Statistics shows that transients produced by lightning or momentary links with external objects, have produced more than 80% of faults in overhead lines. Reclosing of circuit breaker (CB) after a pre-defined dead time...Statistics shows that transients produced by lightning or momentary links with external objects, have produced more than 80% of faults in overhead lines. Reclosing of circuit breaker (CB) after a pre-defined dead time is very common however reclosing onto permanent faults may damage the power system stability and aggravate severe damage to the system. Thus, adaptive single-phase auto-reclosing (ASPAR) based on investigating existing electrical signals has fascinated engineers and researchers. An ASPAR blocks CB reclosing onto permanent faults and allows reclosing permission once secondary arc is quenched. To address the subject, there have been many ASPARs techniques proposed based on the features trapped in a faulty phase. This paper presents a critical survey of adaptive auto-reclosing schemes that have hitherto been applied to EHV transmission lines.展开更多
文摘Statistics shows that transients produced by lightning or momentary links with external objects, have produced more than 80% of faults in overhead lines. Reclosing of circuit breaker (CB) after a pre-defined dead time is very common however reclosing onto permanent faults may damage the power system stability and aggravate severe damage to the system. Thus, adaptive single-phase auto-reclosing (ASPAR) based on investigating existing electrical signals has fascinated engineers and researchers. An ASPAR blocks CB reclosing onto permanent faults and allows reclosing permission once secondary arc is quenched. To address the subject, there have been many ASPARs techniques proposed based on the features trapped in a faulty phase. This paper presents a critical survey of adaptive auto-reclosing schemes that have hitherto been applied to EHV transmission lines.