This paper presents practical distribution system equipment models such as various distributed generators, voltage regulators, and loads for fast three phase unbalanced load flow calculation in distribution systems. T...This paper presents practical distribution system equipment models such as various distributed generators, voltage regulators, and loads for fast three phase unbalanced load flow calculation in distribution systems. The method can calculate voltage and current of distribution systems, in which distributed generators are introduced. The calculation time of the proposed method is about 40 times faster than that of the Newton-Raphson method. Moreover, an introduction effect evaluation tool for distributed generators using the proposed three phase unbalanced load flow calculation is presented. It provides various functions such as a power system network diagram creation function and a voltage profile chart display function. Therefore, the introduction effect evaluation of distributed generators in distribution systems can be evaluated quite easily.展开更多
文摘This paper presents practical distribution system equipment models such as various distributed generators, voltage regulators, and loads for fast three phase unbalanced load flow calculation in distribution systems. The method can calculate voltage and current of distribution systems, in which distributed generators are introduced. The calculation time of the proposed method is about 40 times faster than that of the Newton-Raphson method. Moreover, an introduction effect evaluation tool for distributed generators using the proposed three phase unbalanced load flow calculation is presented. It provides various functions such as a power system network diagram creation function and a voltage profile chart display function. Therefore, the introduction effect evaluation of distributed generators in distribution systems can be evaluated quite easily.