期刊文献+
共找到1篇文章
< 1 >
每页显示 20 50 100
FRT Control Method Including Islanding Detection in PCS Model for Photovoltaic Generation
1
作者 Miyazaki Takahiro Cheng Wai Tatt Yoshimura Kazuaki Taoka Hisao Kawasaki Shoji Matsuki Junya 《Journal of Energy and Power Engineering》 2013年第7期1388-1393,共6页
The experimental results by the simulated PV (photovoltaic) system for understanding the cause of disconnection when instantaneous voltage sag occurs are reported in this study. Moreover, it is understood that the P... The experimental results by the simulated PV (photovoltaic) system for understanding the cause of disconnection when instantaneous voltage sag occurs are reported in this study. Moreover, it is understood that the PCS with the voltage phase jump detection method which is one of the main causes of the disconnection. We modeled it in the simulation. When fault occurs, even though the residual voltage is more than 20% and the voltage sag time is within 1.0 s, the PCS disconnected by the voltage phase jump detection was confirmed in the simulation results. Ifa large number of PV systems are interconnected in the power system, this study is verified through the simulation that the interaction caused by the disconnection which generated by the voltage phase jump detection. This study is proposed threshold limit value of islanding detection. The validity of proposed method was verified through the simulation in this study. 展开更多
关键词 FRT function PCS islanding detection voltage sag voltage phase jump detection.