In order to study the dynamic response of high-voltage transmission lines under mechanical failure, a finite element model of a domestic 500-kV high-voltage transmission line system is established. The initial equilib...In order to study the dynamic response of high-voltage transmission lines under mechanical failure, a finite element model of a domestic 500-kV high-voltage transmission line system is established. The initial equilibrium condition of the coupling system model is verified by nonlinear static analysis. The transient dynamic analysis method is proposed to analyze the variation law of dynamic response under cable or insulator rupture, and the dynamic response of structural elements next to the broken span is calculated. The results show that upper crossarm cable rupture has no effect on cable tension at adjacent suspension points, but it has a significant influence on tension in the insulator and the tower component of the upper crossarm next to the broken span. The peak tension in the conductor of the upper crossarm at the suspension point exceeds the design value under insulator rupture. Insulator rupture has no effect on the tower component of the upper crossarm, but it has a significant influence on insulator tension of the upper crossarm. Insulator rupture should be taken into account in the design of overhead transmission lines. The research results can provide a theoretical basis for the design of transmission lines.展开更多
In order to study the sliding characteristics when the cable structures are connected with other rods, a string of sliding cable dements (SCE) consisting of one active threenode SCE passing through the sliding point...In order to study the sliding characteristics when the cable structures are connected with other rods, a string of sliding cable dements (SCE) consisting of one active threenode SCE passing through the sliding point and multiple inactive two-node SCEs is put forward. Based on the updated Lagrangian formulation, the geometric nonlinear stiffness matrix of the three-node straight sliding cable dement is deduced. The examples about two-span and three-span continuous cable structures are studied to verify the effectiveness of the derived SCE. Comparing the cable tension of SCE with the existing research results, the calculating results show that the error is less than 1%. The sliding characteristics should be considered in practical engineering because of the obvious difference between the cable tension of the SCE and that of the cable element without considering sliding characteristics.展开更多
In order to study the sliding characteristics when the cable is connected with the other rods in the transmission line structures,a linear sliding cable element based on updated Lagrangian formulation and a sliding ca...In order to study the sliding characteristics when the cable is connected with the other rods in the transmission line structures,a linear sliding cable element based on updated Lagrangian formulation and a sliding catenary element considering the out-of-plane stiffness coefficient are put forward.A two-span and a three-span cable structures are taken as examples to verify the sliding cable elements.By comparing the tensions of the two proposed cable elements with the existing research results,the error is less than 1%,which proves the correctness of the proposed elements.The sliding characteristics should be considered in the practical engineering because of the significant difference between the tensions of sliding cable elements and those of cable element without considering sliding.The out-of-plane stiffness coefficient and friction characteristics do not obviously affect the cable tensions.展开更多
Insulated underground cables have the potential to reduce power outages, maintenance costs, and transmission losses compared to overhead lines.</span><span style="font-family:""> </span&g...Insulated underground cables have the potential to reduce power outages, maintenance costs, and transmission losses compared to overhead lines.</span><span style="font-family:""> </span><span style="font-family:""><span style="font-family:Verdana;">On the other hand, they are exposed to several risks and physical damages, since they are buried in the ground. Though the cables are armoured in order to provide mec</span><span style="font-family:Verdana;">hanical protection and achieve tensile strength, and also to provide effective conductance of earth fault currents.</span></span><span style="font-family:""> </span><span style="font-family:Verdana;">The main purpose of this paper is to introduce insulated underground cables, armouring process, and to analyze the induced currents in metallic parts such as sheath and armour </span><span style="font-family:Verdana;">that causeohmic losses which are categorized mainly in two groups as circulating current and eddy current. This paper presents a review on analytical techniques used to analyze the effect of magnetic fields, andcalculate the losses in </span><span style="font-family:Verdana;">the armour of the cables,</span><span style="font-family:""> </span><span style="font-family:Verdana;">besides providing the strategies and solutions used for armour loss reduction.展开更多
