In the transient process of power grid faults,the transferring distortion of current transformer(CT)can seriously affect relay protection performance.Under these conditions,it is difficult to analyze the ferromagnetic...In the transient process of power grid faults,the transferring distortion of current transformer(CT)can seriously affect relay protection performance.Under these conditions,it is difficult to analyze the ferromagnetic characteristic of the magnetizing branch in the transient equivalent circuit of CT.The Jiles-Atherton hysteresis model(J-A model),which is widely used in digital simulations,can accurately describe the hysteresis and saturation process of the core characteristics;however,to acquire the parameters of the J-A model of current transformers in practical use is still a challenging problem.In this paper,physical tests based on a practical CT and parameter identification are presented to solve the problem.The basic hysteresis loops of P,PR,and TPY class of practical current transformers are obtained through physical tests.Thus,the J-A model parameters are identified using a hybrid genetic/simulated annealing algorithm,based on which transient simulation models of different class CTs are constructed.The effectiveness of the proposed method is verified via dynamic physical simulation tests.A typical accident is analyzed based on these models.展开更多
基金supported by the Key project of smart grid technology and equipment of national key research and development plan of China under Grant 2016YFB0900600。
文摘In the transient process of power grid faults,the transferring distortion of current transformer(CT)can seriously affect relay protection performance.Under these conditions,it is difficult to analyze the ferromagnetic characteristic of the magnetizing branch in the transient equivalent circuit of CT.The Jiles-Atherton hysteresis model(J-A model),which is widely used in digital simulations,can accurately describe the hysteresis and saturation process of the core characteristics;however,to acquire the parameters of the J-A model of current transformers in practical use is still a challenging problem.In this paper,physical tests based on a practical CT and parameter identification are presented to solve the problem.The basic hysteresis loops of P,PR,and TPY class of practical current transformers are obtained through physical tests.Thus,the J-A model parameters are identified using a hybrid genetic/simulated annealing algorithm,based on which transient simulation models of different class CTs are constructed.The effectiveness of the proposed method is verified via dynamic physical simulation tests.A typical accident is analyzed based on these models.