The nozzle ablation process is described as two phases of heat and ablation in the interruption for an SF6 circuit breaker in this paper. Their mathematical models are established with the Fourier heat conduction diff...The nozzle ablation process is described as two phases of heat and ablation in the interruption for an SF6 circuit breaker in this paper. Their mathematical models are established with the Fourier heat conduction differential equation respectively. The masses of nozzle ablation with different arc durations and arc currents are calculated through the model of the nozzle abla- tion combined with an MHD (magneto-hydrodynamic) arc model. The time of the temperature rise on the inner surface of the nozzle under a given energy flux and of reaching the pyrolysis temperature under different energy fluxes is respectively analyzed. The relations between the mass of nozzle ablation and breaking current and arc duration are obtained. The result shows that the absorbing energy process before the nozzle ablation can be neglected under the condition of the energy flux entering into nozzle q 〉 10^9 W/m^2. The ablation is the severest during the high-current phase and the ablation mass increases rapidly with the breaking current and with arc duration respectively.展开更多
A new magnetic hydro-dynamics model for nozzle arc emphasizing the interaction of arc with PTFE (polytetrafluorethylene) vapour is established based on the conservation equations. The interruption of auto-expansion ...A new magnetic hydro-dynamics model for nozzle arc emphasizing the interaction of arc with PTFE (polytetrafluorethylene) vapour is established based on the conservation equations. The interruption of auto-expansion circuit breaker is simulated numerically by finite element method and the influence of PTFE vapour on the arc is analysed with this model. The results reveal that the flow field inside the arc chamber is determined by the arc current, the arcing time, the nozzle arc and the clogging of its thermal boundary. The establishment of quenching pressure relies on both SF6 gas and PTFE vapour that absorbed arc energy in the nozzle. The PTFE vapour leads to an increase in the pressure of nozzle arc obviously, and a decrease in the temperature of arc. But it enhances the temperature of arc at zero current and slows down the decreasing rate of arc temperature as the current decreases.展开更多
基金supported by National Natural Science Foundation of China(Nos.51177005 and 51477004)
文摘The nozzle ablation process is described as two phases of heat and ablation in the interruption for an SF6 circuit breaker in this paper. Their mathematical models are established with the Fourier heat conduction differential equation respectively. The masses of nozzle ablation with different arc durations and arc currents are calculated through the model of the nozzle abla- tion combined with an MHD (magneto-hydrodynamic) arc model. The time of the temperature rise on the inner surface of the nozzle under a given energy flux and of reaching the pyrolysis temperature under different energy fluxes is respectively analyzed. The relations between the mass of nozzle ablation and breaking current and arc duration are obtained. The result shows that the absorbing energy process before the nozzle ablation can be neglected under the condition of the energy flux entering into nozzle q 〉 10^9 W/m^2. The ablation is the severest during the high-current phase and the ablation mass increases rapidly with the breaking current and with arc duration respectively.
文摘A new magnetic hydro-dynamics model for nozzle arc emphasizing the interaction of arc with PTFE (polytetrafluorethylene) vapour is established based on the conservation equations. The interruption of auto-expansion circuit breaker is simulated numerically by finite element method and the influence of PTFE vapour on the arc is analysed with this model. The results reveal that the flow field inside the arc chamber is determined by the arc current, the arcing time, the nozzle arc and the clogging of its thermal boundary. The establishment of quenching pressure relies on both SF6 gas and PTFE vapour that absorbed arc energy in the nozzle. The PTFE vapour leads to an increase in the pressure of nozzle arc obviously, and a decrease in the temperature of arc. But it enhances the temperature of arc at zero current and slows down the decreasing rate of arc temperature as the current decreases.