A conceptual superconducting DC cable model is designed and its magnetic fields distribution is analyzed with Ansoft/Maxwell soft. A DC Power transmission system is also studied by using the Matlab/Simulink. With the ...A conceptual superconducting DC cable model is designed and its magnetic fields distribution is analyzed with Ansoft/Maxwell soft. A DC Power transmission system is also studied by using the Matlab/Simulink. With the DC Line and AC Ground Fault, the system losses analysis is introduced.The analysis results mainly include the magnetic fields distribution of the HTS cable model with Ansoft/Maxwell, the system loss, the DC Line and AC Ground Fault with Matlab/Simulation.展开更多
This article outlines the development of downhole monitoring and data transmission technology for separated zone water injection in China.According to the development stages,the principles,operation processes,adaptabi...This article outlines the development of downhole monitoring and data transmission technology for separated zone water injection in China.According to the development stages,the principles,operation processes,adaptability and application status of traditional downhole data acquisition method,cable communications and testing technology,cable-controlled downhole parameter real-time monitoring communication method and downhole wireless communication technology are introduced in detail.Problems and challenges of existing technologies in downhole monitoring and data transmission technology are pointed out.According to the production requirement,the future development direction of the downhole monitoring and data transmission technology for separated zone water injection is proposed.For the large number of wells adopting cable measuring and adjustment technology,the key is to realize the digitalization of downhole plug.For the key monitoring wells,cable-controlled communication technology needs to be improved,and downhole monitoring and data transmission technology based on composite coiled tubing needs to be developed to make the operation more convenient and reliable.For large-scale application in oil fields,downhole wireless communication technology should be developed to realize automation of measurement and adjustment.In line with ground mobile communication network,a digital communication network covering the control center,water distribution station and oil reservoir should be built quickly to provide technical support for the digitization of reservoir development.展开更多
Downburst event is identified as a major cause to failure of transmission lines in non-coastal regions.In this paper,a novel nonlinear analytical frame for quasi-static buffeting responses of hinged and multi-span ins...Downburst event is identified as a major cause to failure of transmission lines in non-coastal regions.In this paper,a novel nonlinear analytical frame for quasi-static buffeting responses of hinged and multi-span insulator-line systems are derived based on the theory of cable structure.The closed-form solutions are presented and applied to predict nonlinear response including displacements and other reactions of the system subjected to a moving downburst wind in a case study.Accuracy and efficiency of the derived analytical frame are validated via comparisons with results from finite element method.展开更多
The transmission characteristics of video transmission mediums,coaxial ca ble and optical fiber,are discussed in the paper. The formulas for frequency bandwidth are given to evaluate the video transmission distance. F...The transmission characteristics of video transmission mediums,coaxial ca ble and optical fiber,are discussed in the paper. The formulas for frequency bandwidth are given to evaluate the video transmission distance. For typical video transmission systems with BB/IM and PFM/IM tising optical fiber as the channel, expressions and calculating results for both S/N and sensitivity are given. Finally, the principle for se lecting different type of transmission systems according to transmission distances of the industrial TV is presented.展开更多
During geomagnetic disturbances, electric fields induced in the Earth and in power systems, pipelines and submarine cables can interfere with the operation of these systems. Calculations for submarine cables are compl...During geomagnetic disturbances, electric fields induced in the Earth and in power systems, pipelines and submarine cables can interfere with the operation of these systems. Calculations for submarine cables are complicated by the need to consider not just the induction directly into the cable but also the earth potentials produced at the coast at each end of the cable. To determine the coast potentials, we present a new model of the ocean and earth conductivity structure that spans the whole length of a cable from one coast to another. Calculations are based on the generalised thin sheet approach introduced by Ranganayaki and Madden but converted to a transmission line model that can be solved using standard circuit theory techniques. It is shown how the transmission line model can be used to calculate the earth potential profile from one side of an ocean or sea to the other. Example calculations are presented for a shallow sea, a shallow ocean, and a deep ocean that are simplified approximations to the North Sea, Tasman Sea and Pacific Ocean and show that the peak potentials occur at the coast. An examination is also made of how the width of a shallow sea and the width of the continental shelf affect these coast potentials. The modelling technique and example results provide a guide for more detailed modelling of geomagnetic induction along the routes of specific submarine cables.展开更多
