Contaminations adhering on HVDC transmission line will change its corona characteristics to generate electromagnetic pollution. The corona-induced radio interference and audible noise become important factors influenc...Contaminations adhering on HVDC transmission line will change its corona characteristics to generate electromagnetic pollution. The corona-induced radio interference and audible noise become important factors influencing the configuration and costs of transmission project. For understanding the effects of contaminations on the corona pulse characteristics of an HVDC transmission line,a corona cage was adopted to experimentally investigate corona pulse inception voltage and corona pulse characteristics of the conductors with different contaminations on surfaces. The contaminations include simulated contaminations,carbon powder,cement and fine sand. The results show that when conductor is covered with contaminations,the positive polarity corona pulses have high amplitude and low frequency,while the negative polarity corona pulses have low amplitude and incremental high frequency components. The corona pulse inception voltage presents a negatively exponential decrease with the increase of contamination density,showing a saturation trend. Fine sand shows the greatest effect on the corona pulse inception voltage with positive polarity,while cement shows the least effect. A function of corona inception voltage and surface contamination density is given. This study may provide reference for design of transmission lines.展开更多
提出±800 k V与±500 k V混压同塔双回直流输电线路的极导线布置方案,对不同极导线布置方式下的电磁环境(导地线表面场强、地面合成场强、离子流密度)、线路最小对地高度与走廊宽度、线路防雷性能等进行计算分析,给出不同海拔...提出±800 k V与±500 k V混压同塔双回直流输电线路的极导线布置方案,对不同极导线布置方式下的电磁环境(导地线表面场强、地面合成场强、离子流密度)、线路最小对地高度与走廊宽度、线路防雷性能等进行计算分析,给出不同海拔高度下极导线布置方式的推荐方案。研究结果可为特超高压同塔双回直流输电线路的设计提供参考。展开更多
目的深入研究超特高压输电电磁辐射环境。方法采用窄带测试的方法分别对500 k V变电站和500 k V交流输电线路的超高频电磁环境进行测试与分析。结果变电站周围产生的超高频辐射场上限频率可达1 GHz,线路周围产生的超高频辐射场上限频率...目的深入研究超特高压输电电磁辐射环境。方法采用窄带测试的方法分别对500 k V变电站和500 k V交流输电线路的超高频电磁环境进行测试与分析。结果变电站周围产生的超高频辐射场上限频率可达1 GHz,线路周围产生的超高频辐射场上限频率可达700 MHz,分裂导线将会影响线路的高频辐射场分布。在传播过程中,辐射场电场以垂直极化分量为主,辐射信号峰值随距离的衰减曲线呈非线性关系,远距离处辐射信号以低频分量为主。结论测试得到的规律对研究高压输电的高频电磁环境具有参考意义。展开更多
基金Project Supported by Science and Technology Foundation of State Grid Corporation of China(SGSC[2005]81)
文摘Contaminations adhering on HVDC transmission line will change its corona characteristics to generate electromagnetic pollution. The corona-induced radio interference and audible noise become important factors influencing the configuration and costs of transmission project. For understanding the effects of contaminations on the corona pulse characteristics of an HVDC transmission line,a corona cage was adopted to experimentally investigate corona pulse inception voltage and corona pulse characteristics of the conductors with different contaminations on surfaces. The contaminations include simulated contaminations,carbon powder,cement and fine sand. The results show that when conductor is covered with contaminations,the positive polarity corona pulses have high amplitude and low frequency,while the negative polarity corona pulses have low amplitude and incremental high frequency components. The corona pulse inception voltage presents a negatively exponential decrease with the increase of contamination density,showing a saturation trend. Fine sand shows the greatest effect on the corona pulse inception voltage with positive polarity,while cement shows the least effect. A function of corona inception voltage and surface contamination density is given. This study may provide reference for design of transmission lines.
文摘提出±800 k V与±500 k V混压同塔双回直流输电线路的极导线布置方案,对不同极导线布置方式下的电磁环境(导地线表面场强、地面合成场强、离子流密度)、线路最小对地高度与走廊宽度、线路防雷性能等进行计算分析,给出不同海拔高度下极导线布置方式的推荐方案。研究结果可为特超高压同塔双回直流输电线路的设计提供参考。
文摘目的深入研究超特高压输电电磁辐射环境。方法采用窄带测试的方法分别对500 k V变电站和500 k V交流输电线路的超高频电磁环境进行测试与分析。结果变电站周围产生的超高频辐射场上限频率可达1 GHz,线路周围产生的超高频辐射场上限频率可达700 MHz,分裂导线将会影响线路的高频辐射场分布。在传播过程中,辐射场电场以垂直极化分量为主,辐射信号峰值随距离的衰减曲线呈非线性关系,远距离处辐射信号以低频分量为主。结论测试得到的规律对研究高压输电的高频电磁环境具有参考意义。