The article describes design peculiarities of the novel compact vacuum circuit breaker with rated voltage 40.5 kV. The design incorporates several novel technical solutions: polycarbonate support insulation, mono-sta...The article describes design peculiarities of the novel compact vacuum circuit breaker with rated voltage 40.5 kV. The design incorporates several novel technical solutions: polycarbonate support insulation, mono-stable magnetic actuator, labyrinth pulling insulator, core-type flexible contact and new compact vacuum interrupter (VI). Phases are encapsulated into silicone rubber providing required creepage distance and excellent tracking resistance. These novelties along with extensive modeling of the mechanical and electrical fields followed by design optimization resulted in weight reduction of more than 50% compared with alternatives available in the market. And this is in spite of built in sensors measuring: phase currents, zero-sequence current, phase voltages.展开更多
文摘The article describes design peculiarities of the novel compact vacuum circuit breaker with rated voltage 40.5 kV. The design incorporates several novel technical solutions: polycarbonate support insulation, mono-stable magnetic actuator, labyrinth pulling insulator, core-type flexible contact and new compact vacuum interrupter (VI). Phases are encapsulated into silicone rubber providing required creepage distance and excellent tracking resistance. These novelties along with extensive modeling of the mechanical and electrical fields followed by design optimization resulted in weight reduction of more than 50% compared with alternatives available in the market. And this is in spite of built in sensors measuring: phase currents, zero-sequence current, phase voltages.