A 33.5 m, 35 kV/121 MVA, three-phase, warm dielectric HTS power cable system was successfully installed and activated in China Southern Power Grid at the Puji substation in Kunming on April 19th of 2004, supplying ele...A 33.5 m, 35 kV/121 MVA, three-phase, warm dielectric HTS power cable system was successfully installed and activated in China Southern Power Grid at the Puji substation in Kunming on April 19th of 2004, supplying electricity to four industrial customers (including two metallurgical refineries) and a residential population of about 100000. In this paper, we give an update on the operation and maintenance status of the system and comments on reliability issues. We conclude that the superconducting cable system is currently quite robust and feasible for particular utility applications, and it will be improved by advancement in cryogenic equipment and system technology.展开更多
Some specified chips in traditional Manchester-Ⅱencoding/decoding designs are used to guarantee strictly the stability of the input wave,otherwise the capacity of anti-interference and resilience are degraded serious...Some specified chips in traditional Manchester-Ⅱencoding/decoding designs are used to guarantee strictly the stability of the input wave,otherwise the capacity of anti-interference and resilience are degraded seriously.In this paper,a new Manchester-Ⅱencoding/ decoding system is used for nuclear logging by a 7 000 m armoring cable.A thorough hardware wave tracking decoding algorithm is proposed and realized in a FPGA hardware chip.An on-site measurements show that this transmission system can decode correctly in real time,with a bit error rate of better than 10^(-10).展开更多
It is necessary to study dynamic operation efficiency of transmission networks in order to realize high intensification of communication networks. The operation efficiency discussed here should exist not only in logic...It is necessary to study dynamic operation efficiency of transmission networks in order to realize high intensification of communication networks. The operation efficiency discussed here should exist not only in logic-circuit layer, but also in both path layer and medium layer. A theoretical method of the measurement of layers and comprehensive evaluations is presented based on the concept of transmission efficiency.展开更多
基金The National Natural Science Foundation of China (No.50578038)the Science and Technology Project of the State Grid Corporation of China(No.SGKJ[2007]116)
文摘In order to study the dynamic response of high-voltage transmission lines under mechanical failure, a finite element model of a domestic 500-kV high-voltage transmission line system is established. The initial equilibrium condition of the coupling system model is verified by nonlinear static analysis. The transient dynamic analysis method is proposed to analyze the variation law of dynamic response under cable or insulator rupture, and the dynamic response of structural elements next to the broken span is calculated. The results show that upper crossarm cable rupture has no effect on cable tension at adjacent suspension points, but it has a significant influence on tension in the insulator and the tower component of the upper crossarm next to the broken span. The peak tension in the conductor of the upper crossarm at the suspension point exceeds the design value under insulator rupture. Insulator rupture has no effect on the tower component of the upper crossarm, but it has a significant influence on insulator tension of the upper crossarm. Insulator rupture should be taken into account in the design of overhead transmission lines. The research results can provide a theoretical basis for the design of transmission lines.
基金The National Natural Science Foundation of China (No.51308193)China Postdoctoral Science Foundation (No.20110491342)+1 种基金Jiangsu Planned Projects for Postdoctoral Research Funds(No.1101018C)the Science and Technology Project of State Grid Corporation of China(No.SGKJ[2007]116)
文摘In order to study the sliding characteristics when the cable structures are connected with other rods, a string of sliding cable dements (SCE) consisting of one active threenode SCE passing through the sliding point and multiple inactive two-node SCEs is put forward. Based on the updated Lagrangian formulation, the geometric nonlinear stiffness matrix of the three-node straight sliding cable dement is deduced. The examples about two-span and three-span continuous cable structures are studied to verify the effectiveness of the derived SCE. Comparing the cable tension of SCE with the existing research results, the calculating results show that the error is less than 1%. The sliding characteristics should be considered in practical engineering because of the obvious difference between the cable tension of the SCE and that of the cable element without considering sliding characteristics.
