期刊文献+
共找到1篇文章
< 1 >
每页显示 20 50 100
Design of Capacitor Bank in Parallel to Photovoltaic Power Plant
1
作者 A. Kalyuzhny B. Reshef +3 位作者 G.Yehuda G.David P. Koulbekov T. Day 《Journal of Energy and Power Engineering》 2014年第5期939-947,共9页
The purpose of the paper is to develop a solution for application of PV (photovoltaic) generators in MV (medium voltage) distribution system without unacceptable voltage changes due to drops of PV power output. Th... The purpose of the paper is to develop a solution for application of PV (photovoltaic) generators in MV (medium voltage) distribution system without unacceptable voltage changes due to drops of PV power output. The proposed solution includes operation of PV with predetermined leading power factor and addition of a capacitor bank in parallel to PV plant in order to compensate the reactive power absorbed by the PV inverters. The analytical expression of required power factor angle is derived. Adding a capacitor bank in parallel to PV power plant may pose a problem because of space limitations. The dimensions and cost of small MV capacitor banks depend significantly on the capacitor bank protection against internal faults. Application of the developed negative-sequence current difference method for the unbalance protection of the capacitor banks enables to achieve a compact and cost-reduced design of the banks connected in parallel to PV power plants. A real-world example of operation of the PV plant in parallel to the capacitor bank with the novel protection scheme is described. 展开更多
关键词 Photovoltaic power plant power quality capacitor bank unbalance protection.
下载PDF
上一页 1 下一页 到第
使用帮助 返回顶部