Transient stability enhancement of DC-connected DFIG and its converter system using fault protective device 被引量:2
1
作者 Shaomin YAN Aimin ZHANG +2 位作者 Hang ZHANG Jianhua WANG Bin CAI 《Journal of Modern Power Systems and Clean Energy》 SCIE EI 2017年第6期887-896,共10页
Transient stability of doubly-fed induction generators(DFIGs)is a major concern in both AC and DC grids,and DFIGs must stay connected for a time during grid faults according to the power grid requirements.For this pur... Transient stability of doubly-fed induction generators(DFIGs)is a major concern in both AC and DC grids,and DFIGs must stay connected for a time during grid faults according to the power grid requirements.For this purpose,this work proposes an overcurrent and overvoltage protective device(OCV-PD)to ensure that DCbased DFIG system can stay connected and operate well during the faults.Compared with a series dynamic braking resistor(SDBR),two aspects are improved.First,a twolevel control strategy and DC inductor circuit are used to ensure that the OCV-PD can limit the current impulse to protect DFIG system during an overcurrent fault.Second,the OCV-PD can protect system from overvoltage fault which a SDBR cannot do.Simulation results verify itsvalidity and feasibility,finding that for overcurrent protection the OCV-PD outperforms a SDBR with an average decreased index of 3.29%,and for overvoltage protection it achieves an average index of 1.02%. 展开更多
关键词 Transient stability Doubly-fed induction generator(DFIG) overcurrent and overvoltage protective device(OCV-PD) DC grid Series dynamic braking resistor(SDBR)