The hybrid cascaded high-voltage direct current(HVDC)transmission system has various operation modes,and some operation modes have sharply increasing requirements for protection rapidity,while the traditional pilot di...The hybrid cascaded high-voltage direct current(HVDC)transmission system has various operation modes,and some operation modes have sharply increasing requirements for protection rapidity,while the traditional pilot differential protection(PDP)has poor rapidity,and even refuses to operate when faults occur on the DC line.Therefore,a novel pilot protection scheme based on traveling wave characteristics is proposed.First,the adaptability of the traditional PDP applied in engineering is analyzed for different operation modes.Then,the expressions of the forward traveling wave(FTW)and backward traveling wave(BTW)on the rectifier side and the inverter side are derived for different fault locations.From the theoretical derivation,the difference between the BTW and FTW on the rectifier side is less than zero,and the same is true on the inverter side.However,in the event of an external fault of DC line,the difference between the BTW and FTW at nearfault terminal protection installation point is greater than zero.Therefore,by summing over the product of the difference between BTW and FTW of the rectifier side and that of the inverter side,the fault identification criterion is constructed.The simulation results show that the proposed pilot protection scheme can quickly and reliably identify the short-circuit faults of DC line in different operation modes.展开更多
为提高风电场交直流混合输电并网的系统性能,提出一种更加灵活的电压源换流器高压直流(voltage source converter based high voltage direct current,VSC-HVDC)控制策略。对于风电场侧电压源换流器,设计了一种新的交流电压–功角控制...为提高风电场交直流混合输电并网的系统性能,提出一种更加灵活的电压源换流器高压直流(voltage source converter based high voltage direct current,VSC-HVDC)控制策略。对于风电场侧电压源换流器,设计了一种新的交流电压–功角控制方法。对于交直流混合输电模式,该方法通过调节风电场交流母线电压与电压源换流器输出电压间的功角来实现定有功功率控制。对于纯柔性直流输电模式,风电场交流母线电压自动被调节为具有恒幅恒频的交流电压,实现了对波动风电的同步输送。该方法中输电模式的变化无需切换控制;另外,通过附加电流高通滤波器增强了对系统谐振的阻尼作用。对电网侧电压源换流器,采用一种新的直接电流矢量控制,使直流电压稳定在参考值上。运用PSCAD/EMTDC仿真软件对分别接入笼型感应发电机(squirrel cage induction generator,SCIG)风电场和双馈感应发电机(doubly fed induction generator,DFIG)风电场的交直流混合输电系统建模仿真。一系列运行条件下的仿真结果验证了控制方法的有效性与可行性。展开更多
为提高系统运行稳定性,高补偿度串补装置广泛投入使用,但线路故障后潜供电流存在高幅值的低频分量,潜供电弧难以自熄。针对此问题,基于交直流混联输电线路,研究了不同布置方式下串补度对潜供电流与恢复电压幅值影响,提出了一种固定串补(...为提高系统运行稳定性,高补偿度串补装置广泛投入使用,但线路故障后潜供电流存在高幅值的低频分量,潜供电弧难以自熄。针对此问题,基于交直流混联输电线路,研究了不同布置方式下串补度对潜供电流与恢复电压幅值影响,提出了一种固定串补(fixed series compensation,FSC)和可控串补(thyristor controlled series compensation,TCSC)混合复用抑制潜供电弧的方法。此外,为满足线路对高补偿度的需求,设计FSC和TCSC混合复用串补度最佳配置方案。结果表明,交直流混联线路采用串补度40%的双平台分散布置方式,潜供电流与恢复电压幅值达到最小,燃弧时间最短。高补偿度串补线路TCSC采用串补度10%、20%的配置方案更利于熄弧,提高重合闸成功率。展开更多
高压直流输电系统嵌入大型交流系统,将进一步增加换相失败、直流闭锁等故障对系统安全稳定的影响,交流系统与直流系统的交互作用,将使系统动态更加复杂。针对电网不同运行方式下大扰动后系统复杂动态响应特性分析难题,文中提出一种基于...高压直流输电系统嵌入大型交流系统,将进一步增加换相失败、直流闭锁等故障对系统安全稳定的影响,交流系统与直流系统的交互作用,将使系统动态更加复杂。针对电网不同运行方式下大扰动后系统复杂动态响应特性分析难题,文中提出一种基于机电-电磁混合仿真与机器学习的智能分析方法。该方法基于主成分分析(principal components analysis,PCA)降维、基于密度的噪声应用空间聚类(density-based spatial clustering of applications with noise,DBSCAN)、K-means等算法建立二阶段聚类模型,可针对直流落点近区严重故障后大量混合仿真动态曲线在高维空间中自动聚类,并给出相应标识与严重程度;提取交直流系统在不同故障下的典型动态模式,自动标注并识别各模式下主导安全稳定问题。文中所提方法的有效性在2025年华东电网运行方式中得以验证,仿真结果表明,所提方法可有效提取不同故障下系统动态模式,将有效支撑后续复杂故障下的交直流系统动态机理分析。展开更多
基金Project supported by Funds for Innovative Research Groups of China (51021005), National Basic Research Program of China (973 Program) (2009CB724504), National Natural Science Foundation of China(50707036).
