期刊文献+
共找到1篇文章
< 1 >
每页显示 20 50 100
On-line monitoring of dissolved gas-in-oil with FTIR spectra 被引量:1
1
作者 XianyongLiu YunluoLiu LiYue 《Journal of University of Science and Technology Beijing》 CSCD 2003年第4期65-68,共4页
To overcome the disadvantages of conventional DGA (dissolved gas-in-oil)analysis using gas chromatography and other electrochemical sensors, initial researches werecompleted to realize on-line monitoring of dissolved ... To overcome the disadvantages of conventional DGA (dissolved gas-in-oil)analysis using gas chromatography and other electrochemical sensors, initial researches werecompleted to realize on-line monitoring of dissolved gas-in-oil of power transformers using FTIR(Fourier Transform InfraRed) spectroscopy. Gas cell method is used to determine the characteristicabsorption peaks of each diagnostic gas; simple and novel devices and procedures were designed inorder to get measurable samples and spectra of mixed diagnostic gases with known concentration aretaken using long optical path gas cell. The range of wavelength is estimated to be 3.0-13.9 mum fromexperimental spectra data. Hence the corresponding sampling frequency range should be in 536-4288Hz and usable optical materials are suggested. It is concluded that a resolution of 10 cm^(-1) maywell satisfy the monitoring of all diagnostic gases and water content except hydrogen, and thelowest detection limit may be as low as 2Xl0^(-8) to acetylene with a 2.4-meter-long optical length. 展开更多
关键词 FTIR power transformer dissolved gas-in-oil on-line monitoring INFRAREDSPECTRA
下载PDF
上一页 1 下一页 到第