基金Project(51308193)supported by the National Natural Science Foundation of ChinaProject(SGKJ[2007]116)supported by the Science and Technology Program of State Grid Corporation of China
文摘In order to study the sliding characteristics when the cable is connected with the other rods in the transmission line structures,a linear sliding cable element based on updated Lagrangian formulation and a sliding catenary element considering the out-of-plane stiffness coefficient are put forward.A two-span and a three-span cable structures are taken as examples to verify the sliding cable elements.By comparing the tensions of the two proposed cable elements with the existing research results,the error is less than 1%,which proves the correctness of the proposed elements.The sliding characteristics should be considered in the practical engineering because of the significant difference between the tensions of sliding cable elements and those of cable element without considering sliding.The out-of-plane stiffness coefficient and friction characteristics do not obviously affect the cable tensions.
文摘Insulated underground cables have the potential to reduce power outages, maintenance costs, and transmission losses compared to overhead lines.</span><span style="font-family:""> </span><span style="font-family:""><span style="font-family:Verdana;">On the other hand, they are exposed to several risks and physical damages, since they are buried in the ground. Though the cables are armoured in order to provide mec</span><span style="font-family:Verdana;">hanical protection and achieve tensile strength, and also to provide effective conductance of earth fault currents.</span></span><span style="font-family:""> </span><span style="font-family:Verdana;">The main purpose of this paper is to introduce insulated underground cables, armouring process, and to analyze the induced currents in metallic parts such as sheath and armour </span><span style="font-family:Verdana;">that causeohmic losses which are categorized mainly in two groups as circulating current and eddy current. This paper presents a review on analytical techniques used to analyze the effect of magnetic fields, andcalculate the losses in </span><span style="font-family:Verdana;">the armour of the cables,</span><span style="font-family:""> </span><span style="font-family:Verdana;">besides providing the strategies and solutions used for armour loss reduction.
文摘A conceptual superconducting DC cable model is designed and its magnetic fields distribution is analyzed with Ansoft/Maxwell soft. A DC Power transmission system is also studied by using the Matlab/Simulink. With the DC Line and AC Ground Fault, the system losses analysis is introduced.The analysis results mainly include the magnetic fields distribution of the HTS cable model with Ansoft/Maxwell, the system loss, the DC Line and AC Ground Fault with Matlab/Simulation.
基金Supported by the National Natural Science Foundation Science Center Project/Basic Science Center Project(72088101)PetroChina Scientific Research and Technology Development Project(2020B-4119,2021ZG12).
文摘This article outlines the development of downhole monitoring and data transmission technology for separated zone water injection in China.According to the development stages,the principles,operation processes,adaptability and application status of traditional downhole data acquisition method,cable communications and testing technology,cable-controlled downhole parameter real-time monitoring communication method and downhole wireless communication technology are introduced in detail.Problems and challenges of existing technologies in downhole monitoring and data transmission technology are pointed out.According to the production requirement,the future development direction of the downhole monitoring and data transmission technology for separated zone water injection is proposed.For the large number of wells adopting cable measuring and adjustment technology,the key is to realize the digitalization of downhole plug.For the key monitoring wells,cable-controlled communication technology needs to be improved,and downhole monitoring and data transmission technology based on composite coiled tubing needs to be developed to make the operation more convenient and reliable.For large-scale application in oil fields,downhole wireless communication technology should be developed to realize automation of measurement and adjustment.In line with ground mobile communication network,a digital communication network covering the control center,water distribution station and oil reservoir should be built quickly to provide technical support for the digitization of reservoir development.