基金supported in part by the National Natural Science Foundation of China(No.51977183)。
文摘The hybrid cascaded high-voltage direct current(HVDC)transmission system has various operation modes,and some operation modes have sharply increasing requirements for protection rapidity,while the traditional pilot differential protection(PDP)has poor rapidity,and even refuses to operate when faults occur on the DC line.Therefore,a novel pilot protection scheme based on traveling wave characteristics is proposed.First,the adaptability of the traditional PDP applied in engineering is analyzed for different operation modes.Then,the expressions of the forward traveling wave(FTW)and backward traveling wave(BTW)on the rectifier side and the inverter side are derived for different fault locations.From the theoretical derivation,the difference between the BTW and FTW on the rectifier side is less than zero,and the same is true on the inverter side.However,in the event of an external fault of DC line,the difference between the BTW and FTW at nearfault terminal protection installation point is greater than zero.Therefore,by summing over the product of the difference between BTW and FTW of the rectifier side and that of the inverter side,the fault identification criterion is constructed.The simulation results show that the proposed pilot protection scheme can quickly and reliably identify the short-circuit faults of DC line in different operation modes.
文摘为提高风电场交直流混合输电并网的系统性能,提出一种更加灵活的电压源换流器高压直流(voltage source converter based high voltage direct current,VSC-HVDC)控制策略。对于风电场侧电压源换流器,设计了一种新的交流电压–功角控制方法。对于交直流混合输电模式,该方法通过调节风电场交流母线电压与电压源换流器输出电压间的功角来实现定有功功率控制。对于纯柔性直流输电模式,风电场交流母线电压自动被调节为具有恒幅恒频的交流电压,实现了对波动风电的同步输送。该方法中输电模式的变化无需切换控制;另外,通过附加电流高通滤波器增强了对系统谐振的阻尼作用。对电网侧电压源换流器,采用一种新的直接电流矢量控制,使直流电压稳定在参考值上。运用PSCAD/EMTDC仿真软件对分别接入笼型感应发电机(squirrel cage induction generator,SCIG)风电场和双馈感应发电机(doubly fed induction generator,DFIG)风电场的交直流混合输电系统建模仿真。一系列运行条件下的仿真结果验证了控制方法的有效性与可行性。
文摘为提高系统运行稳定性,高补偿度串补装置广泛投入使用,但线路故障后潜供电流存在高幅值的低频分量,潜供电弧难以自熄。针对此问题,基于交直流混联输电线路,研究了不同布置方式下串补度对潜供电流与恢复电压幅值影响,提出了一种固定串补(fixed series compensation,FSC)和可控串补(thyristor controlled series compensation,TCSC)混合复用抑制潜供电弧的方法。此外,为满足线路对高补偿度的需求,设计FSC和TCSC混合复用串补度最佳配置方案。结果表明,交直流混联线路采用串补度40%的双平台分散布置方式,潜供电流与恢复电压幅值达到最小,燃弧时间最短。高补偿度串补线路TCSC采用串补度10%、20%的配置方案更利于熄弧,提高重合闸成功率。
文摘高压直流输电系统嵌入大型交流系统,将进一步增加换相失败、直流闭锁等故障对系统安全稳定的影响,交流系统与直流系统的交互作用,将使系统动态更加复杂。针对电网不同运行方式下大扰动后系统复杂动态响应特性分析难题,文中提出一种基于机电-电磁混合仿真与机器学习的智能分析方法。该方法基于主成分分析(principal components analysis,PCA)降维、基于密度的噪声应用空间聚类(density-based spatial clustering of applications with noise,DBSCAN)、K-means等算法建立二阶段聚类模型,可针对直流落点近区严重故障后大量混合仿真动态曲线在高维空间中自动聚类,并给出相应标识与严重程度;提取交直流系统在不同故障下的典型动态模式,自动标注并识别各模式下主导安全稳定问题。文中所提方法的有效性在2025年华东电网运行方式中得以验证,仿真结果表明,所提方法可有效提取不同故障下系统动态模式,将有效支撑后续复杂故障下的交直流系统动态机理分析。