protection is firstly introduced,in which a centralized protection system or relay pr...This paper presents an integrated relay and its associated protection scheme for power transmission lines.The concept of integrated protection is firstly introduced,in which a centralized protection system or relay provides the protection for multiple power plants or a substation.A novel integrated protection relay based on the combination of a number of protection principles is described.In the proposed scheme,the specially designed protection relays are installed at each substation of a network and are responsible for the protection of every line section connected to the substation busbar.The combined algorithms with multiple settings are implemented into the relay to cover all the protected line sections.Simulation studies show that the proposed protection scheme is able to produce desirable performance and may offer many advantages over the existing one and great potential for future applications.展开更多
Current phase comparison based pilot protection had been generally utilized as primary protection of the transmission lines in China from the 1950's to the 1980' s, Comentional phase comparison pilot protection has ...Current phase comparison based pilot protection had been generally utilized as primary protection of the transmission lines in China from the 1950's to the 1980' s, Comentional phase comparison pilot protection has a long phase comparison time, which results in a longer fault-clearing time. This paper proposes a new current phase comparison, pilot protection scheme that is based on non-power frequency fauh eun'ent component. The phase of the fourth harmonic eun'ent of each end of the protected line has heen abstracted hy utilizing complex wavelet transformation and then compared in order to determine whether the inner fauh occurs or not. This way can greatly deerease fauh-elearing time and improve performances of this pilot protection when fault occurs under the heavy-load current and asymmetrical operation eonditions, Many EMTP simulations have verified the proposed scheme's correctness and effectiveness.展开更多
不对称接地故障占所有线路故障的90%以上,接地距离保护在应对此类故障方面发挥了不可替代的作用。随着新能源高比例渗透,各种传统单端工频量保护性能显著下降已成为共识。基于故障分量线模和零模波速差的保护判据理论上仅需利用到故障...不对称接地故障占所有线路故障的90%以上,接地距离保护在应对此类故障方面发挥了不可替代的作用。随着新能源高比例渗透,各种传统单端工频量保护性能显著下降已成为共识。基于故障分量线模和零模波速差的保护判据理论上仅需利用到故障初始行波到达时刻信息,是一种原理简单可靠的单端量快速保护判据,已经在直流电网中成功实践。但在尝试将这类保护应用于交流电网时发现,受波头前陡较缓而难以精确定位波到时刻、依赖高采样率等诸多不利因素影响,存在过大的模糊判别区,除了特长线路外,对绝大部分线路几乎没有应用可行性。波到时刻的精准辨识是一个复杂的非线性问题,利用人工智能的方法进行辨识是一条可行的解决思路,对此,该文提出一种新的单端暂态量主保护判据。首先,分析波达时刻与波形关系,并指出这种关系能够采用机器学习来映射;其次,引入高斯过程回归(Gaussian process regression,GPR),在对初始行波数据进行预处理得到样本集后,输入GPR预测模型进行训练;然后,依据模型评估指标得到最优训练模型以输出高可信性的线-零模波达时差,据此实现了基于行波模量传输时间差的保护判据;最后,在利用PSCAD仿真验证所提保护判据有效性和普适性的基础上,进一步利用现场实测数据对判据进行测试,验证其实用性。该文工作为新能源交流系统下单端暂态量保护的性能提升提供新的解决思路。展开更多
文摘This paper focuses on the transient protection of transmission line with FACTS Devices;the principle and mathematical model of static synchronous compensator (STATCOM) has been analyzed. And feasible control strategy has been proposed considering the voltage source inverter (VSI) as a core part of the FACTS components. The simulation results verify the rightness using electromagnetic transient simulation software PSCAD/EMTDC to set up electromagnetic transient model.
文摘Multi-terminal hybrid high-voltage direct current(HVDC)systems have been developed quickly in recent years in power transmission area.However,for voltage-source converter(VSC)stations in hybrid HVDC systems,no direct current(DC)filters are required.In addition,the DC reactor is also not installed at the line end because the DC fault can be limited by the converter itself.This means that the boundary element at the line end is absent,and the single-ended protections used in line commutated converter(LCC)based HVDC(LCC-HVDC)systems or VSC-HVDC systems cannot distinguish the fault line in multi-terminal hybrid HVDC systems.This paper proposes a novel singleended DC protection strategy suitable for the multi-terminal hybrid HVDC system,which mainly applies the transient information and active injection concept to detect and distinguish the fault line.Compared with the single-ended protections used in LCC-HVDC and VSC-HVDC systems,the proposed protection strategy is not dependent on the line boundary element and is thus suitable for the multiterminal hybrid HVDC system.The corresponding simulation cases based on power systems computer aided design(PSCAD)/electromagnetic transients including DC(EMTDC)are carried out to verify the superiority of the proposed protection.