基金supported in part by Science and Technology Foundation of State Grid Shandong Electric Power Company(Grant No.52062518000U)National Natural Science Foundation of China(Grant Nos.51720105005 and 51478373)+1 种基金by Science and Technology Foundation of State Grid Shandong Electric Power Company(Grant No.52062518000U)National Natural Science Foundation of China(Grant Nos.51720105005 and 51478373)are greatly acknowledged.
文摘Downburst event is identified as a major cause to failure of transmission lines in non-coastal regions.In this paper,a novel nonlinear analytical frame for quasi-static buffeting responses of hinged and multi-span insulator-line systems are derived based on the theory of cable structure.The closed-form solutions are presented and applied to predict nonlinear response including displacements and other reactions of the system subjected to a moving downburst wind in a case study.Accuracy and efficiency of the derived analytical frame are validated via comparisons with results from finite element method.
文摘The transmission characteristics of video transmission mediums,coaxial ca ble and optical fiber,are discussed in the paper. The formulas for frequency bandwidth are given to evaluate the video transmission distance. For typical video transmission systems with BB/IM and PFM/IM tising optical fiber as the channel, expressions and calculating results for both S/N and sensitivity are given. Finally, the principle for se lecting different type of transmission systems according to transmission distances of the industrial TV is presented.
文摘During geomagnetic disturbances, electric fields induced in the Earth and in power systems, pipelines and submarine cables can interfere with the operation of these systems. Calculations for submarine cables are complicated by the need to consider not just the induction directly into the cable but also the earth potentials produced at the coast at each end of the cable. To determine the coast potentials, we present a new model of the ocean and earth conductivity structure that spans the whole length of a cable from one coast to another. Calculations are based on the generalised thin sheet approach introduced by Ranganayaki and Madden but converted to a transmission line model that can be solved using standard circuit theory techniques. It is shown how the transmission line model can be used to calculate the earth potential profile from one side of an ocean or sea to the other. Example calculations are presented for a shallow sea, a shallow ocean, and a deep ocean that are simplified approximations to the North Sea, Tasman Sea and Pacific Ocean and show that the peak potentials occur at the coast. An examination is also made of how the width of a shallow sea and the width of the continental shelf affect these coast potentials. The modelling technique and example results provide a guide for more detailed modelling of geomagnetic induction along the routes of specific submarine cables.
基金This work was supported in part by the Chinese Ministry of Science and Technology under Grant No. 2002AA306154, 2004AA306110,2005AA306120 and 2006AA03Z207the Beijing Municipal Scienceand Technology Commission under Grant No. H020420010210the Yunnan Provincial Science and Technology Department under Grant No.2003BABCA05A041 and 2003530101000415.
文摘A 33.5 m, 35 kV/121 MVA, three-phase, warm dielectric HTS power cable system was successfully installed and activated in China Southern Power Grid at the Puji substation in Kunming on April 19th of 2004, supplying electricity to four industrial customers (including two metallurgical refineries) and a residential population of about 100000. In this paper, we give an update on the operation and maintenance status of the system and comments on reliability issues. We conclude that the superconducting cable system is currently quite robust and feasible for particular utility applications, and it will be improved by advancement in cryogenic equipment and system technology.
基金Supported by the China National High Technology Research and Development Program(863 Plans) funding for this project(No,2006AA09A102-02)
文摘Some specified chips in traditional Manchester-Ⅱencoding/decoding designs are used to guarantee strictly the stability of the input wave,otherwise the capacity of anti-interference and resilience are degraded seriously.In this paper,a new Manchester-Ⅱencoding/ decoding system is used for nuclear logging by a 7 000 m armoring cable.A thorough hardware wave tracking decoding algorithm is proposed and realized in a FPGA hardware chip.An on-site measurements show that this transmission system can decode correctly in real time,with a bit error rate of better than 10^(-10).
文摘It is necessary to study dynamic operation efficiency of transmission networks in order to realize high intensification of communication networks. The operation efficiency discussed here should exist not only in logic-circuit layer, but also in both path layer and medium layer. A theoretical method of the measurement of layers and comprehensive evaluations is presented based on the concept of transmission efficiency.