A deconpling control strategy of inverter parallel system is proposed based on the equivalent output impedance of single phase voltage source SPWM (sinusoidal pulse width modulation) inverter. The active power and r...A deconpling control strategy of inverter parallel system is proposed based on the equivalent output impedance of single phase voltage source SPWM (sinusoidal pulse width modulation) inverter. The active power and reactive power are calculated in terms of output voltage and current of the inverter, and sent to the other inverters in the parallel system via controller area network (CAN) bus. By calculating and decoupling the circumfluence of the active power and reactive power, the inverters can share load current via the regulation of the reference-signal phase and amplitude. Experimental results of an 110V/2kVA inverter parallel system show the feasibility of the decoupling control strategy.展开更多
基金supported by the National Natural Science Foundation of China under Grant No 50677056
文摘A deconpling control strategy of inverter parallel system is proposed based on the equivalent output impedance of single phase voltage source SPWM (sinusoidal pulse width modulation) inverter. The active power and reactive power are calculated in terms of output voltage and current of the inverter, and sent to the other inverters in the parallel system via controller area network (CAN) bus. By calculating and decoupling the circumfluence of the active power and reactive power, the inverters can share load current via the regulation of the reference-signal phase and amplitude. Experimental results of an 110V/2kVA inverter parallel system show the feasibility of the decoupling control strategy.