文摘The paper is concerned with whether CT transient saturation, which caused by sympathetic inrush, is the direct reason for mal-operation of transformer differential relays. In order to analyze transforming characteristics of saturated CT, the gain of each harmonic current transforming from primary winding to secondary winding of transient saturation CT is calculated. Based on the fact that series sympathetic inrush is easier to lead differential relay mal-operation than parallel sympathetic inrush, the effect of CT saturation on differential relay?in the case of both parallel sympathetic inrush and series sympathetic inrush are investigated respectively. Theory analysis and simulation show that higher harmonic will be transferred by saturated CT more easily than lower harmonic, and then the second harmonic proportion of CT secondary side is higher than that of CT primary side. Thus CT transient saturation itself is not essential reason for differential relay mal-operation. Parallel sympathetic inrush and series sympathetic inrush will lead to different location CT saturated. Parallel sympathetic inrush will lead to CT located system side saturated;second harmonic ratio of differential current increase and dead angle is large. Series sympathetic inrush will lead to CT located load side saturated;second harmonic ratio of differential current decrease and dead angle is small.
基金National Natural Science Foundation of China(No.50077011 and 50377019)National Basic Research Project("973"Project No.2004CB217906).
文摘This paper presents an integrated relay and its associated protection scheme for power transmission lines.The concept of integrated protection is firstly introduced,in which a centralized protection system or relay provides the protection for multiple power plants or a substation.A novel integrated protection relay based on the combination of a number of protection principles is described.In the proposed scheme,the specially designed protection relays are installed at each substation of a network and are responsible for the protection of every line section connected to the substation busbar.The combined algorithms with multiple settings are implemented into the relay to cover all the protected line sections.Simulation studies show that the proposed protection scheme is able to produce desirable performance and may offer many advantages over the existing one and great potential for future applications.
基金Sponsored by the Power Electrical Science and Technology Foundation of XJ Group and the Shanghai University Foundation for Excellent Young Teacher.
文摘Current phase comparison based pilot protection had been generally utilized as primary protection of the transmission lines in China from the 1950's to the 1980' s, Comentional phase comparison pilot protection has a long phase comparison time, which results in a longer fault-clearing time. This paper proposes a new current phase comparison, pilot protection scheme that is based on non-power frequency fauh eun'ent component. The phase of the fourth harmonic eun'ent of each end of the protected line has heen abstracted hy utilizing complex wavelet transformation and then compared in order to determine whether the inner fauh occurs or not. This way can greatly deerease fauh-elearing time and improve performances of this pilot protection when fault occurs under the heavy-load current and asymmetrical operation eonditions, Many EMTP simulations have verified the proposed scheme's correctness and effectiveness.
文摘不对称接地故障占所有线路故障的90%以上,接地距离保护在应对此类故障方面发挥了不可替代的作用。随着新能源高比例渗透,各种传统单端工频量保护性能显著下降已成为共识。基于故障分量线模和零模波速差的保护判据理论上仅需利用到故障初始行波到达时刻信息,是一种原理简单可靠的单端量快速保护判据,已经在直流电网中成功实践。但在尝试将这类保护应用于交流电网时发现,受波头前陡较缓而难以精确定位波到时刻、依赖高采样率等诸多不利因素影响,存在过大的模糊判别区,除了特长线路外,对绝大部分线路几乎没有应用可行性。波到时刻的精准辨识是一个复杂的非线性问题,利用人工智能的方法进行辨识是一条可行的解决思路,对此,该文提出一种新的单端暂态量主保护判据。首先,分析波达时刻与波形关系,并指出这种关系能够采用机器学习来映射;其次,引入高斯过程回归(Gaussian process regression,GPR),在对初始行波数据进行预处理得到样本集后,输入GPR预测模型进行训练;然后,依据模型评估指标得到最优训练模型以输出高可信性的线-零模波达时差,据此实现了基于行波模量传输时间差的保护判据;最后,在利用PSCAD仿真验证所提保护判据有效性和普适性的基础上,进一步利用现场实测数据对判据进行测试,验证其实用性。该文工作为新能源交流系统下单端暂态量保护的性能提升提供新的解决思路。