Due to the complexity of the valve side winding voltage of the converter transformer, the insulation characteristics of the oil-impregnated pressboard(OIP) of the converter transformer are different from those of the ...Due to the complexity of the valve side winding voltage of the converter transformer, the insulation characteristics of the oil-impregnated pressboard(OIP) of the converter transformer are different from those of the traditional AC transformer. The study on effect of temperature on the creeping discharge characteristics of OIP under combined AC–DC voltage is seriously inadequate. Therefore, this paper investigates the characteristics of OIP creepage discharge under combined AC–DC voltage and discusses the influence of temperature on creepage discharge characteristics under different temperatures from 70 °C to 110 °C. The experimental results show that the partial discharge inception voltage and flashover voltage decrease with increasing temperature. The times of low amplitude discharge(LAD) decrease and amplitude of LAD increases. Simultaneously, the times of high amplitude discharge(HAD) gradually increase at each stage of creepage discharge with higher temperature. The analysis indicates that the charge carriers easily accumulate and quickly migrate directional movement along the electric field ahead of discharging. The residual charge carriers are more easily dissipated after discharging.The ‘hump’ region of LAD moves to the direction of higher discharge magnitude. The interval time between two continuous discharges is shortened obviously. The concentration of HAD accelerates the development of OIP insulation creepage discharge. The temperature had an accelerating effect on the development of discharge in the OIP under applying voltage.展开更多
AC and DC breakdown tests were performed on large populations of oil-impregnated pressboard samples. The effect of voltage ramp rate on dielectric strength has been investigated. A statistical analysis of breakdown da...AC and DC breakdown tests were performed on large populations of oil-impregnated pressboard samples. The effect of voltage ramp rate on dielectric strength has been investigated. A statistical analysis of breakdown data was carried out using the Weibull distribution. The 90% confidence intervals of Weibull graphs were calculated. The study shows that dielectric strength and shape parameter change versus ramp rate. The variations are attributed to the size and number of defects. Discharges occur from the oil to the oil-pressboard interface and lead to breakdown. DC dielectric strength is larger than that corresponding to AC voltage. This is ascribed to the dissipated energy difference under the two types of field and the fatigue produced by the alternating voltage. This phenomenon is related to space charge. Under DC stress, dielectric strength is higher under negative polarity. It is assigned to the different quantities of space charge accumulated under the two polarities.展开更多
基金supported by the Natural Science Foundation of Qinghai Province(No.2016-ZJ-925Q)Chinese National Programs for Fundamental Research(No.2011CB209400)
文摘Due to the complexity of the valve side winding voltage of the converter transformer, the insulation characteristics of the oil-impregnated pressboard(OIP) of the converter transformer are different from those of the traditional AC transformer. The study on effect of temperature on the creeping discharge characteristics of OIP under combined AC–DC voltage is seriously inadequate. Therefore, this paper investigates the characteristics of OIP creepage discharge under combined AC–DC voltage and discusses the influence of temperature on creepage discharge characteristics under different temperatures from 70 °C to 110 °C. The experimental results show that the partial discharge inception voltage and flashover voltage decrease with increasing temperature. The times of low amplitude discharge(LAD) decrease and amplitude of LAD increases. Simultaneously, the times of high amplitude discharge(HAD) gradually increase at each stage of creepage discharge with higher temperature. The analysis indicates that the charge carriers easily accumulate and quickly migrate directional movement along the electric field ahead of discharging. The residual charge carriers are more easily dissipated after discharging.The ‘hump’ region of LAD moves to the direction of higher discharge magnitude. The interval time between two continuous discharges is shortened obviously. The concentration of HAD accelerates the development of OIP insulation creepage discharge. The temperature had an accelerating effect on the development of discharge in the OIP under applying voltage.
文摘AC and DC breakdown tests were performed on large populations of oil-impregnated pressboard samples. The effect of voltage ramp rate on dielectric strength has been investigated. A statistical analysis of breakdown data was carried out using the Weibull distribution. The 90% confidence intervals of Weibull graphs were calculated. The study shows that dielectric strength and shape parameter change versus ramp rate. The variations are attributed to the size and number of defects. Discharges occur from the oil to the oil-pressboard interface and lead to breakdown. DC dielectric strength is larger than that corresponding to AC voltage. This is ascribed to the dissipated energy difference under the two types of field and the fatigue produced by the alternating voltage. This phenomenon is related to space charge. Under DC stress, dielectric strength is higher under negative polarity. It is assigned to the different quantities of space charge accumulated under the two polarities.