The performances of a refrigeration unit relying on compressors working in parallel have been investigated considering the influence of the compressor volumetric efficiency and isentropic efficiency on the compression...The performances of a refrigeration unit relying on compressors working in parallel have been investigated considering the influence of the compressor volumetric efficiency and isentropic efficiency on the compression ratio.Moreover,the following influential factors have been taken into account:evaporation temperature,condensation temperature and compressor suction-exhaust pressure ratio for different opening conditions of the compressor.The following quantities have been selected as the unit performance measurement indicators:refrigeration capacity,energy efficiency ratio(COP),compressor power consumption,and refrigerant flow rate.The experimental results indicate that the system refrigeration capacity and COP decrease with a decrease in evaporation temperature,increase of condensation temperature,and increase in pressure ratio.The refrigerant flow rate increases with the increase in evaporation temperature,decrease in condensing temperature and increase in pressure ratio.The compressor power consumption increases with the increase in condensing temperature and increase in pressure ratio,but is not significantly affected by the evaporation temperature.展开更多
基于矿井热害对井下职工健康危害的考虑,研制出了一种冷风型矿用制冷机组,该机组首次采用半封闭式螺杆压缩机,克服了开启式活塞机和螺杆机的性能缺陷。介绍了制冷机组基本原理、测试过程以及应用情况,结果表明:该制冷机组性能良好、运...基于矿井热害对井下职工健康危害的考虑,研制出了一种冷风型矿用制冷机组,该机组首次采用半封闭式螺杆压缩机,克服了开启式活塞机和螺杆机的性能缺陷。介绍了制冷机组基本原理、测试过程以及应用情况,结果表明:该制冷机组性能良好、运行稳定可靠;设计工况下机组的制冷量达到440 k W、COP达到3.6、蒸发器的空气流通阻力仅为510 Pa;在紧急情况下机组的安全保护性能可靠。展开更多
基金supported by the National Natural Science Foundation of China(No.41877251)the Key project of Natural Science Foundation of Tianjin City(No.6JCZDJC39000).
文摘The performances of a refrigeration unit relying on compressors working in parallel have been investigated considering the influence of the compressor volumetric efficiency and isentropic efficiency on the compression ratio.Moreover,the following influential factors have been taken into account:evaporation temperature,condensation temperature and compressor suction-exhaust pressure ratio for different opening conditions of the compressor.The following quantities have been selected as the unit performance measurement indicators:refrigeration capacity,energy efficiency ratio(COP),compressor power consumption,and refrigerant flow rate.The experimental results indicate that the system refrigeration capacity and COP decrease with a decrease in evaporation temperature,increase of condensation temperature,and increase in pressure ratio.The refrigerant flow rate increases with the increase in evaporation temperature,decrease in condensing temperature and increase in pressure ratio.The compressor power consumption increases with the increase in condensing temperature and increase in pressure ratio,but is not significantly affected by the evaporation temperature.
文摘基于矿井热害对井下职工健康危害的考虑,研制出了一种冷风型矿用制冷机组,该机组首次采用半封闭式螺杆压缩机,克服了开启式活塞机和螺杆机的性能缺陷。介绍了制冷机组基本原理、测试过程以及应用情况,结果表明:该制冷机组性能良好、运行稳定可靠;设计工况下机组的制冷量达到440 k W、COP达到3.6、蒸发器的空气流通阻力仅为510 Pa;在紧急情况下机组的安全保护性能可靠。